This page documents catalog number 20BD730N0ANNNNC0, a PowerFlex 700 drive on the 480 V three-phase class at 730 A continuous output. It sits on frame 9, and frames 7 to 10 of this line are no longer available for sale, so the page records the rating that exists in installed plants rather than a product a new project can order.
| Field | Value |
| Catalog number | 20BD730N0ANNNNC0 |
| Family (characters 1-3) | 20B - PowerFlex 700 adjustable frequency AC drive |
| Voltage class (character 4) | D - 480 V AC three-phase |
| Rating code (characters 5-7) | 730 - 730 A continuous |
| Frame class | frame 9, no longer available for sale |
| Enclosure (character 8) | N |
| Brake IGBT (character 11) | N - no brake IGBT |
| Control (character 13) | N |
The current code is readable from the string: at this size the three characters are the continuous amps, so the 730 in the code is 730 A. That figure is a starting condition, not an ordering answer. Frames 7 to 10 were withdrawn, and the withdrawal is an ordering fact rather than a technical one: the drives exist in installed plants, but a replacement has to come from the current large-frame family, with its own terminal, enclosure and reactor tables rather than the frame 0 to 6 tables on this page.
A like-for-like replacement therefore starts from the motor and the duty, not from the old catalog number. The load current, the overload profile the process needs, the available cabinet space and the reactor already in the line are the four inputs the replacement selection needs, and the old string supplies only the third decimal place of the first one.
The 480 V class itself is unchanged in what it publishes: nominal motor voltage 460 V, full power from 460 to 528 V, operating range from 342 to 528 V with linear derating below the full-power floor. A replacement drive on this class is compared to the old unit on those numbers rather than on horsepower alone.
Character 8 reads N for enclosure, character 11 reads N for the brake IGBT, and character 13 reads N for control. Positions 9, 10 and 14 to 16 read 0 A NC0 and are carried rather than translated, because the option tables resolve them per code.
The enclosure on a withdrawn frame is the part of this page that matters most in practice. A large frame in IP20 Type 1 and the same rating in IP54 stand-alone or open/flange are different physical products with different cabinet consequences, so a spare carried on a pallet from another site is the same rating and possibly the wrong mounting. The character is the only place that records which one was ordered.
Two duty ratings sit behind one catalog number across this line: the normal-duty current is what the code reads, and the heavy-duty current is the next smaller code in the same frame. A machine that stalls or starts loaded needs the heavy-duty figure, and a machine that runs a fan or a pump can be sized on the normal-duty one. A withdrawal does not change that arithmetic, it only removes the option of ordering the same string again.
The voltage envelope of the class is unchanged by the withdrawal. Nominal motor voltage is 460 V, rated current is available from 460 to 528 V, and below 460 V the drive derates linearly down to the operating floor at 342 V. A replacement selected at the same current but a different frame is compared on that envelope, because a large drive running at the bottom of it loses torque authority at the top of the speed range rather than returning a fault.
Reactors are part of the replacement, not of the old drawing. Input reactors in this family are selected on NEC fundamental motor amps and output reactors on the drive rated output current, so the reactor bolted to a withdrawn unit is correctly sized for that unit's current basis and not automatically for its replacement. The reactor is read off the published table with the new catalog number, and the difference between 3 percent and 5 percent impedance is a separate selection again.
For 20BD730N0ANNNNC0 no lifecycle statement beyond the frame availability note and no price is implied. The current, frame, fuse, reactor, terminal, dimension and weight figures are quoted from the PowerFlex 700 published technical data for the 480 V class.
The 480 V class is the widest ladder in the series: twenty-eight rating codes from 1.1 A on frame 0 to 875 A on frame 10. Rating codes are not a sequence - they are the output current written into the catalog number, which is why 8P0 and 011 both exist and why 040 and 052 share one frame. The table is the whole published ladder for this voltage class, so the position of this page against its neighbours can be read directly instead of estimated from a horsepower list.
| Rating code | Output current | Horsepower | Frame |
| 1P1 | 1.1 A | 0.5 HP | Frame 0 |
| 2P1 | 2.1 A | 1.0 HP | Frame 0 |
| 3P4 | 3.4 A | 2.0 HP | Frame 0 |
| 5P0 | 5.0 A | 3.0 HP | Frame 0 |
| 8P0 | 8.0 A | 5.0 HP | Frame 0 |
| 011 | 11 A | 7.5 HP | Frame 0 |
| 014 | 14 A | 10 HP | Frame 1 |
| 022 | 22 A | 15 HP | Frame 1 |
| 027 | 27 A | 20 HP | Frame 2 |
| 034 | 34 A | 25 HP | Frame 2 |
| 040 | 40 A | 30 HP | Frame 3 |
| 052 | 52 A | 40 HP | Frame 3 |
| 065 | 65 A | 50 HP | Frame 3 |
| 077 | 77 A | 60 HP | Frame 4 |
| 096 | 96 A | 75 HP | Frame 5 |
| 125 | 125 A | 100 HP | Frame 5 |
| 156 | 156 A | 125 HP | Frame 6 |
| 180 | 180 A | 150 HP | Frame 6 |
| 248 | 248 A | 200 HP | Frame 6 |
| 292 | 292 A | 250 HP | Frame 7 |
| 325 | 325 A | 300 HP | Frame 7 |
| 365 | 365 A | 350 HP | Frame 8 |
| 415 | 415 A | 400 HP | Frame 8 |
| 481 | 481 A | 500 HP | Frame 8 |
| 535 | 535 A | 600 HP | Frame 8 |
| 600 | 600 A | not printed | Frame 8 |
| 730 | 730 A | not printed | Frame 9 |
| 875 | 875 A | not printed | Frame 10 |
Where this page sits: 20BD730N0ANNNNC0 carries rating code 730. The rating field reads 730 A. The printed ladder gives no horsepower figure at that step at all, only the amp rating, on a frame 9 chassis. It is the only rating code on frame 9, so the chassis changes in both directions: 600 below and 875 above. Frame 9 is past the wall-mount end of the ladder, so the enclosure, not the kW, decides how this drive gets installed.
Two things this ladder does not answer. It prints one output-current figure per code and no duty split: normal duty and heavy duty are separate tables in 20B-TD001, and a 480 V drive selected for constant torque needs the heavy-duty column, which is smaller than the figure above. And above 535 A the printed ladder stops giving a horsepower figure altogether, so the 600, 730 and 875 A steps are rated in amps only.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label. This page covers 20BD730N0ANNNNC0 and its ordering options.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated. This page covers 20BD730N0ANNNNC0 and its ordering options.
Twelve of the 82 20BD records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 20BD730N0ANNNNC0.
Group index: AB Drives & Motors. 20BD730N0ANNNNC0 is filed under that heading in the site's own product tree. Sibling codes of the same group are one click away from that page.