This page documents catalog number 1738-ACNR, the ControlNet adapter for the ArmorPoint I/O family, Series A. It is the head of a sealed IP67 backplane on a ControlNet segment, with redundant coaxial ports, and the figures below are quoted from the ControlNet adapter installation instructions.
| Field | Value |
| Expansion capacity | 63 modules maximum; 5 rack-optimized connections for digital modules only and 25 direct connections |
| Backplane current | 1.0 A at 5 V dc maximum, extendable by 1.3 A per 1738-EP24DC up to 63 modules |
| Network connectors | two redundant TNC coaxial connectors, ControlNet A and B |
| Node address | two rotary switches, X10 and X1, settable from 01 to 99, read periodically and at power-up |
| PointBus output | 1 A at 5 V dc plus or minus 5 percent (4.75 to 5.25 V) |
| Auxiliary power | mini style power connector; 24 V dc field supply |
| Indicators | adapter status, two ControlNet status, PointBus status, system power and adapter power |
| Dimensions | 112 x 72 x 65 mm (4.41 x 2.83 x 2.56 in.) |
| Terminating base | ships with the adapter and is mounted as the last base on the backplane |
| Keyswitch | starter position, left side of the system |
The adapter publication prints the PointBus current of each module class, and that table is what a segment is added up from before the module list is fixed:
| Module | PointBus current |
| 1738-IB4xxx, IB8xxx, IV4xxx, OB4Exxx, OB8Exxx, OV4EM12, IE2VM12 | 75 mA |
| 1738-OW4xxx | 90 mA |
| 1738-SSIM23 | 110 mA |
| 1738-IJM23 | 160 mA |
| 1738-IT2IM12 | 175 mA |
| 1738-VHSC24M23 | 180 mA |
| 1738-IR2M12 | 220 mA |
Twenty-five direct connections is the number that separates this adapter from the EtherNet/IP members of the family, which allow thirty-one. A segment built from analog and specialty modules, where every module needs its own connection, reaches its ceiling at twenty-five rather than at sixty-three, and that is a planning figure nobody reads off the module count.
The two TNC connectors are redundant paths on the same media, not two segments: ControlNet A and B carry the same schedule and a break on one is survived rather than routed around. The adapter reports each port separately, which is how a technician tells a failed cable from a failed node.
Node addressing is decimal on two switches, X10 and X1, from 01 to 99, and this adapter reads the switches periodically rather than only at power-up. If the switch setting no longer matches the online address, the adapter raises a minor fault shown as a flashing red adapter status indicator, which is the behaviour that distinguishes a changed address from a broken network.
One ampere of backplane current is the budget before an extension supply is added, and each 1738-EP24DC adds 1.3 A rather than restoring the adapter allowance. The terminating base that ships with the adapter belongs at the end of the backplane, and this family reaches its 63 module maximum only with those extension units in place.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. This entry is for 1738-ACNR.
What this page does not claim matters as much as what it does. It does not state a media length, a network update time or a redundancy recovery time for this adapter, because those are properties of the ControlNet segment rather than of the catalog number; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The capacity, addressing and environmental figures are quoted from the ArmorPoint ControlNet adapter installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
The adapter publishes the 5 V PointBus current of every module class in the family, and that table is what a segment is added up from before the module list is fixed. The last two columns are that publication arithmetic carried one step further: how many of each class the adapter carries on its own 1.0 A budget, and how many more each 1738-EP24DC buys with its 1.3 A.
| Module class | Printed PointBus current | On the adapter 1.0 A | Per 1738-EP24DC 1.3 A |
| 1738-IB2M12, IB4xxx, IB8xxx, IV4xxx, OB2EM12, OB2EPM12, OB4Exxx, OB8Exxx, OV4EM12, IE2CM12, OE2CM12, IE2VM12, OE2VM12, IA2xxx, OA2xxx, 232ASCM12, 485ASCM12 | 75 mA | 13 modules | 17 more |
| 1738-OW4xxx | 90 mA | 11 modules | 14 more |
| 1738-SSIM23 | 110 mA | 9 modules | 11 more |
| 1738-IJM23 | 160 mA | 6 modules | 8 more |
| 1738-IT2IM12 | 175 mA | 5 modules | 7 more |
| 1738-VHSC24M23 | 180 mA | 5 modules | 7 more |
| 1738-IR2M12 | 220 mA | 4 modules | 5 more |
Where this adapter sits: 1738-ACNR is the ControlNet head of the family, with redundant TNC A and B connectors, and the class table above is the one this page prints. The same 1.0 A budget applies to what hangs to the right of it, and the 63-module ceiling printed beside that budget is the limit that has to be checked separately, because 63 modules spread across classes does not cost the same current twice.
Read the table by class rather than by module: three of the seven bands hold one catalog number each, and those three - SSI, resolver and high-speed counter - are the ones that decide where a second 1738-EP24DC goes.
What the printed data does not carry: neither adapter page states a maximum segment length in metres, and no class prints a start-up or inrush current on the PointBus, so the table sizes steady-state load only. Both numbers would be needed to size a supply against a cold start.
Source: Rockwell publication 1738-IN001 (ArmorPoint adapter installation instructions), PointBus current table; the per-supply column is that table divided by the printed 1.0 A and 1.3 A budgets. No figure here is estimated.
Twelve of the 42 1738 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1738-ACNR.
Group index: Allen Bradley Other PLC. 1738-ACNR is filed under that heading in the site's own product tree. Sibling codes of the same group are one click away from that page.