logo
Home ProductsAB Drives & Motors

Allen Bradley PowerFlex 20BH170A0ANNANC0

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PowerFlex 20BH170A0ANNANC0

China Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier
Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier Allen Bradley PowerFlex 20BH170A0ANNANC0 supplier

Large Image :  Allen Bradley PowerFlex 20BH170A0ANNANC0

Product Details:

Place of Origin: Made in MEXICO
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PowerFlex 20BH170A0ANNANC0

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $6068.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Western Union and Paypal.
Supply Ability: 2 PCS
Detailed Product Description

20BH170A0ANNANC0

This page documents catalog number 20BH170A0ANNANC0, a PowerFlex 700 drive in the 540 V DC input class at 170 A on frame 6. The decode and ratings come from the drive family's published catalog number explanation and DC input normal-duty table; the trailing option block is not interpreted beyond the enclosure field.

Decode and published ratings

SpecificationValue
Catalog number20BH170A0ANNANC0
Family (first three characters)20B - PowerFlex 700
Input class (fourth character)H - 540 V DC
Precharge as published for this classH is listed with no precharge; the P entry at the same 540 V DC is listed with precharge
Rating code (fifth to seventh)170 - 170 A
Enclosure field (fourth block)A - IP20, NEMA/UL Type 1
Normal-duty rating, DC input table170 A, 90 kW
Frame as published6
Larger rows in the same table365 A, 415 A, 600 A, 730 A and 875 A carry the note that those models are no longer available for sale
Output specification basisDirect-current output rating at the motor terminals, as the DC classes are specified

What the DC class decides and what it leaves to the system

This code sits on frame 6 in the 540 V DC range, and the frame is the fact that dominates its installation. The string reads 20B for PowerFlex 700, H for the 540 V DC input class, 170 for the output current in amps, and A for the enclosure field, which the family defines as IP20 and NEMA/UL Type 1.

The published normal-duty row for this code is 170 A at 90 kW on frame 6 in the DC input table. Direct-current output at the motor terminals is how the DC classes are specified, so the 170 A figure is the drive's output current and not an alternating input current.

The precharge split is the part of the class definition that a spare order most often gets wrong. The family publishes H as 540 V DC without precharge and P as 540 V DC with precharge, and the same distinction exists at 650 V DC between J and R. A frame 6 drive at 170 A connected to a common bus without an external precharge arrangement is a drive whose first energisation may take out the upstream protection rather than the drive.

Frame 6 is the top of the range that is still available. The DC input table continues past this code into rows at 205 A, 260 A, and then at 365 A, 415 A, 600 A, 730 A and 875 A, and the manual marks those larger rows as no longer available for sale. A 170 A drive is therefore in the range where the frame is the largest that can still be bought, which is a consideration for a project that expects to scale a bus upwards.

At 90 kW on a shared DC bus the drive is usually one section of a multi-drive system rather than a standalone unit. The engineering questions that follow are system questions: how the bus is charged, how the sections are coordinated on fault, and what the bus capacitance is relative to the total connected power.

Enclosure A as IP20 and NEMA/UL Type 1 puts the protection and the thermal duty on the cabinet. On a frame 6 unit the cabinet's airflow and clearance are part of the drive's rating, and the difference between a cabinet that meets the room specification and one that meets the drive's own requirement is the difference between a ten-year drive and a five-year one.

The trailing option block carries brake IGBT, communication slot, control type, feedback and documentation, each defined in its own table. This page does not decode them, because the field positions in this family shift with the length of the string.

What an engineer should verify before ordering is three things that the catalog number does not contain: the measured bus voltage, whether the system provides precharge elsewhere, and the duty the section actually runs. On a DC bus the first and second decide whether the unit can be connected at all.

Adjacent codes in this class are 140 A on frame 5 and 205 A on frame 6. The step from 140 to 170 crosses a frame boundary and the step from 170 to 205 does not, so the two substitutions have different mechanical consequences despite looking similar on a current table.

No lifecycle statement and no price is implied. The row, class definition, precharge pairing, frame and the note about larger unavailable rows are all quoted from the drive family's published tables.

Frame 6 units at this rating are installed rather than mounted, and the practical consequence is that the mechanical drawing matters as much as the electrical one. Clearance for the heatsink, cable entry for the motor and routing for the bus connection are all frame decisions, and they are settled before the panel is cut rather than after the drive arrives.

The duty question on a bus-fed section is often a question about the machine cycle rather than about the process. A section that accelerates and decelerates many times an hour loads the bus differently from one that runs for hours at a steady speed, and the normal-duty row assumes the second pattern more comfortably than the first.

The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Neighbouring codes in the same class are listed at 20BH105A0AYNANC0, 20BH140A0ANNANC0, 20BH260A0ANNANC0, and this drive is listed at 20BH170A0ANNANC0.

The twelve 20B voltage codes, and the frames each one is built on

The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.

CodeVoltage ratingFrames built onWhere the class is used
B240 V AC, 3-phase, 50/60 Hz0-6208...240 V supply, the North American low-voltage class
C400 V AC, 3-phase, 50/60 Hz0-6380...415 V supply, the European standard class
D480 V AC, 3-phase, 50/60 Hz0-6440...480 V supply, the widest rating ladder of the series
E600 V AC, 3-phase, 50/60 Hz0-6575...600 V supply, Canada and heavy industry
F690 V AC, 3-phase, 50/60 Hz5-6690 V supply, and only on the larger frames
H540 V DC input, pre-charge5-6fed from a 540 V DC bus, pre-charge circuit built in
J650 V DC input5-6650 V DC common DC bus, no pre-charge letter
N325 V DC input (Y), pre-charge5-6325 V DC bus, common-bus configuration
P540 V DC input (Y), pre-charge5-8540 V DC common bus, the widest DC frame range
R650 V DC input (Y), pre-charge5-8650 V DC common bus, frames 5 through 8
T810 V DC input (Y), pre-charge5-6810 V DC bus for 600 V class front ends
W932 V DC input (Y), pre-charge5-6932 V DC bus for 690 V class front ends

Where this page sits: The fourth character of 20BH170A0ANNANC0 is H: 540 V DC input, pre-charge, frames 5-6 in the catalog explanation, with 170 A in the rating field.

What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.

Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.

Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)