This page documents catalog number 1738-EXT1, a one metre backplane bus extension unit in the ArmorPoint I/O family, Series A. It is a cable assembly with a starter and an end, not an I/O module, and the figures and application rules below are quoted from the extension unit installation instructions.
| Field | Value |
| Cable length | 1 m (3.3 ft) |
| Weight | 0.4 kg (0.88 lb) approximately |
| Function | extends the backplane to a second bank of I/O modules; passes backplane signals through the cable |
| Extension units per adapter | up to four, for all adapters except 1738-ADNX |
| 1738-ADNX exception | only one extension unit when there are fewer than 32 modules on the backplane |
| First module after the unit | must be a 1738-FPD or a 1738-EP24DC |
| When an EP24DC is required | when additional backplane power is needed, or after two extension units |
| When neither is required | when the segment after the unit holds only 1738-IT2IM12, IR2M12, OW4M12 or OW4M12AC modules |
| Cable routing | bend radius not smaller than 70 mm (2.76 in.), at least 30.7 mm (1.21 in.) from the base edge before the first bend |
| Mounting screws | M4 (#8), minimum 12 mm (0.47 in.) at the cable starter and 40 mm (1.57 in.) at the cable end |
| Keyswitch | starter position, left side of the system |
| Enclosure | meets IP65/66/67 when marked |
Four extension units per adapter is the published ceiling, and the ADNX adapter is the one exception: only a single unit is allowed while the backplane holds fewer than 32 modules. A layout drawn for a DeviceNet segment therefore cannot be copied to an EtherNet/IP segment unchanged, even where the module mix is identical.
The rule that shapes the physical layout is the next one: the first module after an extension unit must be either a 1738-FPD or a 1738-EP24DC. The extension unit carries signals but not the power bus, so a module placed directly after the cable has no field power of its own. Two extension units in a row force an 1738-EP24DC rather than an FPD, because the backplane current has to be replenished as well.
There is one published exception worth knowing before adding an FPD to a plan: if the segment after the extension unit holds only 1738-IT2IM12, 1738-IR2M12, 1738-OW4M12 or 1738-OW4M12AC modules, neither an FPD nor an EP24DC is needed. Those are the temperature, relay and high-speed counter parts, and a short segment of them can follow a cable directly.
Cable routing is specified numerically rather than left to practice: a bend radius no smaller than 70 mm and at least 30.7 mm of straight cable from the base edge before the first bend. The screws differ at each end, 12 mm minimum at the starter and 40 mm minimum at the end, because the end must also hold the cable gland rather than only the base.
The length is the difference between this catalog number and its sibling: 1 m reaches a second bank across a single machine section, and 3 m crosses a frame or a conveyor line. Both carry the same signals and the same rules, and excess length is meant to be looped and tied into a wireway rather than coiled at the base.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The family is designed so that the module is the replaceable unit and the base stays on the machine. That is why the base is ordered with the module, why the keyswitch on the base has to match the module class, and why the ground lug is also a mounting hole: the conductive path runs through the base and the plate rather than through the module. Swapping a module onto a dirty base is the failure that looks like a module fault and measures as a missing earth.
The default data map matters as much as the rating: a digital module produces one byte and, for outputs, consumes one, and that byte is the channel status and output state the controller actually sees.
What this page does not claim matters as much as what it does. It does not state a maximum backplane current for the cable itself, because the limit is the adapter or the EP24DC rating rather than the cable; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The length, mounting rules and environmental figures are quoted from the ArmorPoint extension unit installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
An extension unit carries the backplane to a second bank of modules, and the publication puts four rules around it that are all visible in the one table: four units per adapter, a first module that must be a 1738-FPD or a 1738-EP24DC, a supply required after the second unit, and one exception for the 1738-ADNX adapter.
| Extension unit | Modules on the segment | First module after the unit | Expansion supply |
| First 1738-EXT1 or 1738-EXT3 | no printed requirement | 1738-FPD or 1738-EP24DC | not required |
| Second | no printed requirement | 1738-FPD or 1738-EP24DC | required after two units |
| Third | no printed requirement | 1738-FPD or 1738-EP24DC | required after two units |
| Fourth | still four units per adapter | 1738-FPD or 1738-EP24DC | required after two units |
Where this cable sits: 1738-EXT1 is the 1 m (3.3 ft) member of a two-length pair, and the length is the only thing that separates it from its sibling. Everything that governs how many units can be chained - four per adapter, the first-module rule, the supply after the second unit - is identical on both pages.
The first-module rule is the one that catches people: the module immediately after the unit has to be a 1738-FPD or a 1738-EP24DC, so an extension cannot be dropped mid-segment and continued with the same I/O mix. The unit is a break in the backplane, and the publication treats it as one.
What the printed data does not carry: the page gives no current rating for the cable itself and no maximum total backplane length in metres, only the four-unit count. The 70 mm bend radius and the 30.7 mm clearance from the base edge are the only mechanical numbers published.
Source: Rockwell publication 1738-IN001 (extension unit installation instructions); cable length and the four-unit rule are printed on this page, the rest is the same publication rule restated.
This page links twelve of the 42 1738 records on this site; the closest rating codes come first. This page is 1738-EXT1.
For the surrounding range, open the Allen Bradley Other PLC catalogue index — 1738-EXT1 is listed there beside the rest of the other-PLC group. The index sits one level above this page in the site tree.