Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier Allen Bradley PowerFlex 20BE052A0AYNANA0 supplier

Large Image :  Allen Bradley PowerFlex 20BE052A0AYNANA0

Product Details:

Place of Origin: Made in MEXICO
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PowerFlex 20BE052A0AYNANA0

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $5816.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Western Union and Paypal.
Supply Ability: 2 PCS
Detailed Product Description

20BE052A0AYNANA0

This page documents catalog number 20BE052A0AYNANA0, a PowerFlex 700 drive in the 600 V AC class at 52 A. The decode and ratings come from the drive family's published catalog number explanation and line reactor tables; the trailing option block is not interpreted beyond the enclosure field.

Decode and published ratings

SpecificationValue
Catalog number20BE052A0AYNANA0
Family (first three characters)20B - PowerFlex 700
Voltage class (fourth character)E - 600 V AC, three-phase
Rating code (fifth to seventh)052 - 52 A
Enclosure field (fourth block)A - IP20, NEMA/UL Type 1
Heavy-duty rating as published40 Hp
Normal-duty rating as published50 Hp
Input line reactor, heavy duty1321-3R45-B
Output line reactor, heavy duty1321-3R55-B
Input line reactor, normal duty1321-3R55-B
Output line reactor, normal duty1321-3R55-B
Full power range, 600 V class frames 0-4575...660 V
Operating range, 600 V class frames 0-4432...660 V
Nominal motor voltage575 V
Brake IGBT availabilityStandard on frames 0-3, optional on frames 4-6
Low voltage directive note600 V class below 77 A (frames 0-4) declared to meet the Low Voltage Directive; EMC compliance determined by the user

What the number fixes and what it leaves to the nameplate

This number is the 52 A step of the 600 V PowerFlex 700 range, and it is the point where the two reactor numbers in the table come closest together. The string reads 20B for the family, E for 600 V AC three-phase, 052 for the output current in amps, and A in the enclosure field, which the family's catalog number explanation defines as IP20, NEMA/UL Type 1.

The published pairing for this code is a heavy-duty rating of 40 Hp with a 1321-3R45-B input reactor and a 1321-3R55-B output reactor, and a normal-duty rating of 50 Hp with the 3R55-B part on both sides. The input reactor moving from 3R45 to 3R55 between the two duties is the whole difference between the columns at this rating, and it is the number a panel builder needs before mounting the reactors.

PowerFlex 700 drives publish both a heavy-duty and a normal-duty figure for the same catalog number and select between them in programming rather than at the time of purchase. So a 20BE052 can correctly be described as a 40 Hp drive or as a 50 Hp drive, and the two descriptions are of the same hardware under different duty assumptions.

The distinction has an electrical cost that shows up late if it is ignored. A 50 Hp normal-duty rating assumes a load whose torque falls with speed, which is the profile of a centrifugal pump or a fan. A 40 Hp heavy-duty rating assumes a load that keeps asking for torque at low speed, which is the profile of a positive-displacement pump, a screw conveyor or a loaded mixer. The same drive serves both, but not at the same horsepower.

The voltage envelope for the 600 V class on frames 0 to 4 is a full power range of 575 to 660 V against a nominal motor voltage of 575 V, and an operating range of 432 to 660 V. Below the full power floor the drive is linearly derated, so the 52 A rating is a figure at nominal voltage rather than at the bottom of the window.

The compliance sentence for this class applies here: 600 V drives below 77 A on frames 0 to 4 are declared to meet the Low Voltage Directive, with EMC compliance determined by the user. A 52 A drive is inside that band, and the margin to the 77 A boundary is the reason this code and the 62 A code above it are treated differently in a declaration of conformity.

Enclosure is the one trailing field this page reads with confidence, because the enclosure table in the family's catalog explanation is explicit that A means IP20 and NEMA/UL Type 1. A panel-mounted drive in an IP20 enclosure is a drive that relies on the cabinet for its protection, which is a statement about the installation rather than about the drive.

The rest of the trailing block is not decoded here. Brake, communication slot, control type and documentation each have their own table, and the ordering of those fields is not uniform across the family, so a claim about them inferred from this string would be a claim about a machine's wiring.

What a buyer should do with this page is compare the fitted reactor rather than the enclosure. A drive with a 3R45 on the input is running the heavy-duty pairing for this code; a 3R55 in both positions is the normal-duty pairing. That check takes a torch and thirty seconds and answers the duty question that the catalog number leaves open.

Adjacent ratings in the class are 041 at 41 A and 062 at 62 A, and the reactor pair changes at both steps. A substitution from 041 to 052 changes the input reactor from the 3R35 group to the 3R45 group, which is a frame and mounting decision as much as an electrical one.

No lifecycle statement and no price is implied by this page. The ratings, reactor numbers, voltage window and enclosure definition are quoted from the drive family's own published tables.

The cabinet consequence of an IP20 drive at this rating is thermal rather than electrical. Fifty-two amps of 600 V output is a heat source that the enclosure has to move, and the mounting clearances in the drive's installation data assume the airflow the enclosure was designed to provide. A drive that is correctly sized and incorrectly ventilated trips on its own temperature long before it trips on current.

There is one more practical note about the reactor pair at this code: the output reactor number changes between the duty columns while the input number changes only once. A panel being laid out for a spare therefore has space allocated for two different output reactors depending on which duty the machine runs, and the drawing should say which.

Fifty horsepower on a 600 V supply is a size that appears on process pumps and on air-handling equipment where the motor is often the largest single load in the section. That is the reason the normal-duty column exists for this code at all: at this size the variable-torque assumption is the common case, and the constant-torque assumption is the exception that has to be checked rather than assumed.

The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. The neighbouring ratings and entries are listed at 20BE062A0AYNAND0, 20BE062A0ANNAND0, and this drive is listed at 20BE052A0AYNANA0.

Neighbouring catalog numbers in this class

Catalog numbers held on this site that sit closest to 20BE052A0AYNANA0, ordered by character overlap.

Site catalogue: plc-vip.com. This page is 20BE052A0AYNANA0.

Sources. Rockwell publishes the technical data for the PowerFlex 700 range as 20B-TD001, and the installation instructions split by frame size, with 20B-IN019 covering frames 0…6 and 20B-IN014 covering frames 7…10. The ratings, current figures and ordering characters quoted on this page for 20BE052A0AYNANA0 follow those publications, and the user manual for the frames covered here is 20B-UM001.