This page documents catalog number 1738-EP24DC, the 24 V dc expansion power supply in the ArmorPoint I/O family, Series A. It is not an I/O module: it sits between modules, extends the backplane bus power and starts a new field power partition, and the figures below are quoted from the expansion power supply installation instructions.
| Field | Value |
| Capacity | 5 to 17 I/O modules to the right of the supply, depending on each module current rating |
| Function | extends backplane bus power and starts a new field voltage partition; separates field power between input and output modules or between analog and digital groups |
| Input rating | 12 V dc or 24 V dc nominal, 10 to 28.8 V dc range, inrush 6 A for 10 ms, reverse polarity protected |
| Backplane output | 5 V dc at 1.3 A |
| PointBus output | 1 A with a 10 to 19.2 V input, 1.3 A with a 19.2 to 28.8 V input |
| Field side requirement | 24 V dc at 400 mA maximum |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc, 10 A maximum supply current |
| Isolation | 50 V rms continuous |
| Interruption | output stays within specification when the input drops out for 10 ms at 10 V with maximum load |
| Indicators | one green field power status and one green 5 V system power |
| Connector | 4-pin mini male: pin 1 user power plus, pin 2 adapter plus, pin 3 adapter minus, pin 4 user power minus |
| Power | consumption 9.8 W at 28.8 V dc, dissipation 3.0 W, 10.0 BTU/hr |
| Dimensions | 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.), 0.289 kg (0.637 lb) |
| Location | mounted between I/O modules; it breaks the field power bus |
| Keyswitch position | 1 |
Seventeen modules is the published reach of one unit, and the word is reach rather than limit: the number of modules that can follow depends on their current ratings, so a segment of sixteen 16-point outputs is a different calculation from a segment of mixed analog and digital parts. The 1.3 A of backplane output is what makes the calculation possible at all.
The second function is the one that is often more valuable than the current: the unit breaks the field power bus, so the modules to its right can be fed from a different 24 V source or a different voltage window. Separating input power from output power, or analog from digital, is a partition that exists physically rather than in documentation.
The PointBus output is not constant across the input range: 1 A with a 10 to 19.2 V input and 1.3 A from 19.2 to 28.8 V. A segment designed at 1.3 A on a nominal 24 V supply loses a quarter of that allowance if the supply sags into the lower half of the window, which is exactly what happens on a long feeder during a motor start.
Two warnings are printed and both matter: 120 or 240 V ac must not be connected to these terminals, and the unit can only be used with ArmorPoint adapters. A generic 24 V supply will power the field side, but the backplane extension only exists inside this family, so the unit is not a substitute for a DIN-rail supply feeding another vendor rack.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The family is designed so that the module is the replaceable unit and the base stays on the machine. That is why the base is ordered with the module, why the keyswitch on the base has to match the module class, and why the ground lug is also a mounting hole: the conductive path runs through the base and the plate rather than through the module. Swapping a module onto a dirty base is the failure that looks like a module fault and measures as a missing earth.
Field power and PointBus power are two separate budgets. The bus current listed for each module is drawn at 5 V dc from the adapter, and the field power at 10 to 28.8 V dc is what the sensors and the loads take; a segment planned on one of them and commissioned on the other trips on the one that was not counted.
What this page does not claim matters as much as what it does. It does not state a module count that a given mix will fit, because the publication expresses that as a range of 5 to 17 modules depending on each module current rating; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The capacity, power and environmental figures are quoted from the ArmorPoint expansion power supply installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
The unit prints two capacities that are easy to mix up: 5 to 17 I/O modules to its right, and 1.3 A of 5 V backplane output. The module count in that range is a consequence of the current, not an independent limit, so the honest way to read it is to divide the 1.3 A by each published class.
| Module class | Printed PointBus current | Modules per 1738-EP24DC |
| 1738-IB2M12, IB4xxx, IB8xxx, IV4xxx, OB2EM12, OB2EPM12, OB4Exxx, OB8Exxx, OV4EM12, IE2CM12, OE2CM12, IE2VM12, OE2VM12, IA2xxx, OA2xxx, 232ASCM12, 485ASCM12 | 75 mA | 17 modules |
| 1738-OW4xxx | 90 mA | 14 modules |
| 1738-SSIM23 | 110 mA | 11 modules |
| 1738-IJM23 | 160 mA | 8 modules |
| 1738-IT2IM12 | 175 mA | 7 modules |
| 1738-VHSC24M23 | 180 mA | 7 modules |
| 1738-IR2M12 | 220 mA | 5 modules |
Where this unit sits: 1738-EP24DC is the only part in the family that adds PointBus current without being a network head, and the table above shows why the printed 5 to 17 range is as wide as it is - five modules of the 220 mA class use the whole 1.3 A, seventeen of the 75 mA class use 1,275 mA of it.
The unit is placed between modules, not at either end, and that placement is what makes the field-power split possible: everything to its left keeps the old field supply, everything to its right starts on the new one.
What the printed data does not carry: the page prints the 10 ms ride-through at 10 V with maximum load but no hold-up time beyond that, and no efficiency figure, so the input current at 12 V cannot be derived from the 9.8 W consumption without assuming a conversion efficiency.
Source: Rockwell publication 1738-IN001 (expansion power supply installation instructions) and the adapter PointBus current table; the module count per supply is 1,300 mA divided by each printed class current.