logo
Home ProductsAllen Bradley Other PLC

Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12

China Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier
Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12 supplier

Large Image :  Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12

Product Details:

Place of Origin: Made in USA
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley ArmorPoint 1738-IE4CM12 / 1738IE4CM12

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $304.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1738-IE4CM12

This page documents catalog number 1738-IE4CM12, the four channel 24 V dc analog input module in the ArmorPoint I/O family, Series A, wired through four M12 connectors. The figures below are quoted from the four channel analog input module installation instructions.

What the module is and what it carries

FieldValue
Inputs4 single-ended, non-isolated
Signal range4 to 20 mA and 0 to 20 mA
Resolution16 bits over 0 to 21 mA, 0.32 uA per count
Accuracy0.1 percent of full scale at 25 C, drift 30 ppm per C
Input impedance60 ohm, sigma-delta conversion
Rejection120 dB common mode, minus 60 dB normal mode
Filterdigital time constant 0 to 10,000 ms, default 0 ms
Notch and step response50 ms step and 200 ms update at the 60 Hz notch, 6.25 ms step and 25 ms update at 480 Hz
Data12 bytes produced with fault status, no consumed data
External power24 V dc nominal, 10 to 28.8 V dc, 15 mA at 24 V dc, input fault protected to 28.8 V dc
PointBus current75 mA at 5 V dc maximum
Power dissipation0.6 W at 28.8 V dc (2.0 BTU/hr)
Isolation50 V continuous reinforced, type tested at 1,250 V ac for 60 s, no isolation between channels
Keyswitch position3
Enclosuremeets IP65/66/67/69K when marked

Connector pinout

PinFunction
124 V dc
2input for connector A through D
3common
4common
5not connected

What the published figures mean in a project

The notch filter is the setting that decides how fast this module can be, and the publication prints the trade rather than a single rate: a 60 Hz notch gives a 50 ms step response and a 200 ms update, while 480 Hz gives 6.25 ms and 25 ms. Eight times faster costs eight times less rejection, and a loop tuned at the default will look sluggish on a fast load cell because of it.

Sixteen bits over 0 to 21 mA with 0.32 uA per count is a statement about the converter, not about the installation: the accuracy figure of 0.1 percent of full scale at 25 C is what survives a real panel, with a 30 ppm per C drift on top. Over a 40 C swing that is roughly 0.12 percent of additional error, which is the number to compare against the sensor rather than the resolution.

The publication carries its own warning that the step response and update rate of this module differ from the two channel 1738-IE2CM12, which is worth knowing before a channel count upgrade is treated as a drop-in: the same notch setting does not guarantee the same loop behaviour.

Twelve bytes produced with fault status and no consumed data means this module is read only, with no configuration written through the I/O connection. Channel filters and notch settings therefore come from the module profile rather than from a runtime write, and a copy of a working project is the practical way to reproduce a setting.

Sixty ohms of input impedance is the number that decides whether a 4 to 20 mA transmitter can drive this point alongside another load. A 60 ohm burden at 20 mA costs 1.2 V of loop headroom, which is small next to a 250 ohm sense resistor but not next to a second module in series on the same loop; the publication does not offer a series arrangement, and the burden is the reason.

Environment and installation facts that repeat across the family

ParameterValue
Dimensions with base120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters
Enclosure ratingMeets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one
Operating temperature-20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock
Storage temperature-40 to 85 degrees C (-40 to 185 degrees F)
Relative humidity5 to 95 percent non-condensing, IEC 60068-2-30 damp heat
Shock and vibrationOperating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating
Isolation50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s
ESD and RF immunity6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz
Transient immunityPlus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge
EmissionsCISPR 11 Group 1 Class A
MountingMounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole
Weight0.29 kg (0.64 lb) with base
Field power bus24 V dc nominal, 10 to 28.8 V dc range
PointBus current75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23

Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.

The default data map matters as much as the rating: a digital module produces one byte and, for outputs, consumes one, and that byte is the channel status and output state the controller actually sees.

What this page does not claim matters as much as what it does. It does not state a loop time or a settling figure beyond the published notch table, because those follow from the loop and the transmitter; only what the source publication states is printed here.

No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint four channel analog input module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.

PointBus budget: how many 1738-IE4CM12 modules one segment carries

Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.

ConfigurationPointBus availableModules at 75 mAWhat that means
1738-APB or 1738-ACNR alone1,000 mA13adapter budget, no expansion supply
Adapter plus one 1738-EP24DC2,300 mA30one supply fitted after the first bank
Adapter plus two 1738-EP24DC3,600 mA48two supplies, two extra banks
63-module station, printed ceiling4725 mA at 75 mA633 expansion supplies needed

Where this module sits: 1738-IE4CM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. At 4 points that is 18.8 mA of 5 V budget per point, so a full 63-module 1738-IE4CM12 station is 4725 mA and needs 3 expansion supplies.

Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.

What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.

Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.

Related catalog numbers in the 1738 range

Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-IE4CM12.

This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 1738-IE4CM12 page is one entry in it. The index sits one level above this page in the site tree.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)