Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12

China Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier
Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12 supplier

Large Image :  Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12

Product Details:

Place of Origin: Made in USA
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley ArmorPoint 1738-IB4DM12 / 1738IB4DM12

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $87.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1738-IB4DM12

This page documents catalog number 1738-IB4DM12, the four channel 24 V dc digital input module with diagnostics in the ArmorPoint I/O family. What separates it from the plain input modules is per channel monitoring of the sensor supply, and the figures below are quoted from the diagnostic input module installation instructions.

What the module is and what it carries

FieldValue
Inputs4 in one group, non-isolated, sinking
On-state voltage11 V dc minimum, 28.8 V dc maximum, 24 V dc nominal
Off-state voltage5 V dc maximum
Off-state current1.5 mA maximum
On-state current2 mA minimum, 15 mA maximum, 3 mA nominal at 24 V dc
Input delay0 to 65,535 us selectable in 1 us steps rounded to 333 us, default 1,000 us in both directions
Sensor source voltagepin 1 provides SSV at 24 V dc, protected per input, 50 mA maximum
Short circuit detectioncurrent above 200 mA raises a fault, solid red indicator, and resets automatically when the short is removed
Open wire detectioncurrent below 0.5 mA raises a fault and a flashing red indicator, resettable per point
Data1 or 2 bytes produced, default 2 bytes with fault, short circuit and open wire bits; no consumed data
Configuration18 byte assembly for per-point off-to-on and on-to-off filters, open wire diagnostics switchable per point or all
PointBus current50 mA at 5 V dc maximum
Power dissipation0.6 W at 28.8 V dc (1.9 BTU/hr)
Isolation50 V continuous reinforced, type tested at 1,000 V dc for 60 s
Keyswitch position1
Enclosuremeets IP65/66/67/69K when marked

Connector pinout

PinFunction
124 V dc sensor source voltage
2not connected
3common
4input for connector A through D
5not connected

What the published figures mean in a project

Two thresholds define the diagnostics and both are current based rather than voltage based: above 200 mA on a sensor supply the module reports a short circuit, and below 0.5 mA it reports an open wire. The second one is the reason a dry contact needs a shunt resistor across it, so that more than 0.5 mA flows at all times even with the contact open. Without that resistor an unused or healthy dry contact reads as a broken wire.

The 50 mA sensor supply is not a large allowance, and the publication quantifies its cost: at the full 50 mA there can be up to 2.5 V dc between the auxiliary supply and the sensor source pin. A 10 V sensor fed from this pin therefore needs 12.5 V at the auxiliary connection, which is the calculation that decides whether a 12 V sensor can be used at all on a marginal supply.

Diagnostics can be switched off per point or for the whole module, and the default has all four channels enabled. That default is what makes an unused channel show red, so a spare input left unconfigured looks like a fault on a panel walk; disabling it per point is the published remedy rather than ignoring the lamp.

Fifty milliampere of PointBus current is the lowest in the family, and the delay is settable from 0 to 65,535 us in both directions with 1,000 us as the default, rounded to the nearest 333 us. The rounding is stated because it is real: a requested 10 us becomes 0 or 333 us depending on the entry, and a filter shorter than that step cannot be relied on from the configuration alone.

The two diagnostic bits come back separately as well as combined: one produced byte carries an open wire or short circuit fault bit per point, and the fuller assembly carries short circuit and open wire in distinct bits. Separating them matters at commissioning, because a short circuit and an open wire produce the same combined fault but different remedies, and the LED only distinguishes them by solid against flashing red.

Environment and installation facts that repeat across the family

ParameterValue
Dimensions with base120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters
Enclosure ratingMeets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one
Operating temperature-20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock
Storage temperature-40 to 85 degrees C (-40 to 185 degrees F)
Relative humidity5 to 95 percent non-condensing, IEC 60068-2-30 damp heat
Shock and vibrationOperating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating
Isolation50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s
ESD and RF immunity6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz
Transient immunityPlus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge
EmissionsCISPR 11 Group 1 Class A
MountingMounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole
Weight0.29 kg (0.64 lb) with base
Field power bus24 V dc nominal, 10 to 28.8 V dc range
PointBus current75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23

The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.

The mounting base ships with the module, so a spare is ordered as a module and arrives with the metal that does the grounding; a panel that keeps bases in stock and swaps only modules is a panel that still has the old base under the new part.

What this page does not claim matters as much as what it does. It does not state a sensor type that will work on every point, because the short circuit and open wire thresholds decide that rather than the input rating; only what the source publication states is printed here.

No lifecycle statement and no price is implied. The thresholds, data map and environmental figures are quoted from the ArmorPoint diagnostic input module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.

Related catalog numbers in the 1738 range

Of the 42 1738 records carried here, these twelve stand closest to this catalog number. This page is 1738-IB4DM12.

Site tree: the Allen Bradley Other PLC index carries 1738-IB4DM12 together with the other entries of the other-PLC group, which is where a catalogue walk usually starts. Reach it directly if the suffix on this record still needs confirming against a sibling.

Sources. Rockwell publishes the ArmorPoint I/O installation instructions as 1738-IN014, the EtherNet/IP adapter user manual as 1738-UM005 and the family user manual as 1738-UM001. The adapter role, node capacity and connector types quoted on this page for 1738-IB4DM12 follow those publications.

Data sources: the input and connector rows quoted on this page for 1738-IB4DM12 follow 1738-UM001 (ArmorPoint I/O user manual) and 1738-IN014 (ArmorPoint I/O installation instructions); nothing here is inferred from the catalog string.