This page documents catalog number 1738-IB16DM12, a 16-point 24 V dc digital input in the ArmorPoint I/O family. It is the high-density member of the family: a sealed IP67 module on a base bridging two positions, with sixteen channels on one module, and the figures below are quoted from the 16 point input and output module installation instructions.
| Field | Value |
| Catalog number | 1738-IB16DM12 |
| Connector | M12 (micro), 8 connectors with 2 inputs each |
| Connector pinout | Pin 1 sensor source voltage for the connector pair (M12-A and B, C and D, E and F, G and H), pin 2 odd inputs 1, 3, 5 up to 15, pin 3 common, pin 4 even inputs 0, 2, 4 up to 14, pin 5 no connect |
| Keyswitch position | 1 |
| Isolation | 50 V continuous, reinforced insulation from field side to system, type tested at 1,000 V dc for 60 s; no isolation between individual channels |
| Dimensions with base | 120 x 72 x 42 mm (4.72 x 2.83 x 4.25 in.), 290 g |
| Enclosure | meets IP65/66/67/69K when marked |
| Indicators | 16 yellow channel status, network and module status, and one red fault status, all on the logic side |
| Inputs per module | 1 group of 16, non-isolated, current sinking |
| On-state voltage | 10 V dc minimum, 24 V dc nominal, 28.8 V dc maximum |
| On-state current | 2 mA minimum, 4 mA at 24 V dc nominal, 5 mA maximum |
| Off-state voltage | 5 V dc |
| Off-state current | 1.5 mA |
| Sensor source current | 50 mA maximum per input, 800 mA maximum per module |
| Field power | 10 to 28.8 V dc |
| Input delay | 0.5 ms hardware plus 0 to 63 ms selectable |
| Data size | 2 or 3 bytes produced, none consumed |
| Power dissipation | 2.7 W at 28.8 V dc maximum (9.2 BTU/hr) |
| PointBus current | 75 mA at 5 V dc maximum |
Sixteen inputs on one module change the spare-part argument: a machine that used to need two eight-channel modules now needs one, but every input shares a single group with no isolation between channels, so a field fault that puts a supply onto one channel is a fault on the group rather than on a point.
The published thresholds are the same ladder as the eight-channel modules: 10 V dc to switch on, 5 V dc or less to switch off, 4 mA at 24 V dc. What the 16-point module adds is the sensor source current, 50 mA per input and 800 mA per module, which is what a 2-wire proximity sensor draws when it is powered from the module rather than from a separate source.
The wiring is arranged in pairs: one connector carries two inputs plus a sensor source pin, which is the reason the connector count is eight and the channel count is sixteen. A technician replacing a cable replaces two channels at a time, and the pair that shares a source pin is the pair to check first when both channels misbehave together.
Diagnostics are the difference from a plain 16-channel card: the module produces 2 or 3 bytes, the extra byte carrying a fault bit for the group, and each channel has its own status indicator on the logic side. A shorted sensor cable is therefore visible at the module rather than only in the controller.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The sealed housing is the reason this family exists. An IP67 module on a machine frame removes the cabinet from the field side of the design, and the price of that is that every environmental claim is made per module rather than per enclosure. 1738-IB16DM12 is the number described on this page.
What this page does not claim matters as much as what it does. It does not state a cable length, a scan time or a channel-to-channel isolation figure, because the publication states that there is no isolation between individual channels and the rest follows from the segment; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint 16 point input and output module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 75 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 13 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 30 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 48 | two supplies, two extra banks |
| 63-module station, printed ceiling | 4725 mA at 75 mA | 63 | 3 expansion supplies needed |
Where this module sits: 1738-IB16DM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. At 16 points that is 4.7 mA of 5 V budget per point, so a full 63-module 1738-IB16DM12 station is 4725 mA and needs 3 expansion supplies.
The station ceiling and the current budget are two different limits and only one of them is printed as a module count. At this draw the ceiling is reached at 4725 mA, so the supply count - not the module count - is the number that decides whether the segment is possible.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.
Twelve of the 42 1738 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1738-IB16DM12.
Group index: Allen Bradley Other PLC. 1738-IB16DM12 is filed under that heading in the site's own product tree. It is the entry point used when a project list is assembled group by group.