Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 1738-8CFGM23, an ArmorPoint module with eight configurable 24 V dc points, Series A, wired through a single M23 connector. The configuration behaviour matches the M12 sibling; what differs is the physical interface, and the figures below are quoted from the configurable point module installation instructions.
| Field | Value |
| Points | 8, each independently configurable as an input or an output |
| On-state current | 2.0 mA minimum, 5.0 mA maximum |
| Off-state voltage | 5 V dc maximum |
| On-state voltage range | 10 to 28.8 V dc, 24 V dc nominal |
| Off-state current | 15 mA maximum |
| Output per point | 0.5 A maximum |
| Module current, all outputs | 3.0 A maximum |
| Surge current | 1.0 A for 100 ms, repeatable every 2 s |
| Input filter | each input set independently in 1 ms steps, truncated to 1 ms resolution, default 1000 ms |
| PointBus current | 100 mA at 5 V dc maximum |
| Power dissipation | 2.6 W at 28.8 V dc |
| Isolation | 50 V continuous, reinforced insulation, type tested at 2,121 V dc for 60 s, field side to system, no isolation between channels |
| Field power bus | 24 V dc nominal, 11 to 28.8 V dc range |
| Dimensions | 120 x 72 x 42 mm (4.72 x 2.83 x 4.25 in.), 290 g |
| Keyswitch position | 1 |
| Enclosure | meets IP65/66/67/69K when marked |
| Pin | Function |
| 1 to 8 | I/O points 0 to 7 |
| 9 | return (common) |
| 10 | return (common) |
| 11 | 24 V dc |
| 12 | chassis |
One M23 connector carries all eight points, the 24 V dc feed and two returns on a single 12-pin shell. In a panel where eight M12 cordsets would not fit, this is the catalog number that buys space, at the cost of a single harness that has to be built and dressed correctly the first time.
Two return pins are provided rather than one, which matters once several outputs drive inductive loads on the same shell; the chassis pin is separate from the returns and is where a shielded harness drain belongs. The keyswitch position, one, has to match the base or the module will not seat, and the field power bus accepts 11 to 28.8 V dc rather than only a nominal 24 V.
The single-shell design also changes commissioning order: because 24 V dc arrives on pin 11 of the same shell as the eight signals, the harness has to be proven pin by pin before the module is seated. On the M12 sibling a miswired point costs one cordset; here it costs the whole harness, and the two return pins on 9 and 10 are the place where a shared 0 V mistake shows up as an unexpected output.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. 1738-8CFGM23 is the number described on this page.
What this page does not claim matters as much as what it does. It does not state a point count that a given load will allow, because the limit is the 3.0 A module current and the 0.5 A per point rather than a count; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint configurable point module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 100 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 10 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 23 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 36 | two supplies, two extra banks |
| 63-module station, printed ceiling | 6300 mA at 100 mA | 63 | 5 expansion supplies needed |
Where this module sits: 1738-8CFGM23 draws 100 mA on the PointBus, which is band 3 of the seven published classes - 25 mA above the 75 mA class that most digital and analog modules sit in. At 8 points that is 12.5 mA of 5 V budget per point, so a full 63-module 1738-8CFGM23 station is 6300 mA and needs 5 expansion supplies.
Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 100 mA. No figure here is estimated.
Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-8CFGM23.