Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 20BH875N0NNNNNC0 in the PowerFlex 700 540 V DC input class at 875 A on frame 10. The decode and ratings come from the drive family's published catalog number explanation and DC input normal-duty table; the option region is not interpreted beyond the enclosure field.
| Specification | Value |
|---|---|
| Catalog number | 20BH875N0NNNNNC0 |
| Family | 20B - PowerFlex 700 |
| Input class | H - 540 V DC |
| Precharge as published | No precharge for H; precharge for P at the same class voltage |
| Rating code | 875 - 875 A |
| Normal-duty rating, DC input table | 875 A, 500 kW |
| Frame as published | 10 |
| Availability per the drive table | Frame sizes 7, 8, 9 and 10 are marked as no longer available for sale |
| Enclosure field | N - not one of the three enclosure codes documented for this family (A, F, G) |
| Option region | Five N characters followed by a final character, not decoded on this page |
This string documents a rating that the drive's own tables mark as no longer available for sale, and that makes the page an archive reference rather than a buying page. The string reads 20B for PowerFlex 700, H for the 540 V DC input class, 875 for the output current in amps, N in the enclosure field and five further N characters before the final character.
The published normal-duty row for code 875 is 875 A at 500 kW on frame 10, and the frame note on the drive's catalog explanation states that frame sizes 7, 8, 9 and 10 are no longer available for sale. Those two statements together are the whole availability answer for this string: the row exists in the table and the model cannot be ordered.
The enclosure field here is N, which is not one of the three enclosure codes the family documents, A for IP20 and NEMA/UL Type 1, F for open and flange mounting, and G for stand-alone and wall mounting. A string whose enclosure field falls outside the documented set is a configuration that the published catalog explanation does not describe, and reading it as a variant of one of the three would be an invention rather than a decode.
The precharge question is answered by the class letter regardless. The family publishes H at 540 V DC without precharge and P at 540 V DC with precharge, and the same split exists at 650 V DC between J and R. At 875 A the DC link capacitance is large, so the external charging arrangement on such an installation is a major piece of panel design rather than an accessory.
What a buyer actually needs from a page like this is the boundary information. An 875 A 540 V DC section cannot be replaced with a new unit of the same rating from this family, because that rating is outside the orderable set. The practical options are a different architecture, a re-rated section, or a used or refurbished unit, and each of those is a different engineering conversation from a spare-part order.
The frame data still carries engineering value for anyone maintaining an existing installation. The terminal tables publish the wire ranges and torque values frame by frame, and the DC terminal group is listed as input power, DC+, DC-, BR1, BR2, PE and the motor connections, which is the set an installer has to land correctly on a bus-fed drive.
There is also a protection-device dimension. The drive documentation publishes input protection device tables for the DC classes, with entries organised by frame, and any replacement of a unit this size has to satisfy the protection coordination of the existing installation rather than the protection table of a hypothetical new one.
The trailing characters are not decoded here. Five N characters followed by a final character is a pattern that the published catalog explanation does not resolve into named option fields for this string, and asserting a meaning would be a guess about what is actually fitted.
For the record, the correct conclusion from this page is not that a 540 V DC 875 A drive never existed. It is that the family publishes the rating, publishes the frame, and publishes the availability note, and the three statements together define an installation that can be maintained but not re-ordered as new.
No price is implied and no lifecycle statement is made beyond the frame note quoted from the drive's catalog explanation.
There is one more consequence worth stating for an engineer inheriting an installation like this. Spare strategy changes at the point where a rating leaves the orderable set: holding one working unit becomes cheaper than holding none, re-rating a section becomes a project rather than a purchase, and the failure mode that used to be a one-week break becomes an indefinite one until an alternative is engineered.
The published documentation is still complete enough to maintain the unit, which is the reassuring half of the situation. The catalog explanation decodes the class, the rating code, the enclosure set and the option fields; the DC input table gives the rating row; the terminal tables give the wire ranges and torques per frame; the protection tables give the coordination basis. Nothing needed to keep the drive running is missing, only the ability to buy a new one of the same rating.
Anyone documenting this string for a customer should separate the two facts clearly: the drive is a published member of the family with a published rating, and the frame note removes it from the sellable range. Mixing those into a single statement of unavailability loses the engineering information that makes the page worth reading.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BH205A0ANNANC0, 20BH260A0AYNANC0, and this drive is listed at 20BH875N0NNNNNC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BH875N0NNNNNC0 is H: 540 V DC input, pre-charge, frames 5-6 in the catalog explanation, with 875 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.
Catalog numbers held on this site that sit closest to 20BH875N0NNNNNC0, ordered by character overlap.
Site catalogue: plc-vip.com. This page is 20BH875N0NNNNNC0.