Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 1738-IE4CM12, the four channel 24 V dc analog input module in the ArmorPoint I/O family, Series A, wired through four M12 connectors. The figures below are quoted from the four channel analog input module installation instructions.
| Field | Value |
| Inputs | 4 single-ended, non-isolated |
| Signal range | 4 to 20 mA and 0 to 20 mA |
| Resolution | 16 bits over 0 to 21 mA, 0.32 uA per count |
| Accuracy | 0.1 percent of full scale at 25 C, drift 30 ppm per C |
| Input impedance | 60 ohm, sigma-delta conversion |
| Rejection | 120 dB common mode, minus 60 dB normal mode |
| Filter | digital time constant 0 to 10,000 ms, default 0 ms |
| Notch and step response | 50 ms step and 200 ms update at the 60 Hz notch, 6.25 ms step and 25 ms update at 480 Hz |
| Data | 12 bytes produced with fault status, no consumed data |
| External power | 24 V dc nominal, 10 to 28.8 V dc, 15 mA at 24 V dc, input fault protected to 28.8 V dc |
| PointBus current | 75 mA at 5 V dc maximum |
| Power dissipation | 0.6 W at 28.8 V dc (2.0 BTU/hr) |
| Isolation | 50 V continuous reinforced, type tested at 1,250 V ac for 60 s, no isolation between channels |
| Keyswitch position | 3 |
| Enclosure | meets IP65/66/67/69K when marked |
| Pin | Function |
| 1 | 24 V dc |
| 2 | input for connector A through D |
| 3 | common |
| 4 | common |
| 5 | not connected |
The notch filter is the setting that decides how fast this module can be, and the publication prints the trade rather than a single rate: a 60 Hz notch gives a 50 ms step response and a 200 ms update, while 480 Hz gives 6.25 ms and 25 ms. Eight times faster costs eight times less rejection, and a loop tuned at the default will look sluggish on a fast load cell because of it.
Sixteen bits over 0 to 21 mA with 0.32 uA per count is a statement about the converter, not about the installation: the accuracy figure of 0.1 percent of full scale at 25 C is what survives a real panel, with a 30 ppm per C drift on top. Over a 40 C swing that is roughly 0.12 percent of additional error, which is the number to compare against the sensor rather than the resolution.
The publication carries its own warning that the step response and update rate of this module differ from the two channel 1738-IE2CM12, which is worth knowing before a channel count upgrade is treated as a drop-in: the same notch setting does not guarantee the same loop behaviour.
Twelve bytes produced with fault status and no consumed data means this module is read only, with no configuration written through the I/O connection. Channel filters and notch settings therefore come from the module profile rather than from a runtime write, and a copy of a working project is the practical way to reproduce a setting.
Sixty ohms of input impedance is the number that decides whether a 4 to 20 mA transmitter can drive this point alongside another load. A 60 ohm burden at 20 mA costs 1.2 V of loop headroom, which is small next to a 250 ohm sense resistor but not next to a second module in series on the same loop; the publication does not offer a series arrangement, and the burden is the reason.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.
The default data map matters as much as the rating: a digital module produces one byte and, for outputs, consumes one, and that byte is the channel status and output state the controller actually sees.
What this page does not claim matters as much as what it does. It does not state a loop time or a settling figure beyond the published notch table, because those follow from the loop and the transmitter; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint four channel analog input module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 75 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 13 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 30 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 48 | two supplies, two extra banks |
| 63-module station, printed ceiling | 4725 mA at 75 mA | 63 | 3 expansion supplies needed |
Where this module sits: 1738-IE4CM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. At 4 points that is 18.8 mA of 5 V budget per point, so a full 63-module 1738-IE4CM12 station is 4725 mA and needs 3 expansion supplies.
Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.
Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-IE4CM12.
This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 1738-IE4CM12 page is one entry in it. The index sits one level above this page in the site tree.