Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier Allen Bradley PowerFlex 20BH260A0ANNANC0 supplier

Large Image :  Allen Bradley PowerFlex 20BH260A0ANNANC0

Product Details:

Place of Origin: Made in MEXICO
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PowerFlex 20BH260A0ANNANC0

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $9348.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Western Union and Paypal.
Supply Ability: 2 PCS
Detailed Product Description

20BH260A0ANNANC0

This page documents catalog number 20BH260A0ANNANC0, a PowerFlex 700 drive in the 540 V DC input class at 260 A on frame 6. The decode and ratings come from the drive family's published catalog number explanation and DC input normal-duty table; the trailing option block is not interpreted beyond the enclosure field.

Decode and published ratings

SpecificationValue
Catalog number20BH260A0ANNANC0
Family (first three characters)20B - PowerFlex 700
Input class (fourth character)H - 540 V DC
Precharge as published for this classH is listed with no precharge; the P entry at the same 540 V DC is listed with precharge
Rating code (fifth to seventh)260 - 260 A
Enclosure field (fourth block)A - IP20, NEMA/UL Type 1
Normal-duty rating, DC input table260 A, 132 kW
Position in the orderable rangeTop of the 540 V DC range still offered on this platform
Frame as published6
Larger rows in the same table365 A, 415 A, 600 A, 730 A and 875 A carry the note that those models are no longer available for sale
Output specification basisDirect-current output rating at the motor terminals, as the DC classes are specified

What the DC class decides and what it leaves to the system

This is the largest 540 V DC code in the 20B range that is still offered, and that single fact is worth more to a buyer than the rating row. The string reads 20B for the family, H for the 540 V DC input class, 260 for the output current in amps, and A for the enclosure, which the family defines as IP20 and NEMA/UL Type 1.

The published normal-duty row for this code is 260 A at 132 kW on frame 6 in the DC input table. The rows below it in the same table stop at 205 A, and the rows above it, at 365 A and beyond, carry the manual's note that those models are no longer available for sale. A 260 A drive therefore sits at the top of the orderable range for this DC class on this platform.

The precharge distinction applies here with more force than at smaller ratings. The family publishes H as 540 V DC without precharge and P as 540 V DC with precharge, alongside the same split at 650 V DC between J and R. A 132 kW drive on a common bus has a DC link capacitance that makes uncontrolled energisation a substantial event, so the system's precharge arrangement is a design item rather than a detail.

Common-bus architecture is the natural home for a drive this size. Several sections share one rectifier or one regenerative front end, energy flows between motoring and regenerating sections, and the individual drive's catalog number settles the current, the frame and the class while the system settles the bus, the charging and the fault coordination.

Frame 6 is the largest frame still available on this platform, so a project that expects to add a larger section later will not find one above this in the same class; the larger rows in the table exist as documentation of what was once offered. That is a planning consideration rather than a specification one, and it belongs in the file before the panel is cut.

Enclosure A as IP20 and NEMA/UL Type 1 places the protection on the cabinet, and at 132 kW the thermal design of that cabinet is a serious engineering task. The drive's published ambient figure is measured at the drive; the cabinet's job is to make that figure true at the drive rather than at the room.

The trailing option block carries brake IGBT, communication slot, control type, feedback and documentation. The brake field matters on a DC-bus drive for a structural reason: a drive with a brake IGBT can dissipate energy into a resistor, and a drive without one depends on the bus absorbing it. On a shared bus that decision is made at the system level, but the drive has to be ordered to match it.

What this page does not do is assert a lifecycle status beyond what the table states about larger rows. The statement quoted is about models above 260 A, not about this one.

The check before ordering is the same as for any DC class: measure the bus, establish where the precharge sits, and confirm the duty. At 260 A a wrong assumption about the bus is an expensive assumption, because the drive is not a shelf item and the lead time is real.

Adjacent codes are 205 A on frame 6 and 365 A in the unavailable region. The step down stays on the same frame; the step up leaves the orderable range entirely, which makes this code the boundary of the family rather than a midpoint in it.

Being the boundary has one practical benefit and one practical cost. The benefit is that a spare at this code is the largest that can be bought, so a replacement decision does not have to consider a bigger frame that no longer exists; the cost is that a project which outgrows this section has no next step inside the class, and the answer becomes a different architecture rather than a different catalog number.

At 132 kW the heat and the bus current make the enclosure design a joint exercise between the drive supplier's installation data and the panel builder's thermal calculation. A cabinet dimensioned for the room rather than for the drive is the most common cause of early failures at this size, and it is not covered by the catalog number in any of its fields.

The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Neighbouring codes in the same class are listed at 20BH105A0AYNANC0, 20BH140A0ANNANC0, 20BH170A0ANNANC0, and this drive is listed at 20BH260A0ANNANC0.

The twelve 20B voltage codes, and the frames each one is built on

The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.

CodeVoltage ratingFrames built onWhere the class is used
B240 V AC, 3-phase, 50/60 Hz0-6208...240 V supply, the North American low-voltage class
C400 V AC, 3-phase, 50/60 Hz0-6380...415 V supply, the European standard class
D480 V AC, 3-phase, 50/60 Hz0-6440...480 V supply, the widest rating ladder of the series
E600 V AC, 3-phase, 50/60 Hz0-6575...600 V supply, Canada and heavy industry
F690 V AC, 3-phase, 50/60 Hz5-6690 V supply, and only on the larger frames
H540 V DC input, pre-charge5-6fed from a 540 V DC bus, pre-charge circuit built in
J650 V DC input5-6650 V DC common DC bus, no pre-charge letter
N325 V DC input (Y), pre-charge5-6325 V DC bus, common-bus configuration
P540 V DC input (Y), pre-charge5-8540 V DC common bus, the widest DC frame range
R650 V DC input (Y), pre-charge5-8650 V DC common bus, frames 5 through 8
T810 V DC input (Y), pre-charge5-6810 V DC bus for 600 V class front ends
W932 V DC input (Y), pre-charge5-6932 V DC bus for 690 V class front ends

Where this page sits: The fourth character of 20BH260A0ANNANC0 is H: 540 V DC input, pre-charge, frames 5-6 in the catalog explanation, with 260 A in the rating field.

What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.

Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.

Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.

Contact Details
PLC-VIP SHOP