20BE125A0ANNAND0 is a PowerFlex 700 drive, catalog code b=E: 600 V AC, 3-phase, 50/60 Hz.
The three digits after the voltage letter are the output current in amps - here 125 A. Rockwell publishes no power rating for this catalog number, so this page states the current rating only.
Quick answer. 20BE125A0ANNAND0 is a PowerFlex 700 drive, 600 V AC, normal duty, frame 0-6 range for this voltage class, A - IP 20, NEMA/UL Type 1, with conformal coating.
| 20AC037A0NYNACC0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE017A0AYNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE027A0AYNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE052A0AYNANA0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE062A0ANNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE062A0AYNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE125A0ANNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE2P7A0AYNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BE6P1A0AYNAND0 | Frame 0-6 range for this voltage class | IN STOCK |
| 20BF060A0AYNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BF082A0ANNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BF098A0ANNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BF098A0AYNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BF119A0ANNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BF142A0ANNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
| 20BH105A0AYNANC0 | Frame 5-6 range for this voltage class | IN STOCK |
Catalog number |
20BE125A0ANNAND0 |
Voltage rating (b) |
E - 600 V AC, 3-phase, 50/60 Hz |
Output current rating (c) |
125 A |
Frame size |
Frame 0-6 range for this voltage class |
Enclosure (d) |
A - IP 20, NEMA/UL Type 1, with conformal coating |
HIM (e) |
0 - Blank cover |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
N - No brake IGBT |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
A - CE filter fitted, CM choke fitted |
Comm slot (j) |
N - None |
Control and I/O (k) |
D - Vector control, 115 V AC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
125 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell rating tables |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), E (voltage), 125 (output current in amps), then nine option positions d to l.
Here: d=A, e=0, f=A, g=N, h=N, i=A, j=N, k=D, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): IP 20, NEMA/UL Type 1, with conformal coating.
HIM (e): Blank cover. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): No brake IGBT. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): CE filter fitted, CM choke fitted. Comm slot (j): None. Control and I/O (k): Vector control, 115 V AC I/O. Feedback (l): No feedback.
A 20BD drive is the 480 V AC three-phase member of the PowerFlex 700 family: three-phase input, three-phase output, 0 to rated motor voltage on the output.
The current code is the drive output current in amps, so the same code reappears across the 400 V and 480 V families with different kW values - the kW figure here is the 480 V one.
Sensorless vector control with full tuning is standard; the k position decides whether the I/O is 24 V DC/AC or 115 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BE125A0ANNAND0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BE125A0ANNAND0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BE125A0ANNAND0?
PowerFlex 700 drive, 600 V AC, 3-phase, 50/60 Hz, 125 A output.
What is the output current of 20BE125A0ANNAND0?
125 A.
What does the E code mean?
600 V AC, 3-phase, 50/60 Hz.
Does 20BE125A0ANNAND0 have a communication option?
None.
What enclosure is 20BE125A0ANNAND0?
IP 20, NEMA/UL Type 1, with conformal coating.
Related catalog numbers in the same rating code as 20BE125A0ANNAND0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20AC037A0NYNACC0 (Frame 0-6 range for this voltage class) · 20BE017A0AYNAND0 (Frame 0-6 range for this voltage class) · 20BE027A0AYNAND0 (Frame 0-6 range for this voltage class) · 20BE052A0AYNANA0 (Frame 0-6 range for this voltage class) · 20BE062A0ANNAND0 (Frame 0-6 range for this voltage class) · 20BE062A0AYNAND0 (Frame 0-6 range for this voltage class) · 20BE2P7A0AYNAND0 (Frame 0-6 range for this voltage class) · 20BE6P1A0AYNAND0 (Frame 0-6 range for this voltage class) · 20BF060A0AYNANC0 (Frame 5-6 range for this voltage class)
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BE125A0ANNAND0 is E: 600 V AC, 3-phase, 50/60 Hz, frames 0-6 in the catalog explanation, with 125 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.
Related models, options and spare parts for this range are listed in the Allen-Bradley PowerFlex drives and motors category.