This page documents catalog number 1738-8CFGM12, an ArmorPoint module with eight configurable 24 V dc points, Series A. Each of the eight points is set as an input or an output independently rather than by module type, and the figures below are quoted from the configurable point module installation instructions.
| Field | Value |
| Points | 8, each independently configurable as an input or an output |
| On-state current | 2.0 mA minimum, 5.0 mA maximum |
| Off-state voltage | 5 V dc maximum |
| On-state voltage range | 10 to 28.8 V dc, 24 V dc nominal |
| Off-state current | 15 mA maximum |
| Output per point | 0.5 A maximum |
| Module current, all outputs | 3.0 A maximum |
| Surge current | 1.0 A for 100 ms, repeatable every 2 s |
| Input filter | each input set independently in 1 ms steps, truncated to 1 ms resolution, default 1000 ms |
| PointBus current | 100 mA at 5 V dc maximum |
| Power dissipation | 2.6 W at 28.8 V dc |
| Isolation | 50 V continuous, reinforced insulation, type tested at 2,121 V dc for 60 s, field side to system, no isolation between channels |
| Field power bus | 24 V dc nominal, 11 to 28.8 V dc range |
| Dimensions | 120 x 72 x 42 mm (4.72 x 2.83 x 4.25 in.), 290 g |
| Keyswitch position | 1 |
| Enclosure | meets IP65/66/67/69K when marked |
| Pin | Function |
| 1 | 24 V dc |
| 2 | not used |
| 3 | common |
| 4 | I/O point for connector A through H |
| 5 | not used |
Eight M12 connectors, one per point, each carrying 24 V dc on pin 1, common on pin 3 and the point itself on pin 4. That is a point-per-connector layout: a failed sensor is replaced by unplugging one cordset, and a point changed from input to output needs a load on that connector rather than a different module in the rack.
The module current of 3.0 A across all eight outputs is the real ceiling, and 0.5 A per point is the ceiling before that: eight outputs at full 0.5 A would be 4.0 A and the module stops at 3.0 A. Reconfiguring points to outputs therefore has a budget consequence, and it is a module-level budget rather than a per-channel one. The published surge allowance is 1.0 A for 100 ms repeatable every 2 s, which sizes lamp and solenoid inrush rather than steady current.
The input filter is the setting most often left at its default and most often wrong. It is set per input in 1 ms steps with a default of 1000 ms, and a 1000 ms filter on a point used for a cam or a part-present sensor turns a real edge into a missed one. Two milliseconds of debounce on a mechanical switch and one second on a switch are different modules in behaviour even though the catalog number is the same.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
The mounting base ships with the module, so a spare is ordered as a module and arrives with the metal that does the grounding; a panel that keeps bases in stock and swaps only modules is a panel that still has the old base under the new part.
What this page does not claim matters as much as what it does. It does not state a point count that a given load will allow, because the limit is the 3.0 A module current and the 0.5 A per point rather than a count; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint configurable point module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 100 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 10 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 23 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 36 | two supplies, two extra banks |
| 63-module station, printed ceiling | 6300 mA at 100 mA | 63 | 5 expansion supplies needed |
Where this module sits: 1738-8CFGM12 draws 100 mA on the PointBus, which is band 3 of the seven published classes - 25 mA above the 75 mA class that most digital and analog modules sit in. At 8 points that is 12.5 mA of 5 V budget per point, so a full 63-module 1738-8CFGM12 station is 6300 mA and needs 5 expansion supplies.
Read the three capacity rows from the top down and the shape of the decision is visible: the first supply more than doubles what the adapter carries, the second adds a fixed 1.3 A again, and the 63-module ceiling has to be checked separately because it binds at a different point for each class.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 100 mA. No figure here is estimated.