Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 1738-OE2CM12, a 2-channel current analog output, M12 connectors in the ArmorPoint I/O family. It is the current-loop output of the family: a sealed IP67 module on a base bridging two positions, with the resolution, accuracy, load and conversion figures taken from the analog output installation instructions. The figures below are quoted from the installation instructions for this module.
| Field | Value |
| Outputs per module | 2 single-ended, non-isolated |
| Connector | M12 (micro), 2 connectors: pin 1 output (channel 0 on M12-A, channel 1 on M12-B), pin 2 24 V dc, pins 3-4 common, pin 5 no connect |
| Output range | 4 to 20 mA user configurable and 0 to 20 mA user configurable, 0 mA until communication is established |
| Resolution | 13 bits over 0 to 21 mA, 2.5 uA per count typical (2.3 to 2.7 uA per count) |
| Accuracy and drift | 0.1 percent of full scale at 25 degrees C, 30 ppm per degree C |
| Load | 0 to 750 ohm resistive on the mA output |
| Conversion | digital-to-analog converter, 16 us conversion rate, 24 us step response to 63 percent of full scale |
| Data size | 2 bytes produced (fault status), 4 bytes consumed |
| Keyswitch position | 4 |
| PointBus current | 75 mA at 5 V dc |
| External supply | 24 V dc nominal, 10 to 28.8 V dc, 70 mA at 24 V dc including outputs at 20 mA |
| Power dissipation | 1.23 W at 28.8 V dc with a 750 ohm load on each output (4.19 BTU/hr) |
| Isolation | 50 V rms, tested at 1,250 V ac rms for 60 s |
| Dimensions | 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.), 0.289 kg |
The 750 ohm load limit is the number that decides whether a valve positioner or a remote indicator can be driven directly: 20 mA into 750 ohm is 15 V, and a device that needs more compliance than the 24 V supply leaves after that drop is a device that needs a separate supply rather than a different module.
Resolution is 13 bits over 0 to 21 mA at 2.5 uA per count, and the published typical window of 2.3 to 2.7 uA per count is there because the step size is a typical value rather than a guaranteed one. A loop scaled for 4 to 20 mA therefore has roughly 6,400 counts across its useful span.
The clamp and channel alarms are produced as 2 bytes and the module consumes 4 bytes of output data. Open wire or missing power is reported as a flashing red channel indicator, which is the difference between a loop that reads zero because of a fault and one that legitimately sits at 4 mA.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
The mounting base ships with the module, so a spare is ordered as a module and arrives with the metal that does the grounding; a panel that keeps bases in stock and swaps only modules is a panel that still has the old base under the new part.
What this page does not claim matters as much as what it does. It does not invent a cable length, a loop length or a scan time for this catalog number, because those follow from the device on the other end of the connector and from the segment; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 75 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 13 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 30 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 48 | two supplies, two extra banks |
| 63-module station, printed ceiling | 4725 mA at 75 mA | 63 | 3 expansion supplies needed |
Where this module sits: 1738-OE2CM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. At 2 points that is 37.5 mA of 5 V budget per point, so a full 63-module 1738-OE2CM12 station is 4725 mA and needs 3 expansion supplies.
Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.
Of the 42 1738 records carried here, these twelve stand closest to this catalog number. This page is 1738-OE2CM12.
Site tree: the Allen Bradley Other PLC index carries 1738-OE2CM12 together with the other entries of the other-PLC group, which is where a catalogue walk usually starts. Reach it directly if the suffix on this record still needs confirming against a sibling.