Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 1738-FPD, the field potential distributor in the ArmorPoint I/O family, Series A. It is a partitioning device rather than an I/O module: it breaks the internal field power bus and lets the modules to its right run from a different source, including ac. The figures below are quoted from the field potential distributor installation instructions.
| Field | Value |
| Function | discontinues the internal field power bus for modules to the right of the unit and starts a new field power source |
| Signal handling | passes through all backplane signals except the internal power bus |
| Input rating | 12 V dc or 24 V dc nominal with a 10 to 28.8 V dc range, and 120 V ac or 240 V ac nominal |
| Input and field bus current | 10 A maximum |
| Field bus ceiling | 264 V ac maximum, 50/60 Hz on the ac sources |
| Backplane output | pass through, with no conversion |
| PointBus | pass through, with no conversion |
| Indicators | none |
| Power consumption | none; the unit dissipates no power of its own |
| Isolation | 50 V rms continuous, 120 V rms or 240 V rms working; tested at 1,528 V ac rms for 60 s |
| Connector | 4-pin mini male: pin 1 user power plus, pins 2 and 3 no connect, pin 4 user power minus |
| Keyswitch position | 8 |
| Dimensions | 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.), 0.289 kg (0.637 lb) |
| Mounting base | ships with the module; bridges two bases |
Pass through is the operative word in the specification: backplane output, PointBus current and power consumption are all listed as pass through or none. The unit adds no current and consumes none, which is why it appears in a current budget as a zero rather than as a margin consumer. What it changes is the source, not the amount.
The voltage range is the reason this unit exists next to the 1738-EP24DC: 12 or 24 V dc with a 10 to 28.8 V dc window, and 120 or 240 V ac with a 264 V ac field bus ceiling. A mixed assembly with ac output modules and dc input modules is partitioned here rather than fed from two adapters.
The isolation rating is not the 50 V rms of the dc-only family members: the continuous rating is 50 V rms with a 120 or 240 V rms working voltage, tested at 1,528 V ac rms for 60 s. That figure is what makes an ac field side defensible on the same backplane as a controller-side circuit, and it is the one number to quote when a panel is reviewed.
There are no indicators on this unit, which is stated rather than implied: a segment that is dark after an FPD has no lamp to consult, and the fault appears at the modules to its right instead. That absence is also why the keyswitch position, eight, matters during installation, since the base position is the only local evidence that the correct device is fitted.
The connector passes only two wires, user power plus on pin 1 and user power minus on pin 4, with pins 2 and 3 not connected. On the sibling 1738-EP24DC those two pins carry adapter plus and minus, which is precisely the difference between distributing a source and creating one.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.
The mounting base ships with the module, so a spare is ordered as a module and arrives with the metal that does the grounding; a panel that keeps bases in stock and swaps only modules is a panel that still has the old base under the new part.
What this page does not claim matters as much as what it does. It does not state a module capacity for the segment after the unit, because the capacity belongs to the adapter and its extension supplies rather than to the distributor; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The ratings, connector pinout and environmental figures are quoted from the ArmorPoint field potential distributor installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
1738-FPD and 1738-EP24DC are both placed between modules and both break the field power bus, which is why they get confused. They differ in what they do with the 5 V backplane: the distributor passes it through and adds nothing, the expansion supply converts and adds 1.3 A. The table puts the two side by side.
| What it does | 1738-FPD | 1738-EP24DC |
| Internal field power bus to the right | discontinued | starts a new field power source |
| All other backplane signals | passed through | passed through |
| 5 V backplane conversion | none | converts, 5 V at 1.3 A |
| PointBus current added | none | 1.3 A |
| Input rating | 12 or 24 V dc and 120 or 240 V ac | 12 or 24 V dc only |
| Power of its own | none, dissipates nothing | 9.8 W at 28.8 V dc |
Where this unit sits: 1738-FPD is the pass-through member of that pair and the only part in the family that can take 120 or 240 V ac onto the field bus, up to the printed 264 V ac ceiling. It is chosen when a second bank of modules needs a different field source, not when the PointBus budget is short.
The distributor dissipates no power of its own, which is the tell: it contains no converter, so it cannot create backplane current to give away. A segment that is short of PointBus will not be fixed by fitting one, however the field wiring looks.
What the printed data does not carry: the page prints the isolation test at 1,528 V ac rms for 60 s but no derating against ambient temperature, and no maximum number of units per backplane - the extension unit rule of four per adapter is the only limit published for placement.
Source: Rockwell publication 1738-IN001 (field power distributor and expansion power supply installation instructions); both columns are printed values from the two part pages.
Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-FPD.
This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 1738-FPD page is one entry in it. The index sits one level above this page in the site tree.