Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 20BF119A0ANNANC0, a PowerFlex 700 drive in the 690 V AC input class at 119 A on frame 6. The decode and the published rating come from the drive family's catalog number explanation and its 690 V normal-duty table; the line reactor pairing is stated as unpublished rather than filled in.
| Specification | Value |
|---|---|
| Catalog number | 20BF119A0ANNANC0 |
| Family (first three characters) | 20B - PowerFlex 700 |
| Input class | F - 690 V AC, three-phase, frames 5-6 only |
| Rating code | 119 - 119 A |
| Normal-duty rating, 690 V table | 119 A, 110 kW |
| Frame | 6 |
| Enclosure field | A - IP20, NEMA/UL Type 1 |
| Brake field | N - no brake IGBT; optional on frames 4-6 |
| Voltage window, 690 V class | Motor rated 690 V, full power 690-759 V, operating 475-759 V |
| Line reactor pairing at 690 V | Not published in the drive table, which covers 240, 480 and 600 V only |
| Other listing of this exact string | A second platform entry carries the identical string |
The platform lists this string twice, with identical characters in both entries, and this page documents the specification once rather than twice. The string reads 20B for PowerFlex 700, F for the 690 V AC three-phase input, 119 for the output current in amps, A for the enclosure and N in the brake field.
The published normal-duty row for code 119 in the 690 V, 50 Hz table is 119 A at 110 kW on frame 6. The rows around it are 98 A at 90 kW and 142 A at 132 kW, both also on frame 6, so the upper part of the 690 V range sits on one frame and the current codes step within it rather than across frames.
The 690 V class has its own voltage window and it is not the 600 V window scaled up. The family publishes the class at a motor rating of 690 V, full power from 690 to 759 V and operation from 475 to 759 V, while the 600 V class is published at 575 V with full power from 575 to 660 V and operation from 432 to 660 V. A drive chosen on one window is not a drive chosen on the other, and the two classes are not interchangeable by arithmetic on paper.
The line reactor pairing for 690 V is the field where a number is most likely to be invented, and this page does not invent one. The drive's published reactor table covers 240 V, 480 V and 600 V inputs; the 690 V rows are absent. A 690 V installation therefore needs the current revision of the documentation for that selection rather than a value scaled from the 600 V column.
The enclosure field A is IP20 and NEMA/UL Type 1, with F and G covering open and flange mounting and stand-alone wall mounting. On frame 6 at 110 kW the cabinet carries the airflow and the protection, and at this rating the thermal design of the enclosure is a real engineering task rather than a selection exercise.
The brake field reads N, which the published rule makes definite: no brake IGBT, and the option is available on frames 4 to 6. On a 690 V installation with a machine that regenerates, that has to be matched by a braking arrangement elsewhere or by a process that does not need one.
The frames in the 690 V class stop at 6, unlike the DC and 480 V classes which extend further. That means a 110 kW section is in the part of the range where a modest increase in power no longer requires a larger frame, which is a maintenance advantage and a growth limitation at the same time.
What this page deliberately does not do is express the rating in horsepower. The 690 V table is published in amps and kW, and a horsepower figure derived from kW is arithmetic rather than a published pairing, which matters when a buyer is comparing against a North American specification written in horsepower.
The fact that two platform entries carry the same string is worth stating plainly, because it changes how a buyer should treat them: they are one specification, and an enquiry answered from either should produce the same decode. Where duplicate entries exist for a string, the useful work is the decode, not a second description.
The remaining option characters carry the communication slot, the control type, feedback and documentation, and they are not decoded here. The family's strings vary in length and a field position is not a safe inference without the matching documentation.
No lifecycle statement and no price is implied. The class definitions, the voltage windows, the normal-duty row, the frame, the brake rule and the absence of 690 V reactor rows are quoted from the drive family's published documentation.
There is also a commissioning point that belongs with any 690 V section: the operating window allows the drive to run well below nominal motor voltage, which is useful for a machine that accelerates a large inertia but also means the incoming supply is measured rather than assumed. A section specified at 690 V placed on a 600 V distribution is a mismatch that the class letter records and the rating row cannot correct.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BW052A0ANNANC0, 20BW098A0ANNANC0, 20BW098A0AYNANC0, 20BW142A0ANNANC0, and this drive is listed at 20BF119A0ANNANC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BF119A0ANNANC0 is F: 690 V AC, 3-phase, 50/60 Hz, frames 5-6 in the catalog explanation, with 119 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.