|
Product Details:
Payment & Shipping Terms:
|
20BB2P2A3AYNBNC0 is a PowerFlex 700 drive, catalog code b=B: 240 V AC, 3-phase, 50/60 Hz.
The three digits after the voltage letter are the output current in amps - here 2.2 A. Published ratings: 0.5 HP, frame 0.
Quick answer. 20BB2P2A3AYNBNC0 is a PowerFlex 700 drive, 240 V AC, normal duty, frame 0, A - IP 20, NEMA/UL Type 1, with conformal coating.
| 20BB9P6A3AYNBNC0 | 9.6 A | IN STOCK |
| 20BB9P6A0AYNBNC0 | 9.6 A | IN STOCK |
| 20BB6P8A0AYNBNC0 | 6.8 A | IN STOCK |
| 20BB4P2A0AYNBND0 | 4.2 A | IN STOCK |
| 20BB4P2A0AYNBNC0 | 4.2 A | IN STOCK |
| 20BB2P2A3AYNBNC0 | 2.2 A | IN STOCK |
| 20BB2P2A0AYNBNC0 | 2.2 A | IN STOCK |
| 20BB260A3AYNANC0 | 260 A | IN STOCK |
| 20BB260A0AYNANC0 | 260 A | IN STOCK |
| 20BB192A0AYNANC0 | 192 A | IN STOCK |
| 20BB192A0ANNANC0 | 192 A | IN STOCK |
| 20BB154A3ANNANC0 | 154 A | IN STOCK |
| 20BB154A0AYNANC0 | 154 A | IN STOCK |
| 20BB154A0ANNANC0 | 154 A | IN STOCK |
| 20BB130A0ANNANC0 | 130 A | IN STOCK |
Catalog number |
20BB2P2A3AYNBNC0 |
Voltage rating (b) |
B - 240 V AC, 3-phase, 50/60 Hz |
Output current rating (c) |
2.2 A |
Normal duty rating |
0.5 HP |
Frame size |
0 |
Enclosure (d) |
A - IP 20, NEMA/UL Type 1, with conformal coating |
HIM (e) |
3 - LCD display, full numeric keypad |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
B - CE filter fitted, no CM choke (200-240 V frame 0-3 only) |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Vector control, 24 V DC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
2P2 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell rating tables |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), B (voltage), 2P2 (output current in amps), then nine option positions d to l.
Here: d=A, e=3, f=A, g=Y, h=N, i=B, j=N, k=C, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): IP 20, NEMA/UL Type 1, with conformal coating.
HIM (e): LCD display, full numeric keypad. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): Brake IGBT fitted. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): CE filter fitted, no CM choke (200-240 V frame 0-3 only). Comm slot (j): None. Control and I/O (k): Vector control, 24 V DC I/O. Feedback (l): No feedback.
A 20BD drive is the 480 V AC three-phase member of the PowerFlex 700 family: three-phase input, three-phase output, 0 to rated motor voltage on the output.
The current code is the drive output current in amps, so the same code reappears across the 400 V and 480 V families with different kW values - the kW figure here is the 480 V one.
Sensorless vector control with full tuning is standard; the k position decides whether the I/O is 24 V DC/AC or 115 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BB2P2A3AYNBNC0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BB2P2A3AYNBNC0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BB2P2A3AYNBNC0?
PowerFlex 700 drive, 240 V AC, 3-phase, 50/60 Hz, 2.2 A output.
What is the output current of 20BB2P2A3AYNBNC0?
2.2 A.
What does the B code mean?
240 V AC, 3-phase, 50/60 Hz.
Does 20BB2P2A3AYNBNC0 have a communication option?
None.
What enclosure is 20BB2P2A3AYNBNC0?
IP 20, NEMA/UL Type 1, with conformal coating.
Related catalog numbers in the same rating code as 20BB2P2A3AYNBNC0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20BB9P6A3AYNBNC0 (9.6 A) · 20BB9P6A0AYNBNC0 (9.6 A) · 20BB6P8A0AYNBNC0 (6.8 A) · 20BB4P2A0AYNBND0 (4.2 A) · 20BB4P2A0AYNBNC0 (4.2 A) · 20BB2P2A0AYNBNC0 (2.2 A) · 20BB260A3AYNANC0 (260 A) · 20BB260A0AYNANC0 (260 A) · 20BB192A0AYNANC0 (192 A)
20BB2P2A3AYNBNC0 is a PowerFlex 700 drive on the 240V AC voltage code. The number splits into 20B for the product line, B for 240V AC three-phase, 2P2 for the output current code, and the enclosure, HIM, brake, resistor, EMC and communication fields after it. The rating, frame and protection devices below are the ones the 208V input protection table assigns to this current code.
| Attribute | Value |
| Catalog number | 20BB2P2A3AYNBNC0 |
| Voltage code | B, 240V AC three-phase |
| Current code | 2P2 |
| Frame | 0 |
| Rating at 240V | 0.5 hp / 0.33 kW |
| PWM frequency / ambient | 4 kHz at 50 degC |
| Motor circuit protector | 140M-C2E-B25 or 140M-D8E-B25 |
| Input reactor basis | NEC fundamental motor amps, 4 percent impedance |
| Output reactor basis | VFD rated output current, 4 percent impedance |
| Terminal capacity | Frame dependent, 12 AWG...22 AWG on frames 0 and 1 up to 1 AWG on frame 5 |
The current code is the output current the frame is rated to deliver, not the motor rating: 2.2 amperes is what the drive supplies continuously, and the horsepower column is the published pairing for a 240V motor. A motor whose nameplate current exceeds that value is not made acceptable by the horsepower pairing, and a motor well under it runs with its own overload device doing the limiting.
Duty changes the reactor, not the drive: the same catalog number appears twice in the reactor table, once as Heavy Duty and once as Normal Duty, and the two rows do not always carry the same part. A 20BB042 on a 10 hp heavy-duty load and the same hardware on a 15 hp normal-duty load differ in the thermal assumption, and the reactor follows the assumption.
Past the last row that prints a 140M manual motor protector, the branch protection for this rating comes from the fuse, non-time-delay fuse and circuit breaker columns rather than from a motor-protector selection. That is a change in the protection scheme and has to be shown on the panel drawing, not silently dropped from the bill of materials.
In the 20B bulletin the fourth character of the catalog number is the voltage: B is 240V AC, C is 400V AC, D is 480V AC, E is 600V AC, F is 690V AC, with H, J and N reserved for DC input variants. Frames 7, 8, 9 and 10 are no longer available for sale, so a specification that calls for one of those sizes is a replacement decision that has to be taken before the panel is drawn.
The external control supply is specified rather than assumed: 300V DC in UL installations and 270 to 600V DC outside UL, with frames 0 to 3 drawing 40 W and 165 mA and frame 5 drawing 80 W and 90 mA. Supplying the control board from a 24V DC distribution is a different design, not a variation of this one.
Before ordering, confirm the voltage code against the actual bus, the current code against the motor nameplate current rather than its horsepower, and the frame against the terminal capacity the field wiring needs. The frame is what the enclosure, the reactor pair and the protection schedule are all built on, so it is the one field worth confirming twice.
Related models, options and spare parts for this range are listed in the Allen-Bradley PowerFlex drives and motors category.