This page documents catalog number 1738-IJM23, the 5 V dc encoder/counter module in the ArmorPoint I/O family, Series A. It is the 5 V member of the two counter modules: a sealed IP67 module on a base bridging two positions, reading a TTL-level encoder directly, and the figures below are quoted from the encoder/counter installation instructions.
| Field | Value |
| Inputs | 1 group of A and A return, B and B return, Z and Z return |
| Connector | M23, 12-pin: pins 1-6 plus and minus A, B, Z; pins 7, 8 and 12 chassis; pins 9-10 return; pin 11 5 V dc |
| Input voltage | 5 V dc, with 19.1 mA at 5 V dc and 25.7 mA at 6 V dc |
| Thresholds | off-state under 1.25 V dc and 0.250 mA maximum, on-state over 2.6 V dc and over 5 mA, maximum on-state plus 6 V |
| Filter selection | off, 10 us, 100 us, 1.0 ms and 10.0 ms per A, B, Z group |
| Maximum frequency | 1.0 MHz counter and encoder X1, 500 kHz encoder X2 and 250 kHz encoder X4 without filter |
| Data size | 6 or 10 bytes produced, 1 byte consumed with value reset, counter preset and counter reset bits |
| Keyswitch position | 2 |
| PointBus current | 160 mA at 5 V dc maximum |
| Power dissipation | 1.1 W at rated load (3.75 BTU/hr) |
| Isolation | 50 V rms continuous, tested at 1,250 V ac rms for 60 s |
| Dimensions | 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.), 0.289 kg |
| External power | none required to power the module |
| Shield | shield lead can be tied to chassis pins 7, 8 or 12 |
Five volts is the whole point of this catalog number: a 24 V counter module needs a level converter in front of a TTL encoder, and this module takes the 5 V signal directly with 19.1 mA at 5 V dc drawn from the encoder supply on pin 11. The maximum on-state of plus 6 V is the ceiling, so a 12 V encoder is not a device this module reads.
The filter ladder is published as rates rather than times, with the minus-only tolerance stated: 50 kHz is 10 us with 0 and minus 1.6 us, 5 kHz is 100 us with minus 13.2 us, 500 Hz is 1.0 ms with minus 125 us, and 50 Hz is 10 ms with minus 1.25 ms. The minus-only window is a statement about how the module counts rather than about accuracy, and it is why a fast pulse train at the edge of the filter is counted slightly slower rather than slightly faster.
The frequency ceiling depends on the configuration: 1.0 MHz for counter and encoder X1, 500 kHz for X2 without filter, 250 kHz for X4 without filter. A quadrature encoder at X4 therefore reaches a quarter of the X1 rate, which is a property of how the edges are resolved rather than a limit of the input circuit.
The shield pins are why the M23 connector lists chassis on three pins: a shielded encoder cable can tie its drain to pin 7, 8 or 12, and the publication makes that an explicit option rather than leaving it to the installer. On a machine frame that carries a drive, that choice is the difference between a count and a noise tally.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. The catalog number covered on this page is 1738-IJM23.
What this page does not claim matters as much as what it does. It does not state an encoder cable length or a maximum input frequency beyond the published configuration table, because those follow from the encoder and the segment; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint 5 V dc encoder/counter installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 160 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 6 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 14 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 22 | two supplies, two extra banks |
| 63-module station, printed ceiling | 10080 mA at 160 mA | 63 | 7 expansion supplies needed |
Where this module sits: 1738-IJM23 draws 160 mA on the PointBus, which is band 4 of the seven published classes - 85 mA above the 75 mA class that most digital and analog modules sit in. A full 63-module station of this type is 10080 mA and needs 7 expansion supplies, which is the number to check before the module list is fixed.
Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 160 mA. No figure here is estimated.
Of the 42 1738 records carried here, these twelve stand closest to this catalog number. This page is 1738-IJM23.
Site tree: the Allen Bradley Other PLC index carries 1738-IJM23 together with the other entries of the other-PLC group, which is where a catalogue walk usually starts. The index sits one level above this page in the site tree.