This page documents catalog number 1738-8CFGDLXM12, an ArmorPoint module with eight configurable 24 V dc points and an on-board DeviceLogix engine, Series A. It is the same eight-point hardware as 1738-8CFGM12 with local logic added, and the figures below are quoted from the DeviceLogix module installation instructions.
| Field | Value |
| Points | 8 configurable points plus an on-board DeviceLogix logic engine |
| On-state voltage | 11 V dc minimum, 10 V dc minimum on the range entry, 28.8 V dc maximum, 24 V dc nominal |
| On-state current | 2.0 mA minimum, 5.0 mA maximum |
| On-state voltage drop | 0.4 V dc maximum |
| Off-state voltage | 5 V dc maximum |
| Off-state leakage | 0.5 mA maximum |
| Output per point | 0.5 A maximum |
| Module current, all outputs | 3.0 A maximum |
| Filter | 0 to 65,535 ms independently for off-to-on and on-to-off, truncated to 1 ms |
| Produced data | 1, 8 or 20 bytes depending on the produced assembly, default 20 bytes |
| Consumed data | 1, 8 or 20 bytes, default 20 bytes |
| PointBus current | 100 mA at 5 V dc maximum |
| Power dissipation | 2.6 W at 28.8 V dc (8.9 BTU/hr) |
| Isolation | 50 V continuous, reinforced insulation, type tested at 2,121 V dc for 60 s |
| Configuration tool | RSNetWorx for DeviceNet |
| Keyswitch position | 1 |
| Enclosure | meets IP65/66/67/69K when marked |
| Pin | Function |
| 1 | 24 V dc |
| 2 | not used |
| 3 | common |
| 4 | I/O point for connector A through H |
| 5 | not used |
The logic runs in the module rather than in the controller, and the publication states what that changes: outputs can continue to be controlled through a communication fault when the communication fault override is enabled, and the masterless produce setting lets the module begin producing at power-up and keep producing after a connection is terminated. Both are configuration bits, both default disabled, and neither is a substitute for a safety function.
The assembly sizes are the second practical difference: the module produces and consumes 1, 8 or 20 bytes, defaulting to 20, and it can be told to use rack assembly 4 and consume rack assembly 34, which is how a digital rack-optimized connection reaches it. Filter time is settable from 0 to 65,535 ms in each direction, with 1,000 us as the default, and fault and idle behaviour per point is chosen between a fault value and hold last state. Configuration is done in RSNetWorx for DeviceNet, which is also where the peer consume message lengths for the eight points are set.
A local logic module is also a diagnostics decision. Because the outputs can be driven without the controller, a machine can keep cycling after the network drops, and that behaviour has to be a deliberate choice rather than a discovered one: the communication fault override and the masterless setting are the two bits that produce it, and both are off by default for that reason.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The family is designed so that the module is the replaceable unit and the base stays on the machine. That is why the base is ordered with the module, why the keyswitch on the base has to match the module class, and why the ground lug is also a mounting hole: the conductive path runs through the base and the plate rather than through the module. Swapping a module onto a dirty base is the failure that looks like a module fault and measures as a missing earth.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. The catalog number covered on this page is 1738-8CFGDLXM12.
What this page does not claim matters as much as what it does. It does not state a point count that a given load will allow, because the limit is the 3.0 A module current and the 0.5 A per point rather than a count; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical and environmental figures are quoted from the ArmorPoint configurable point module installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 100 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 10 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 23 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 36 | two supplies, two extra banks |
| 63-module station, printed ceiling | 6300 mA at 100 mA | 63 | 5 expansion supplies needed |
Where this module sits: 1738-8CFGDLXM12 draws 100 mA on the PointBus, which is band 3 of the seven published classes - 25 mA above the 75 mA class that most digital and analog modules sit in. At 8 points that is 12.5 mA of 5 V budget per point, so a full 63-module 1738-8CFGDLXM12 station is 6300 mA and needs 5 expansion supplies.
The station ceiling and the current budget are two different limits and only one of them is printed as a module count. At this draw the ceiling is reached at 6300 mA, so the supply count - not the module count - is the number that decides whether the segment is possible.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 100 mA. No figure here is estimated.
This page links twelve of the 42 1738 records on this site; the closest rating codes come first. This page is 1738-8CFGDLXM12.
For the surrounding range, open the Allen Bradley Other PLC catalogue index — 1738-8CFGDLXM12 is listed there beside the rest of the other-PLC group. The index sits one level above this page in the site tree.