This page documents catalog number 1738-OB16EM12, a 16-point 24 V dc sourcing digital output in the ArmorPoint I/O family. It is the high-density member of the family: a sealed IP67 module on a base bridging two positions, with sixteen channels on one module, and the figures below are quoted from the 16 point input and output module installation instructions.
| Field | Value |
| Catalog number | 1738-OB16EM12 |
| Connector | M12 (micro), 8 connectors with 2 outputs each |
| Connector pinout | Pin 1 no connect, pin 2 odd outputs 1, 3, 5 up to 15, pin 3 common, pin 4 even outputs 0, 2, 4 up to 14, pin 5 no connect |
| Keyswitch position | 1 |
| Isolation | 50 V continuous, reinforced insulation from field side to system, type tested at 1,000 V dc for 60 s; no isolation between individual channels |
| Dimensions with base | 120 x 72 x 42 mm (4.72 x 2.83 x 4.25 in.), 290 g |
| Enclosure | meets IP65/66/67/69K when marked |
| Indicators | 16 yellow channel status, network and module status, and one red fault status, all on the logic side |
| Outputs per module | 1 group of 16, non-isolated sourcing, electronically protected |
| On-state voltage | 10 V dc minimum, 24 V dc nominal, 28.8 V dc maximum |
| On-state current | 1.0 mA minimum per channel, 0.5 A maximum per channel |
| Output current rating | 4.0 A per module maximum, 0.5 A per channel maximum |
| On-state voltage drop | 0.2 V dc maximum |
| Off-state leakage | 0.5 mA, with 28.8 V dc maximum off-state voltage |
| Output surge current | 1 A maximum, electronically protected |
| Output delay | 0.1 ms off-to-on and on-to-off |
| Pilot duty rating | 1.3 A inrush |
| External supply | 10 to 28.8 V dc, 24 V dc nominal |
| Data size | produces 1 byte of fault status, consumes 2 bytes of output state |
| Power dissipation | 3.0 W at 28.8 V dc (10.3 BTU/hr) |
| PointBus current | 150 mA at 5 V dc maximum |
Sixteen sourcing outputs are delivered through eight connectors, two outputs per connector, and the shared common in the middle pin is the reason a field cable carries two channels. The 0.5 A per channel is unchanged from the eight-point modules but the 4.0 A module ceiling is only eight channels at full rating, which is the number a panel of sixteen valves has to be planned against.
Electronic protection replaces the fuse: the output limits at 1 A of surge current and reports a short circuit as a red fault indicator and a fault bit in the produced byte. That is safer than a fuse in one respect and less convenient in another, because a fault clears itself only when the load is corrected rather than when a fuse is replaced.
The 0.1 ms delay in both directions and the 1.3 A pilot duty inrush rating are the two numbers that decide whether a contactor coil can be driven directly. A coil that pulls 1.3 A for a few milliseconds is inside the pilot duty rating and outside nothing, while a coil that pulls 2 A inrush needs an interposing relay even though its steady current is small.
Each output has its own yellow status indicator on the logic side and the module reports the group fault separately, so a commissioning engineer can see which of the sixteen channels is energised without a meter. The duplicate indication in the produced byte is what lets the controller log the fault instead of relying on an operator noticing an LED.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
Every module in this family carries a green and red module-status indicator, a network-status indicator and per-channel yellow or red status, all on the logic side, so a technician diagnoses a channel from the face of the module rather than from a wiring diagram. The catalog number covered on this page is 1738-OB16EM12.
What this page does not claim matters as much as what it does. It does not state a cable length, a scan time or a channel-to-channel isolation figure, because the publication states that there is no isolation between individual channels and the rest follows from the segment; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint 16 point input and output module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 150 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 6 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 15 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 24 | two supplies, two extra banks |
| 63-module station, printed ceiling | 9450 mA at 150 mA | 63 | 7 expansion supplies needed |
Where this module sits: 1738-OB16EM12 draws 150 mA on the PointBus, which is band 4 of the seven published classes - 75 mA above the 75 mA class that most digital and analog modules sit in. At 16 points that is 9.4 mA of 5 V budget per point, so a full 63-module 1738-OB16EM12 station is 9450 mA and needs 7 expansion supplies.
The station ceiling and the current budget are two different limits and only one of them is printed as a module count. At this draw the ceiling is reached at 9450 mA, so the supply count - not the module count - is the number that decides whether the segment is possible.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 150 mA. No figure here is estimated.
Twelve of the 42 1738 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1738-OB16EM12.
Group index: Allen Bradley Other PLC. 1738-OB16EM12 is filed under that heading in the site's own product tree. Sibling codes of the same group are one click away from that page.