This page documents the 1738-OB8EM23, a 8-channel sourcing dc output, M23 connector in the ArmorPoint I/O family: a sealed IP67 output block on a base bridging two backplane positions. Current, surge, on-state drop and dissipation are quoted from the output module installation instructions rather than from a nameplate.
| Field | Value |
| Catalog number | 1738-OB8EM23 |
| Family | 1738 ArmorPoint I/O, 24 V dc digital output |
| Channels | 8 (1 group of 8), non-isolated, sourcing |
| Connectors | M23, 12-pin single connector |
| Connector pinout | Pin 1 output 0 through pin 8 output 7, pins 9-10 return, pin 11 24 V dc, pin 12 chassis |
| Output rating | 1.0 A per channel, not exceeding 3.0 A per module |
| Surge | 2 A for 10 ms, repeatable every 3 s |
| On-state voltage drop | 0.2 V dc at full on-state |
| Keyswitch position | 1 |
| PointBus current | 75 mA at 5 V dc |
| Power dissipation | 2.0 W at 28.8 V dc (6.8 BTU/hr) |
Two limits apply at once and both bind: this module publishes 1.0 A per channel, not exceeding 3.0 A per module. The channel figure is what a single valve or lamp may draw, and the module figure is the sum across all channels. Eight loads at 0.5 A sit inside every channel limit and outside the module limit, and that is the arithmetic that is discovered in the field rather than in the panel drawing.
Off-state leakage is 0.5 mA maximum and the minimum on-state current is 1.0 mA, so a load that draws less than a milliamp when energised may not hold, and a solid-state relay with a leakage path of its own may stay partly on when the channel is commanded off. Both are published limits of the module, not faults of the load.
Surge is 2 A for 10 ms, repeatable every 3 s, and the on-state drop is 0.2 V dc at full on-state. The surge allowance is what makes the module usable on a solenoid without a separate suppression diode, and the drop is what has to be subtracted when a 24 V load is checked at the far end of a long cord set.
The module produces one byte of channel status and consumes one byte of output state. The status bit reports open circuit while the channel is off and short circuit while it is on, which is how an output fault reaches the controller without a diagnostic module in the rack. A technician who reads the status byte first does not have to disconnect a cord set to find out whether the fault is in the module or in the load.
Output delay is 0.1 ms in each direction, which is fast enough that this module cannot be used as a deliberate debounce. A contactor coil that needs a delay needs the delay in the program, not in the output stage.
The arithmetic a panel check runs is 8 channels at 1.0 A each, which is 8.0 A total against a 3.0 A module limit. At most 3 channels can sit at full rating at the same time, so a bank of 8 identical loads needs a second block or a load schedule, and that is the calculation that decides how many blocks the machine takes.
One twelve-pin mini shell puts the whole block behind a single connector and a single seal. It is the fastest shell to install and the least granular to troubleshoot, because a cord-set fault takes every channel on its pin group out at once.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Mounting is part of the electrical path: the module sits on a base, the base is fixed to a grounded metal plate with #8 (M4) screws, and the ground lug is also a mounting hole. The conductive path therefore runs through the base and the plate rather than through the module, which is why a module swapped onto a dirty base measures as a missing earth and reads like an electronics fault.
The family is built so the module is the replaceable unit and the base stays on the machine. The keyswitch position on the base has to match the module class, and a module inserted one position off is not a wiring error that can be traced with a meter but a mapping error that appears as shifted channels. That is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, only the position and the adapter map.
The same electrical function is published under other strings in this family: 1738-OB8EM12, 1738-OB8EM8, 1738-OB2EPM12. A substitution between them is a change of shell and cord-set preparation rather than a change of channel behaviour, and the keyswitch position is what has to stay compatible with the base already on the machine.
A sealed block is not a substitute for a cabinet when the environment includes washdown or corrosive atmosphere. The IP rating covers the module and its mated connectors; it says nothing about the chemical resistance of the shell or the cable jacket.
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The adapter is the only place the channel map exists. Modules publish channel counts and data bytes; the adapter publishes the order in which those bytes appear to a scanner, so a replacement module in the same position needs no map change while a module moved to a new position does.
Every module in this family carries a green and red module-status indicator, a network-status indicator and per-channel yellow or red status, all on the logic side, so a technician diagnoses a channel from the face of the module rather than from a wiring diagram. This entry is for 1738-OB8EM23.
What this page does not claim matters as much as what it does. It states no cycle time, no maximum cable length and no network baud rate for this catalog number, because those belong to the segment and the adapter rather than to the module, and a figure of that kind copied into a page becomes a specification nobody can trace back to a publication. Where the source documents do fix a value - the channel count, the shell, the current limit, the isolation rating, the temperature window, the data size - it is on this page with the publication named.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint installation instructions (1738-IN001 for dc outputs, 1738-IN002 for dc inputs, 1738-IN003 for analog inputs and the temperature input instructions) and the DeviceNet adapter user manual 1738-UM001.