This page documents catalog number 1738-OW4M12, a 4-channel relay output module in the ArmorPoint I/O family. It is the relay member of the family: a sealed IP67 module on a base bridging two positions, with four isolated normally open contacts, and the figures below are quoted from the relay output module installation instructions.
| Field | Value |
| Outputs per module | 4 Form A isolated normally open electromechanical relays |
| Connector | M12 (micro), 4 connectors: pin 1 24 V dc, pin 2 output B (pins 2 on M12-A to M12-D for outputs 0 to 3), pin 3 common, pin 4 output A, pin 5 no connect |
| Load voltage, dc module | 5 to 28.8 V dc at 2.0 A resistive |
| Load current, resistive | 2 A at 5 to 28.8 V dc; 2 A steady state inductive at L/R of 7 ms |
| Switching frequency | 1 operation every 3 s, 0.3 Hz at rated load |
| Contact life | 100,000 operations minimum at rated loads |
| Initial contact resistance | 30 milliohm |
| Minimum contact load | 100 uA at 100 mV dc |
| Operate and release time | 10 ms maximum each |
| Bounce | 1.2 ms mean |
| Output delay | 10 ms maximum off-to-on and 26 ms maximum on-to-off |
| Fusing | module outputs are not fused; external fusing has to be supplied if required |
| Data size | consumes 1 byte of output state, produces none |
| Keyswitch position | 7 |
| PointBus current | 90 mA at 5 V dc maximum |
| Power dissipation | 0.5 W at 28.8 V dc maximum (1.7 BTU/hr) |
| Isolation | 2,550 V dc between any two sets of contacts and from customer load to logic, withstand for 60 s |
| Field power | none required for the module itself; load supply 5 to 28.8 V dc, 2 A per channel and 8 A per module maximum |
| Dimensions | 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.), 0.289 kg |
| Shock and vibration | 15 g operating and 50 g non-operating shock, 2 g at 10-500 Hz vibration, both lower than the solid-state modules |
This is the only module in the family that switches a contact rather than a semiconductor, and that changes what it can drive: a Form A relay is normally open, isolated between any two sets of contacts to 2,550 V dc, and it does not care about the polarity or the leakage of the load. A solid-state output that leaks 0.5 mA will hold a small indicator faintly lit; a relay simply opens.
The 0.3 Hz switching limit is the number that rules this module out of a fast cycle: one operation every three seconds at rated load is a relay-life statement, and a machine that needs a relay to pulse twice a second is a machine that needs a solid-state output. The 100,000 operation life at rated load is the second half of the same statement, and at a slower rate the life is what a maintenance interval is planned around.
Outputs are not fused, and that is published rather than assumed: external fusing has to be added where a code requires it, and the module will not protect a shorted field cable. The 2 A per channel and 8 A per module ceiling, together with the 30 milliohm initial contact resistance, is what decides the voltage drop into a 2 A load, and the 100 uA at 100 mV minimum contact load is the floor below which a contact may not wet reliably.
The off-to-on delay of 10 ms and the on-to-off delay of 26 ms are mechanical times, and the 1.2 ms mean bounce is the reason a relay output is not used to count an event. Operate and release are each quoted at 10 ms maximum for the contact itself, and the difference between those two figures and the module delays is where the relay coil drive sits.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Two specifications are deliberately lower than the rest of the family and they are the reason this module is mounted with care: operating shock is 15 g rather than 30 g and operating vibration is 2 g at 10 to 500 Hz rather than 5 g, because a relay has moving parts. A bracket that carries a solid-state module without trouble is not automatically a bracket that carries a relay module.
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The mounting base ships with the module, so a spare is ordered as a module and arrives with the metal that does the grounding; a panel that keeps bases in stock and swaps only modules is a panel that still has the old base under the new part.
What this page does not claim matters as much as what it does. It does not state an ac load rating for this catalog number: the publication covers the ac-keyed variant separately, and the dc module is rated for 5 to 28.8 V dc only. It also does not state a cable length or a switching rate beyond the 0.3 Hz limit printed above.
No lifecycle statement and no price is implied. The contact, timing and environmental figures are quoted from the ArmorPoint relay output module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Twelve of the 42 1738 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1738-OW4M12.
Group index: Allen Bradley Other PLC. 1738-OW4M12 is filed under that heading in the site's own product tree. Reach it directly if the suffix on this record still needs confirming against a sibling.
Sources. Rockwell publishes the ArmorPoint I/O installation instructions as 1738-IN014, the EtherNet/IP adapter user manual as 1738-UM005 and the family user manual as 1738-UM001. The adapter role, node capacity and connector types quoted on this page for 1738-OW4M12 follow those publications.
Data sources: the output and connector rows quoted on this page for 1738-OW4M12 follow 1738-UM001 (ArmorPoint I/O user manual) and 1738-IN014 (ArmorPoint I/O installation instructions); nothing here is inferred from the catalog string.