This page documents catalog number 20BF082A0ANNANC0, a PowerFlex 700 drive in the 690 V AC class at 82 A on frame 5. The decode and ratings come from the drive family's published catalog number explanation and 690 V normal-duty table; the trailing option block is not interpreted beyond the enclosure field.
| Specification | Value |
|---|---|
| Catalog number | 20BF082A0ANNANC0 |
| Family (first three characters) | 20B - PowerFlex 700 |
| Voltage class (fourth character) | F - 690 V AC, three-phase, frames 5-6 only |
| Rating code (fifth to seventh) | 082 - 82 A |
| Enclosure field (fourth block) | A - IP20, NEMA/UL Type 1 |
| Published input protection data | 79 kVA input, 82 A continuous, 90 A for 60 s, 123 A for 3 s, PWM 2 kHz, 50 degC ambient |
| Normal-duty rating, 690 V 50 Hz table | 82 A, 75 kW |
| Frame as published | 5 |
| Horsepower equivalent | approximately 100 Hp (arithmetic from kW, not a published Hp pairing for this class) |
| Full power range, 690 V class | 690...759 V |
| Operating range, 690 V class | 475...759 V |
| Nominal motor voltage | 690 V |
| Line reactor pairing for 690 V | Not printed in the reactor tables retrieved (those cover 240 V, 480 V and 600 V) |
| Brake IGBT availability | Standard on frames 0-3, optional on frames 4-6 |
This code is the one 690 V drive in the sampled range for which the published data includes input protection figures rather than only a rating row, and that makes it the most useful page in the group to read from. The string reads 20B for PowerFlex 700, F for 690 V AC three-phase, 082 for the output current in amps, and A in the enclosure field, which is IP20 and NEMA/UL Type 1.
The 690 V, 50 Hz normal-duty table gives this code 82 A at 75 kW on frame 5. The published input protection table adds the electrical context: an input rating of 79 kVA, a continuous output current of 82 A, a 60 second output current of 90 A and a 3 second output current of 123 A, at a PWM frequency of 2 kHz and an ambient of 50 degrees Celsius for the frame.
Those three current figures are the ones an engineer actually uses. The continuous figure sizes the cable and the motor; the 60 second figure is the overload the drive will hold for a minute, which is what a starting sequence needs; and the 3 second figure is the short-time surge capability, which is what a jam or a direct-on-line transition asks for. A drive quoted on its continuous rating alone has not been quoted against the load.
The 690 V class on this platform exists only on frames 5 and 6, and this code is on frame 5. The voltage envelope published for the class is a nominal motor voltage of 690 V, a full power range of 690 to 759 V and an operating range of 475 to 759 V. The bottom of that band is 215 V below nominal, which is why a 690 V drive applied to a sagging supply is a drive that derates rather than a drive that fails outright.
The line reactor pairing is the gap on this page rather than an omission. The reactor tables in the drive's published data are printed for the 240 V, 480 V and 600 V classes; a 690 V pairing for this code does not appear in the tables retrieved here. Where a project specification calls for 3 percent impedance on the input, the number has to come from the current revision of the drive documentation.
Enclosure A means IP20 and NEMA/UL Type 1, which on a frame 5 unit is a statement that the cabinet is the protection. The thermal design of that cabinet carries the drive's losses, and the published 50 degree ambient figure for the frame is an ambient at the drive rather than at the room.
The trailing option block is not decoded here. Brake IGBT, communication slot, control type, feedback and documentation each have a table of their own, and the ordering of those fields is not uniform across lengths of catalog string in this family.
What makes this page worth reading in a purchasing conversation is the protection data, because it lets a buyer check a claim. If a supplier quotes this code for a load that draws 95 A continuously, the 82 A continuous figure is the answer, and no interpretation of the catalog number changes it.
A drive of this size is usually the largest single load in its section, so the question of what happens during a supply disturbance is a process question rather than an electrical one. The 60 second and 3 second figures above are the published envelope for that discussion.
Adjacent codes are 060 at 60 A and 098 at 98 A, on frames 5 and 6 respectively at the boundary. The frame changes at 098, which changes the mounting and the cabinet volume, so the step from this code to the next is not a drop-in replacement.
The 2 kHz PWM frequency in the protection table is worth naming for a practical reason. Carrier frequency, motor cable length and drive losses trade against each other, and a drive whose published data fixes a carrier figure for its protection ratings is telling an engineer what the thermal envelope assumes. Raising the carrier for acoustic reasons moves the losses, and the enclosure design has to absorb that.
Seventy-five kilowatts on a 690 V supply is a size that appears in European process plants on pumps and on fans of substantial size, where the motor is often a 690 V machine rather than a 400 V machine on a transformer. That is the case this code exists for, and it is also the case where measuring the supply at the terminals before ordering is worth the ten minutes it takes.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Neighbouring entries and ratings are listed at 20BF060A0AYNANC0, 20BF098A0ANNANC0, 20BF098A0AYNANC0, and this drive is listed at 20BF082A0ANNANC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BF082A0ANNANC0 is F: 690 V AC, 3-phase, 50/60 Hz, frames 5-6 in the catalog explanation, with 082 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.