20BB260A3AYNANC0 is a PowerFlex 700 drive, catalog code b=B: 240 V AC, 3-phase, 50/60 Hz.
The three digits after the voltage letter are the output current in amps - here 260 A. Published ratings: 100 HP, frame 6.
Quick answer. 20BB260A3AYNANC0 is a PowerFlex 700 drive, 240 V AC, normal duty, frame 6, A - IP 20, NEMA/UL Type 1, with conformal coating.
| 20BB9P6A3AYNBNC0 | 9.6 A | IN STOCK |
| 20BB9P6A0AYNBNC0 | 9.6 A | IN STOCK |
| 20BB6P8A0AYNBNC0 | 6.8 A | IN STOCK |
| 20BB4P2A0AYNBND0 | 4.2 A | IN STOCK |
| 20BB4P2A0AYNBNC0 | 4.2 A | IN STOCK |
| 20BB2P2A3AYNBNC0 | 2.2 A | IN STOCK |
| 20BB2P2A0AYNBNC0 | 2.2 A | IN STOCK |
| 20BB260A3AYNANC0 | 260 A | IN STOCK |
| 20BB260A0AYNANC0 | 260 A | IN STOCK |
| 20BB192A0AYNANC0 | 192 A | IN STOCK |
| 20BB192A0ANNANC0 | 192 A | IN STOCK |
| 20BB154A3ANNANC0 | 154 A | IN STOCK |
| 20BB154A0AYNANC0 | 154 A | IN STOCK |
| 20BB154A0ANNANC0 | 154 A | IN STOCK |
| 20BB130A0ANNANC0 | 130 A | IN STOCK |
| 20BB130A0AYNANC0 | 130 A | IN STOCK |
| 20BB104A0AYNANC0 | 104 A | IN STOCK |
Catalog number |
20BB260A3AYNANC0 |
Voltage rating (b) |
B - 240 V AC, 3-phase, 50/60 Hz |
Output current rating (c) |
260 A |
Normal duty rating |
100 HP |
Frame size |
6 |
Enclosure (d) |
A - IP 20, NEMA/UL Type 1, with conformal coating |
HIM (e) |
3 - LCD display, full numeric keypad |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
A - CE filter fitted, CM choke fitted |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Vector control, 24 V DC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
260 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell rating tables |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), B (voltage), 260 (output current in amps), then nine option positions d to l.
Here: d=A, e=3, f=A, g=Y, h=N, i=A, j=N, k=C, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): IP 20, NEMA/UL Type 1, with conformal coating.
HIM (e): LCD display, full numeric keypad. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): Brake IGBT fitted. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): CE filter fitted, CM choke fitted. Comm slot (j): None. Control and I/O (k): Vector control, 24 V DC I/O. Feedback (l): No feedback.
A 20BD drive is the 480 V AC three-phase member of the PowerFlex 700 family: three-phase input, three-phase output, 0 to rated motor voltage on the output.
The current code is the drive output current in amps, so the same code reappears across the 400 V and 480 V families with different kW values - the kW figure here is the 480 V one.
Sensorless vector control with full tuning is standard; the k position decides whether the I/O is 24 V DC/AC or 115 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BB260A3AYNANC0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BB260A3AYNANC0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BB260A3AYNANC0?
PowerFlex 700 drive, 240 V AC, 3-phase, 50/60 Hz, 260 A output.
What is the output current of 20BB260A3AYNANC0?
260 A.
What does the B code mean?
240 V AC, 3-phase, 50/60 Hz.
Does 20BB260A3AYNANC0 have a communication option?
None.
What enclosure is 20BB260A3AYNANC0?
IP 20, NEMA/UL Type 1, with conformal coating.
Related catalog numbers in the same rating code as 20BB260A3AYNANC0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20BB9P6A3AYNBNC0 (9.6 A) · 20BB9P6A0AYNBNC0 (9.6 A) · 20BB6P8A0AYNBNC0 (6.8 A) · 20BB4P2A0AYNBND0 (4.2 A) · 20BB4P2A0AYNBNC0 (4.2 A) · 20BB2P2A3AYNBNC0 (2.2 A) · 20BB2P2A0AYNBNC0 (2.2 A) · 20BB260A0AYNANC0 (260 A) · 20BB192A0AYNANC0 (192 A)
20BB260A3AYNANC0 is a PowerFlex 700 drive on the 240V AC voltage code, and its current code 260 places it beyond the frame 0 to 5 rows where the bulletin prints the 208V input protection table. The frame, the continuous rating and the recommended branch protection for this size therefore have to be read from the drive rating tables in the bulletin instead of from the short rows reproduced here.
| Attribute | Value |
| Catalog number | 20BB260A3AYNANC0 |
| Voltage code | B, 240V AC three-phase |
| Current code | 260 |
| Frame | confirm against the rating table for this current code |
| Frames no longer available | 7, 8, 9 and 10 |
| Reactor sizing | Input on NEC fundamental motor amps, output on VFD rated output current |
| Terminal capacity | Frame dependent, up to 1 AWG on frame 5 and 300 MCM on brake and PE of the larger frames |
| External control supply | 300V DC UL, 270...600V DC non-UL |
A current code above the published 240V rows is exactly the case where a catalog number is quoted from a distributor listing rather than from the bulletin, and the numbers that decide the installation, the frame, the continuous current and the recommended protection, do not travel with the listing. Establishing the frame first is what makes the rest usable, because the enclosure, the reactor pair and the protection devices are all selected around it.
Protection coordination is the working content of the 208V table: each row pairs the current code with an input rating, an output current rating, a dual-element time-delay fuse, a non-time-delay fuse, a circuit breaker and a motor circuit protector, and the 140M manual motor protector is printed with the adjustable range that suits that rating. Choosing the fuse alone and calling the circuit protected leaves the coordination gap that the table exists to close.
PowerFlex 700 is a general-purpose drive whose frame decides almost everything else in the panel: terminal capacity, mounting footprint, heat, reactor pairing and protection devices all follow from the frame, and the frame follows from the current code rather than from the horsepower. That is why two drives of the same horsepower on different voltages are different catalog numbers, and why a spare kept by horsepower is not a spare.
Terminal capacity steps with the frame and cannot be carried across sizes: frames 0 and 1 accept 12 AWG to 22 AWG at 1.7 to 0.8 N m, frame 2 accepts 8 AWG to 18 AWG at 1.7 to 1.4 N m, frame 3 accepts 3 AWG to 14 AWG at 3.6 to 1.8 N m, frame 4 accepts 3 AWG at 4.0 N m, and frame 5 accepts 1 AWG with 2/0 for the 75 hp rating. Brake and PE terminals on the larger frames take 300 MCM at 6.0 N m and the shield terminal is rated 1.6 N m.
Before ordering, confirm the voltage code against the actual bus, the current code against the motor nameplate current rather than its horsepower, and the frame against the terminal capacity the field wiring needs. The frame is what the enclosure, the reactor pair and the protection schedule are all built on, so it is the one field worth confirming twice.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley PowerFlex drives and motors category.