This page documents catalog number 1738-OE4CM12, the four channel 24 V dc analog output module in the ArmorPoint I/O family, Series A, wired through four M12 connectors. The figures below are quoted from the four channel analog output module installation instructions.
| Field | Value |
| Outputs | 4 single-ended, non-isolated, current |
| Output range | 0 to 21 mA user configurable, holding 0 mA until communication is established |
| Resolution | 16 bits, 0.32 uA per count, signed integer format |
| Accuracy | 0.4 percent of full scale, 0.1 percent when calibrated, drift under 50 ppm per C |
| Load | 0 to 750 ohm resistive |
| Step response | 160 us to 63 percent of full scale, 1 us conversion |
| Data | 4 bytes produced as fault status, 8 bytes consumed |
| Calibration | factory calibrated |
| External power | 24 V dc nominal, 10 to 28.8 V dc, 115 mA at 24 V dc including outputs at 20 mA |
| PointBus current | 75 mA at 5 V dc maximum |
| Power dissipation | 1.3 W at 28.8 V dc (2.5 BTU/hr) |
| Isolation | 50 V continuous reinforced, type tested at 1,250 V ac for 60 s, no isolation between channels |
| Keyswitch position | 4 |
| Enclosure | meets IP65/66/67/69K when marked |
| Pin | Function |
| 1 | output for connector A through D |
| 2 | 24 V dc |
| 3 | common |
| 4 | common |
| 5 | not connected |
The output holds 0 mA until communication is established, and that is a published behaviour rather than a fault state. A valve driven from this module therefore sits at its zero-current position during startup, which is what makes the 0 to 21 mA range and the 0 mA default a decision about a spring-return valve rather than a detail of the data map.
Seven hundred and fifty ohms is the published resistive load ceiling, and it is the number that limits loop resistance rather than the accuracy. A 4 to 20 mA signal into 750 ohm needs 15 V at full scale, so a 24 V supply with a 250 ohm sense resistor and a long cable is a calculation worth doing before the module is blamed for a sag.
Accuracy is stated twice: 0.4 percent of full scale as shipped and 0.1 percent when calibrated, with drift under 50 ppm per C. The factory calibration figure and the calibrated figure are not the same promise, and a loop that needs the tighter one has to be calibrated in place rather than trusted from the label.
Eight bytes consumed and four bytes produced is the other structural difference from the input sibling: this module is written to as well as read. A fault status byte comes back, and the module also reports an open wire or missing field power as a solid red channel indicator, which is the local evidence a technician has before opening the cabinet.
The metal rings on the connectors are earth grounded, and the publication makes that an explicit consideration for cable and grounding choice rather than a footnote. On a drive-fed machine that means a shielded cordset drains into the module housing, so the shield reference is decided at the panel rather than at the sensor end, and a floating supply with a grounded ring is a loop waiting to appear as noise.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
The sealed housing is the reason this family exists. An IP67 module on a machine frame removes the cabinet from the field side of the design, and the price of that is that every environmental claim is made per module rather than per enclosure. 1738-OE4CM12 is the number described on this page.
What this page does not claim matters as much as what it does. It does not state a settling time for a valve or an actuator, because that belongs to the device rather than to the module; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint four channel analog output module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 75 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 13 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 30 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 48 | two supplies, two extra banks |
| 63-module station, printed ceiling | 4725 mA at 75 mA | 63 | 3 expansion supplies needed |
Where this module sits: 1738-OE4CM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. At 4 points that is 18.8 mA of 5 V budget per point, so a full 63-module 1738-OE4CM12 station is 4725 mA and needs 3 expansion supplies.
The count in the second column is where a segment stops, not where it fails: an adapter with 13 modules of this draw leaves the thirteenth with no margin, and the printed answer is to fit a 1738-EP24DC rather than to shorten the bank.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.