Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 20BH260A0AYNANC0 in the PowerFlex 700 540 V DC input class at 260 A on frame 6. The decode and ratings come from the drive family's published catalog number explanation and DC input normal-duty table; the option region is not interpreted beyond the enclosure field.
| Specification | Value |
|---|---|
| Catalog number | 20BH260A0AYNANC0 |
| Family | 20B - PowerFlex 700 |
| Input class | H - 540 V DC |
| Precharge as published | No precharge for H; precharge for P at the same class voltage |
| Rating code | 260 - 260 A |
| Enclosure field | A - IP20, NEMA/UL Type 1 |
| Normal-duty rating, DC input table | 260 A, 132 kW |
| Frame | 6 |
| Position in the orderable range | Top of the 540 V DC range still offered |
| Relation to the other listing of this rating | This string differs from 20BH260A0ANNANC0 in one character of the option region |
Two listings of the same 260 A rating exist on this platform, and they are not duplicates: the strings differ by one character in the option region. This page documents the second of them, 20BH260A0AYNANC0, and the other is 20BH260A0ANNANC0.
The shared part of the string reads 20B for PowerFlex 700, H for the 540 V DC input class, 260 for the output current in amps, and A for the enclosure, which the family defines as IP20 and NEMA/UL Type 1. The published normal-duty row for code 260 is 260 A at 132 kW on frame 6 in the DC input table.
The differing character sits in the option region, where this platform's strings carry brake IGBT, communication slot, control type, feedback and documentation. Which of those fields the single character belongs to is not assigned on this page, because the field positions in this family shift with string length and a wrong assumption about a communication slot is a wrong assumption about a card in a live panel.
What can be said without guessing is the consequence: a buyer holding one of these two strings and ordering the other is ordering a drive that differs in at least one factory-selected option, and that difference will appear as a missing or extra function rather than as a different current. On a spare-part order that is the difference between a drop-in replacement and a commissioning job.
The rating itself is the top of the orderable range for this DC class. The DC table lists 260 A at 132 kW as the last row that is still offered, and the rows above it, at 365 A and beyond, carry the manual's note that those models are no longer available for sale.
The precharge question follows the class letter, not the option character. The family publishes H at 540 V DC without precharge and P at 540 V DC with precharge, so this drive depends on the system for its charging arrangement whatever the option block says, and the panel has to provide for it.
Frame 6 fixes the mechanical facts, and the terminal data for frames 5 and 6 lists input power, DC+, DC-, BR1, BR2, PE and motor connections together with the wire range and torque per frame. On a 132 kW drive the DC terminals are the interface to the bus, and the torque figure is the difference between a joint that lasts and one that heats.
The enclosure field A means IP20 and NEMA/UL Type 1, so the cabinet carries both the protection and the airflow. At this rating the cabinet is also dissipating the losses of the bus arrangement, which is why the thermal calculation for a common-bus panel is a panel-level task rather than a drive-level one.
The practical instruction for this string is to quote all of it. A truncated order that stops at the rating code, or that drops the trailing character, will produce a drive that satisfies the current requirement and not the option requirement, and the mismatch will not be visible until the panel is powered.
No lifecycle statement and no price is implied. The row, the class definition, the precharge pairing, the frame and the availability note about larger rows are quoted from the drive family's published tables.
A spare-part decision on this string has one extra step compared with the AC classes. On an AC drive the supply voltage is a property of the site; on a DC drive the bus is a property of the system, and the same nominal class can present a different voltage depending on how many sections are regenerating when the measurement is taken. Recording the measured bus alongside the catalog number is the practice that makes a later reorder possible.
The documentation field at the end of the string is small and consequential: a drive ordered without manual or without a shipping package arrives as exactly that, and a maintenance store that counts on documentation arriving in the carton should not assume it. The family lists manual and shipping package as separate option characters, so both are decisions taken at order time.
Floor time is also part of the picture at 132 kW. The frame determines the heatsink and the lifting points, and the cabinet determines whether the drive can be slid in or has to be rigged. Neither is visible in the catalog number, and both are cheaper to settle at layout than at installation.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BH205A0ANNANC0, 20BH875N0NNNNNC0, and this drive is listed at 20BH260A0AYNANC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BH260A0AYNANC0 is H: 540 V DC input, pre-charge, frames 5-6 in the catalog explanation, with 260 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.
The closest catalog numbers to 20BH260A0AYNANC0 in this shop, sorted by how many characters they share.
Site catalogue: plc-vip.com. This page is 20BH260A0AYNANC0.