This page documents the 1738-IE2VM12, a 2-channel voltage analog input, M12 connectors in the ArmorPoint I/O family: the analog front end as a sealed IP67 block on a base spanning two positions. Signal range, resolution, accuracy, impedance and data size come from the analog input module installation instructions.
| Field | Value |
| Catalog number | 1738-IE2VM12 |
| Family | 1738 ArmorPoint I/O, analog input |
| Channels | 2 single-ended, non-isolated |
| Connectors | M12 (micro), 2 connectors |
| Signal range | 0-10 V dc user configurable (minus 0.0 V under, plus 0.5 V over) or plus or minus 10 V user configurable (plus or minus 0.5 V over) |
| Resolution | 15 bits plus sign, 320 uV per count in unipolar or bipolar mode |
| Accuracy | 0.1 percent of full scale at 25 degrees C, 5 ppm per degree C drift |
| Input impedance | 100 kohm input impedance, 200 kohm input resistance |
| External supply | 15 mA at 24 V dc external supply |
| Keyswitch position | 3 |
| PointBus current | 75 mA at 5 V dc |
| Power dissipation | 0.75 W at 28.8 V dc (2.5 BTU/hr) |
| Data size | 6 bytes produced (scanner Rx), no consumed data |
This module publishes both: 15 bits plus sign, 320 uV per count in unipolar or bipolar mode, and 0.1 percent of full scale at 25 degrees C, 5 ppm per degree C drift. Sixteen bits over a 0...21 mA span is fine resolution attached to a 0.1 percent accuracy statement, and a page that quotes only the bits overstates what a control loop can hold. The per-degree drift is the figure a plant engineer needs when a reading has to stay put across a shift, because it converts into a microamp error per ten degrees of panel temperature rather than an accuracy that only holds at 25 C.
Input impedance is 100 kohm input impedance, 200 kohm input resistance, which sets how much burden this channel adds to a 4...20 mA transmitter, and the external supply draws 15 mA at 24 V dc external supply. Those two together decide whether a two-wire transmitter can be loop-powered from the segment or needs its own supply.
The digital filter time constant is adjustable from 0 to 10,000 ms with a default of 0 ms, and the notch is set to the line frequency in use: 60 Hz gives a 15.7 Hz notch, 50 Hz gives 13.1 Hz, 250 Hz gives 65.5 Hz and 500 Hz gives 131 Hz. Step response follows the notch from 70 ms at 60 Hz down to 8 ms at 500 Hz, and the module update rate runs from 100 ms to 12 ms on the same ladder.
Common-mode rejection is 120 dB and normal-mode rejection is minus 60 dB. Those figures are what make a milliamp loop readable next to a contactor, and they depend on the earth-grounded metal rings in the connectors, so the shield decision is part of commissioning rather than cosmetic.
The current-input member of the pair takes 4...20 mA and 0...20 mA; the voltage member is the one a 0...10 V transducer needs. Both are two-channel blocks with the same M12 shell, the same keyswitch position and the same data size, so a machine that mixes milliamp and voltage sensors carries two part numbers for one function, and the second number is a purchase order line rather than a design decision.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Mounting is part of the electrical path: the module sits on a base, the base is fixed to a grounded metal plate with #8 (M4) screws, and the ground lug is also a mounting hole. The conductive path therefore runs through the base and the plate rather than through the module, which is why a module swapped onto a dirty base measures as a missing earth and reads like an electronics fault.
The family is built so the module is the replaceable unit and the base stays on the machine. The keyswitch position on the base has to match the module class, and a module inserted one position off is not a wiring error that can be traced with a meter but a mapping error that appears as shifted channels. That is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, only the position and the adapter map.
The same electrical function is published under other strings in this family: 1738-IE2CM12, 1738-IE4CM12. A substitution between them is a change of shell and cord-set preparation rather than a change of channel behaviour, and the keyswitch position is what has to stay compatible with the base already on the machine.
A sealed block is not a substitute for a cabinet when the environment includes washdown or corrosive atmosphere. The IP rating covers the module and its mated connectors; it says nothing about the chemical resistance of the shell or the cable jacket.
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The adapter is the only place the channel map exists. Modules publish channel counts and data bytes; the adapter publishes the order in which those bytes appear to a scanner, so a replacement module in the same position needs no map change while a module moved to a new position does.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. This entry is for 1738-IE2VM12.
What this page does not claim matters as much as what it does. It states no cycle time, no maximum cable length and no network baud rate for this catalog number, because those belong to the segment and the adapter rather than to the module, and a figure of that kind copied into a page becomes a specification nobody can trace back to a publication. Where the source documents do fix a value - the channel count, the shell, the current limit, the isolation rating, the temperature window, the data size - it is on this page with the publication named.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint installation instructions (1738-IN001 for dc outputs, 1738-IN002 for dc inputs, 1738-IN003 for analog inputs and the temperature input instructions) and the DeviceNet adapter user manual 1738-UM001.
Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-IE2VM12.
This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 1738-IE2VM12 page is one entry in it. Reach it directly if the suffix on this record still needs confirming against a sibling.