This page documents catalog number 1738-AENT, the EtherNet/IP adapter for the ArmorPoint I/O family, Series B. It is the head of a sealed IP67 backplane: it carries the network address, the connections and the power budgets, and the figures below are quoted from the adapter installation instructions.
| Field | Value |
| Expansion capacity | 63 modules maximum; 5 rack-optimized connections for digital modules only and 31 direct connections |
| Backplane current | 1.0 A at 5 V dc from the adapter, extendable with 1738-EP24DC backplane extension power supplies and 1738-FPD modules |
| Supply input | 24 V dc at 500 mA or 12 V dc at 1.0 A, range 10 to 28.8 V dc, reverse polarity protected, inrush 6 A for 10 ms |
| Field side power | 24 V dc at 10 A maximum supplied, 10 to 28.8 V dc at 9 A delivered |
| POINTBus output | 5 V dc at 1.0 A maximum |
| Ethernet | 10/100 Mbit/s half or full duplex, 1 port, M12 D-coded female with Ethernet keying, Category 5 shielded or unshielded cable, star or tree topology |
| Power consumption | 8.1 W at 28.8 V dc; dissipation 2.8 W and 9.5 BTU/hr |
| Isolation | type tested at 500 V ac for 60 s between communications and system, communications and user power, system and ground, user power and ground, user power and system |
| Connectors | M12 D-coded female for Ethernet with pins 1 Tx plus, 2 Rx plus, 3 Tx minus, 4 Rx minus; 4-pin mini male for power with pin 1 user power plus, pin 2 adapter power plus, pin 3 adapter power minus, pin 4 user power minus |
| Dimensions | 112.0 x 72.0 x 65.0 mm (4.41 x 2.83 x 2.56 in.), 0.36 kg (0.8 lb) |
| Enclosure | meets IP65/66/67/69K when marked |
| Network switches | rotary address switches ship set to 999 with DHCP enabled |
| Terminating base | ships with the adapter and is mounted as the last base on the backplane instead of the I/O base |
| Keyswitch | adapter occupies the starter position at the left side of the system |
The adapter publication prints the PointBus current of every module in the family, and that table is the one a segment is planned from. The values below are the ones that differ from the 75 mA baseline:
| Module | PointBus current at 5 V dc |
| 1738-IB4DM12 | 50 mA |
| 1738-IB2M12, IB4M12, IB4M8, IB8M8, IB8M12, IB8M23, IB16DM12, IV4M12, IV8M8, IV8M12, IV8M23 | 75 mA |
| Digital and analog output and input modules listed at 75 mA, including OB2EM12, OB4EM8, OB4EM12, OB8EM8, OB8EM12, OB8EM23, OB2EPM12, OV4EM12, IE2CM12, IE4CM12, IE2VM12, OE2CM12, OE4CM12, OE2VM12 | 75 mA |
| 1738-8CFGM8, 8CFGM23, 8CFGDLXM8, 8CFGDLXM12, 8CFGDLXM23, 8CFGM12 | 100 mA |
| 1738-VHSC24M23 | 110 mA |
| 1738-OB16E25DS, OB16E19M23, OB16EM12 | 150 mA |
| 1738-IJM23 | 160 mA |
| 1738-IT2IM12 | 175 mA |
| 1738-IR2M12 | 220 mA |
The adapter is the head of a backplane, and the number that decides the architecture is 63: that is the module ceiling, reached in practice by inserting 1738-EP24DC extension power supplies and 1738-FPD modules rather than by accepting a shorter segment. A single adapter supplies 1.0 A at 5 V dc to the backplane, and that allowance is the one to add up before the module list is fixed.
Connection count is the second limit and it is expressed in two ways: five rack-optimized connections that cover digital modules only, and 31 direct connections where each module keeps its own rate and its own connection. A segment built entirely from analog and specialty modules cannot be rack-optimized, and the 31 direct connections become the ceiling before the 63-module one does.
Power is split three ways on this adapter: the 24 V dc input (or 12 V dc at 1.0 A) feeds the internal converter, the converter produces 5 V dc on POINTBus at 1.0 A, and the field side passes 24 V dc through at up to 10 A with 9 A available at the output. The 6 A inrush for 10 ms is the number a 24 V supply has to survive on a cold start, and reverse polarity protection means a miswired feed does not destroy the adapter.
Addressing ships unlocked rather than fixed: the rotary switches arrive at 999 with DHCP enabled, so an adapter that is powered before an address is assigned joins whatever DHCP server answers. Setting the switches and disabling DHCP is a commissioning step, not a factory default, and a segment that never had that step taken is a segment whose address can move after a power cycle.
The Ethernet port is a single D-coded M12 and the isolation is a 500 V ac type test rather than the 1,250 V ac test used on the I/O modules, which is the difference between a communication port and a field I/O port. The terminating base that ships with the adapter belongs at the end of the backplane; leaving it in the box leaves the last module without its termination.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
Every module in this family carries a green and red module-status indicator, a network-status indicator and per-channel yellow or red status, all on the logic side, so a technician diagnoses a channel from the face of the module rather than from a wiring diagram.
What this page does not claim matters as much as what it does. It does not state a cable length, a topology depth or a scan rate for this adapter, because those follow from the network design rather than from the catalog number; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and capacity figures are quoted from the ArmorPoint I/O EtherNet/IP adapter installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Of the 42 1738 records carried here, these twelve stand closest to this catalog number. This page is 1738-AENT.
Site tree: the Allen Bradley Other PLC index carries 1738-AENT together with the other entries of the other-PLC group, which is where a catalogue walk usually starts. The index sits one level above this page in the site tree.
Sources. Rockwell publishes the ArmorPoint I/O installation instructions as 1738-IN014, the EtherNet/IP adapter user manual as 1738-UM005 and the family user manual as 1738-UM001. The adapter role, node capacity and connector types quoted on this page for 1738-AENT follow those publications.
Data sources: the adapter and connection rows quoted on this page for 1738-AENT follow 1738-UM001 (ArmorPoint I/O user manual) and 1738-IN014 (ArmorPoint I/O installation instructions); nothing here is inferred from the catalog string.