This page documents catalog number 1738-485ASCM12, a RS-485 ASCII module, M12 connector in the ArmorPoint I/O family. It is the serial front end of the family: a sealed IP67 module that puts one RS-485 port on the backplane and exchanges that port with the master as polled, cyclic or change-of-state data. The figures below are quoted from the installation instructions for this module.
| Field | Value |
| Number of inputs | 1, full duplex |
| Connector | M12 (micro), 5-pin: pin 1 Tx minus, pin 2 Tx plus, pin 3 Rx plus, pin 4 Rx minus, pin 5 no connect |
| Signal levels, A to B | 0 asserted: plus 1.5 to plus 6 V dc transmitted, plus 0.2 to 12 V dc received; 1 deasserted: minus 1.5 to plus 6 V dc transmitted, plus 0.2 to 7 V dc received |
| External supply | 24 V dc nominal, 10 to 28.8 V dc range, 15 mA at 24 V dc, fault protected to 28.8 V dc |
| Serial framing | 7N2, 7E1, 7O1, 8N1, 8N2, 8E1, 8O1, 7E2, 7O2 |
| Serial speed | 1200, 2400, 4800, 9600, 19.2k, 38.4k baud |
| Characters per record | 1 to 128 received and 1 to 128 transmitted |
| Assembly size | 4 to 132 bytes produced, 4 to 132 bytes consumed |
| Dimensions | 111.6 x 71.6 x 38.4 mm (4.39 x 2.82 x 1.51 in.), 217 g |
| Keyswitch position | 2 (specialty) |
| PointBus current | 75 mA at 5 V dc |
| Power dissipation | 0.75 W at 28.8 V dc (2.5 BTU/hr) |
| Isolation | 50 V rms continuous, type tested at 1,250 V ac rms for 60 s |
| Wiring category | 2 on communications ports |
The port is full duplex and the pinout is the part that decides whether an existing device works: Tx minus, Tx plus, Rx plus and Rx minus on pins 1 to 4 means a four-wire RS-485 device lands directly and a two-wire device has to be looped, which is a wiring decision and not a module setting.
The module produces and consumes 4 to 132 bytes, and the record delimiters are configurable rather than fixed: start and end delimiters can be excluded, included or absent, the data can be swapped in 16, 24 or 32 bit groups and padded, and that flexibility is what lets one catalog number serve a barcode reader, a weighing terminal and a drive that speaks its own protocol.
Both FIFOs report overflow, parity error and handshake error in the status, which is the difference between a serial module that silently drops a record and one that tells the controller the record was dropped. The transmit and receive indicators on the module face are the field check for a reversed pair before the scanner is blamed.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
Connector shells are the part of the ordering decision a drawing rarely shows. M8 is a single-pin pico shell, M12 is a four or five pin micro shell, M23 is a twelve pin shell, and the same channel count can be delivered in three different shell sizes with three different cable preparations. A plant that standardises on M12 cord sets buys the M12 variant; a plant that already runs M8 patch cables buys the M8 variant and gets the same eight channels in eight single-pin shells, and the field wiring effort differs accordingly.
Every module in this family carries a green and red module-status indicator, a network-status indicator and per-channel yellow or red status, all on the logic side, so a technician diagnoses a channel from the face of the module rather than from a wiring diagram. This page documents 1738-485ASCM12.
What this page does not claim matters as much as what it does. It does not invent a cable length, a maximum encoder distance or a scan time for this catalog number, because those follow from the device on the other end of the connector and from the segment; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Every module in this family takes its 5 V PointBus current from the adapter, and the adapter publishes a 1.0 A budget with 1.3 A added per 1738-EP24DC. The table turns that into a module count for this page's printed draw, which is the arithmetic done when a segment is planned rather than after it browns out.
| Configuration | PointBus available | Modules at 75 mA | What that means |
| 1738-APB or 1738-ACNR alone | 1,000 mA | 13 | adapter budget, no expansion supply |
| Adapter plus one 1738-EP24DC | 2,300 mA | 30 | one supply fitted after the first bank |
| Adapter plus two 1738-EP24DC | 3,600 mA | 48 | two supplies, two extra banks |
| 63-module station, printed ceiling | 4725 mA at 75 mA | 63 | 3 expansion supplies needed |
Where this module sits: 1738-485ASCM12 draws 75 mA on the PointBus, which is band 1 of the seven published classes. A full 63-module station of this type is 4725 mA and needs 3 expansion supplies, which is the number to check before the module list is fixed.
The count in the second column is where a segment stops, not where it fails: an adapter with 13 modules of this draw leaves the thirteenth with no margin, and the printed answer is to fit a 1738-EP24DC rather than to shorten the bank.
What the printed data does not carry: this page prints no start-up or inrush current on the PointBus and no maximum number of modules between two power supplies, so the table sizes steady-state load only. The 5 to 17 module reach is printed for the 1738-EP24DC, not for the modules it feeds.
Source: Rockwell publication 1738-IN001, adapter and expansion power supply PointBus budgets; the module count is 1,000 mA, 2,300 mA and 3,600 mA divided by this page's printed 75 mA. No figure here is estimated.
Twelve of the 42 1738 records carried on this site, ordered by how close their codes sit to this one. This page is 1738-485ASCM12.
This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 1738-485ASCM12 page is one entry in it. It is the entry point used when a project list is assembled group by group.