This page documents catalog number 1738-APB, the PROFIBUS adapter for the ArmorPoint I/O family, Series A. It is the head of a sealed IP67 backplane on a PROFIBUS segment, and the figures below are quoted from the PROFIBUS adapter installation instructions.
| Field | Value |
| Expansion capacity | 1.0 A maximum backplane current; extendable by 1.3 A per 1738-EP24DC up to 63 modules |
| Station address | two rotary switches, most significant and least significant digit, valid 01 to 99, read only at power-up |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range, 10 A maximum supply current |
| Field side requirement | 24 V dc at 28.8 V dc at 400 mA maximum |
| Input rating | 24 V dc nominal, 10 to 28.8 V dc, reverse polarity protected, inrush 6 A maximum for 10 ms |
| PointBus output | 1 A maximum at 5 V dc plus or minus 5 percent (4.75 to 5.25 V) |
| Isolation | 50 V rms continuous, tested at 1,250 V ac rms for 60 s |
| PROFIBUS connectors | M12 male 5-pin in with pin 1 plus 5V bus, pin 2 A line, pin 3 ground bus, pin 4 B line, pin 5 shield; M12 female 5-pin out with user and adapter power and protective ground |
| Indicators | adapter status, PROFIBUS status, PointBus status, adapter power and system power |
| Power | consumption 8.1 W at 28.8 V dc, dissipation 2.8 W, 9.5 BTU/hr |
| Dimensions | 112 x 72 x 65 mm (4.41 x 2.83 x 2.56 in.), 0.36 kg (0.8 lb) |
| Terminating base | ships with the adapter and is mounted as the last base on the backplane |
| Configuration file | requires a GSD file, available from the Rockwell networks GSD library |
| Keyswitch | starter position, left side of the system |
The adapter publication prints the PointBus current of each module class, and that table is what a segment is added up from before the module list is fixed:
| Module | PointBus current |
| 1738-IB2M12, IB4xxx, IB8xxx, IV4xxx, OB2EM12, OB2EPM12, OB4Exxx, OB8Exxx, OV4EM12, IE2CM12, OE2CM12, IE2VM12, OE2VM12, IA2xxx, OA2xxx, 232ASCM12, 485ASCM12 | 75 mA |
| 1738-OW4xxx | 90 mA |
| 1738-SSIM23 | 110 mA |
| 1738-IJM23 | 160 mA |
| 1738-IT2IM12 | 175 mA |
| 1738-VHSC24M23 | 180 mA |
| 1738-IR2M12 | 220 mA |
This adapter is chosen when the plant standard is PROFIBUS rather than EtherNet/IP or DeviceNet, and the visible consequence is the GSD file: the segment cannot be configured from a generic device description, so the file has to be imported into the master before the adapter appears as a node at all.
The station address is set on two rotary switches with a most significant and a least significant digit, valid from 01 to 99, and the publication states that the switches are read only when power is applied. An address changed on a running segment is therefore not an address change until the next power cycle, which is a commissioning trap rather than a feature.
One ampere of backplane current is the whole budget before an extension supply is added, and the 63-module ceiling is reached with 1738-EP24DC units rather than with a single long backplane. The field side takes 400 mA at 28.8 V dc for the adapter itself and passes up to 10 A to the modules, and the two budgets are added separately.
The PROFIBUS connector is a 5-pin M12 with reverse keyway carrying plus 5 V bus, A line, ground bus, B line and shield, which is the physical layer the standard defines rather than a vendor choice. The shield pin is the reason a shielded M12 cordset is specified instead of a generic 5-pin cable.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The family is designed so that the module is the replaceable unit and the base stays on the machine. That is why the base is ordered with the module, why the keyswitch on the base has to match the module class, and why the ground lug is also a mounting hole: the conductive path runs through the base and the plate rather than through the module. Swapping a module onto a dirty base is the failure that looks like a module fault and measures as a missing earth.
The default data map matters as much as the rating: a digital module produces one byte and, for outputs, consumes one, and that byte is the channel status and output state the controller actually sees.
What this page does not claim matters as much as what it does. It does not state a supported baud rate or a maximum segment length for this adapter, because those are properties of the PROFIBUS segment rather than of the catalog number; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The capacity, power and environmental figures are quoted from the ArmorPoint PROFIBUS adapter installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
The adapter publishes the 5 V PointBus current of every module class in the family, and that table is what a segment is added up from before the module list is fixed. The last two columns are that publication arithmetic carried one step further: how many of each class the adapter carries on its own 1.0 A budget, and how many more each 1738-EP24DC buys with its 1.3 A.
| Module class | Printed PointBus current | On the adapter 1.0 A | Per 1738-EP24DC 1.3 A |
| 1738-IB2M12, IB4xxx, IB8xxx, IV4xxx, OB2EM12, OB2EPM12, OB4Exxx, OB8Exxx, OV4EM12, IE2CM12, OE2CM12, IE2VM12, OE2VM12, IA2xxx, OA2xxx, 232ASCM12, 485ASCM12 | 75 mA | 13 modules | 17 more |
| 1738-OW4xxx | 90 mA | 11 modules | 14 more |
| 1738-SSIM23 | 110 mA | 9 modules | 11 more |
| 1738-IJM23 | 160 mA | 6 modules | 8 more |
| 1738-IT2IM12 | 175 mA | 5 modules | 7 more |
| 1738-VHSC24M23 | 180 mA | 5 modules | 7 more |
| 1738-IR2M12 | 220 mA | 4 modules | 5 more |
Where this adapter sits: 1738-APB is the PROFIBUS head of the family, and the class table above is the one this page prints. The 1.0 A is shared by everything to the right of it up to the first 1738-EP24DC, so a segment of sixteen 16-point modules at 75 mA - 1,200 mA - already overruns the adapter alone and needs one supply before it is wired.
The spread in this table is the useful part: the 75 mA class costs 1.3 modules per 100 mA of budget and the 220 mA class costs 0.45, so a segment of encoder and resolver modules runs out of PointBus three times sooner than a segment of the same module count in the 75 mA class.
What the printed data does not carry: neither adapter page states a maximum segment length in metres, and no class prints a start-up or inrush current on the PointBus, so the table sizes steady-state load only. Both numbers would be needed to size a supply against a cold start.
Source: Rockwell publication 1738-IN001 (ArmorPoint adapter installation instructions), PointBus current table; the per-supply column is that table divided by the printed 1.0 A and 1.3 A budgets. No figure here is estimated.