Product Details:
Payment & Shipping Terms:
|
The 2711P-RN20 is Communication module for the PanelView Plus range: Communication Module, Ethernet, PanelView Plus 6 700-1500.
the communication module plugs into the rear slot of a 700...1500 terminal and adds a fieldbus that standard Ethernet and RS-232 cannot reach
| 2711P-RN6 | DH+/DH-485/Remote I/O Communication Module for PanelView Plus 700-1500 and PanelView Plus CE | IN STOCK |
| 2711P-RN6K | DH+/DH-485 Communication Module for Conformal Coated PanelView Plus 6 | IN STOCK |
| 2711P-RN10H | DeviceNet Communication Module for PanelView Plus 700-1500 and PanelView Plus CE | IN STOCK |
| 2711P-RN15S | ControlNet Scheduled and Unscheduled Communication Module for Marine Certified PanelView Plus 700-1500 and PanelView Plus CE | IN STOCK |
| 2711P-RN15SK | ControlNet Communication Module for Conformal Coated PanelView Plus 6 | IN STOCK |
| 2711P-RN20 | Communication Module, Ethernet, PanelView Plus 6 700-1500 | IN STOCK |
Application |
Communication Module, Ethernet, PanelView Plus 6 700-1500 |
Cat Num |
2711P-RN20 |
Brand Name |
Rockwell |
Product Type |
Communication module |
Protocol |
EtherNet/IP |
Network |
Standard 10...1000 speed |
Fits |
PanelView Plus 6 700...1500 |
Lifecycle |
Discontinued September 30, 2021 |
Replacement |
No planned Rockwell replacement |
Fits Family |
PanelView Plus 6 700...1500 terminals |
2711P-RN20 (communication module): field-installable module that gives a PanelView Plus 6 700 to 1500 terminal a second Ethernet port connectivity.
How it wires: every PanelView Plus 6 terminal already has one Ethernet port; this module adds a second one with its own IP address, which is how a terminal is put on a plant network and a machine-level network at the same time. Link settings are not configurable in FactoryTalk View ME Station - the module senses the network settings automatically. The module mounts over the logic module and is the last part fitted - logic module to display module first, then the communication module, four screws at 0.58 N·m (5...7 lb·in). Source: Rockwell publication 2711P-UM006, Table 17 (Communication Modules 700 to 1500), Tables 74 to 77 (terminal-to-controller cable tables) and the communication module installation procedure.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2711P-UM006 (module specifications) and 2711P-TD001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: Communication Module, Ethernet, PanelView Plus 6 700-1500.
Spare-part role: the communication module plugs into the rear slot of a 700...1500 terminal and adds a fieldbus that standard Ethernet and RS-232 cannot reach.
This item, 2711P-RN20, is ordered by this catalog number alone; no terminal order is required, and the part is a service item, not a kit that includes a display or a logic module.
Protocol: EtherNet/IP.
Network: Standard 10...1000 speed.
Fits: PanelView Plus 6 700...1500.
Rockwell Automation discontinued 2711P-RN20 on September 30, 2021; the replacement category published for it is: No planned Rockwell replacement.
A discontinued spare is bought for one of three reasons: the machine is still in production and must keep the same front, the line is being cloned, or the panel is waiting for a planned migration and needs to run until then.
Check the terminal-side catalog number before ordering a replacement: a display module must match the input style of the front it sits on, and a logic module must match the power input (AC or DC) of the panel it serves.
The module sits in the rear slot of the terminal and appears to the application as an additional communication path; Ethernet and RS-232 stay active.
Protocol choice decides the module, not the terminal size: DH+/DH-485 and Remote I/O for legacy SLC networks, DeviceNet for device-level networks, ControlNet for scheduled and unscheduled control traffic, Ethernet for EtherNet/IP.
A conformal-coated module (suffix K) belongs on a conformal-coated terminal; mixing coated and uncoated parts leaves the coating envelope incomplete.
The part number, not the terminal model, is what identifies 2711P-RN20; a photograph of the old part and the terminal nameplate settle the match.
For a logic module, confirm the power input letter (A or D) and the operating-system digit (8 or 9) before ordering; for a display module, confirm the input style (touch, keypad, keypad/touch) and whether the terminal is standard, marine or high-bright. 2711P-RN20 is the exact string those fields have to match.
Ask for the date code when the part is a service exchange: an aged electrolytic or a lamp with run hours already on it costs the same as a fresh unit but fails sooner.
The table lists every catalog number of this part family that this site carries, with the official one-line description; the row in red is the item on this page.
Parts within one family are not interchangeable across rows: the description carries the size, the input style or the certification that separates them.
What is 2711P-RN20?
Communication Module, Ethernet, PanelView Plus 6 700-1500.
Which terminal does 2711P-RN20 fit?
PanelView Plus 6 700...1500.
Is 2711P-RN20 still available?
Rockwell discontinued it on September 30, 2021; replacement category: No planned Rockwell replacement.
What protocol does 2711P-RN20 speak?
EtherNet/IP.
Does 2711P-RN20 replace the built-in Ethernet port?
No. It adds a fieldbus alongside the standard Ethernet and RS-232 ports.
| Module | Fieldbus it adds | Terminals it fits | Build |
| 2711P-RN6 | DH+, DH-485 and Remote I/O | PanelView Plus 700...1500 and PanelView Plus CE | standard build |
| 2711P-RN6K | DH+ and DH-485 | PanelView Plus 6 700...1500 | conformal coated |
| 2711P-RN10H | DeviceNet | PanelView Plus 700...1500 and PanelView Plus CE | standard build |
| 2711P-RN15S | ControlNet, scheduled and unscheduled | PanelView Plus 700...1500 and PanelView Plus CE | marine certified |
| 2711P-RN15SK | ControlNet | PanelView Plus 6 700...1500 | conformal coated |
| 2711P-RN20 | Ethernet, second port | PanelView Plus 6 700...1500 | standard build |
Where this module sits: 2711P-RN20 is the second-Ethernet entry and the only one whose value is an address rather than a protocol. It fits Plus 6 terminals only, so it is not a route to put an older Plus 700...1500 on a plant network.
The four-screw, 0.58 N·m (5...7 lb·in) mount is common to all six modules, and it is the step people skip: a module fitted over a logic module that is not seated shows up as an intermittent network fault rather than as a dead port.
What the printed data does not carry: no module in this table states its own current draw from the terminal supply, and no module states a maximum cable length for its fieldbus. Both numbers live in the terminal and network documentation rather than on the part page, so a power budget cannot be closed from this table alone.
Source: Rockwell publication 2711P-UM006, Table 17 (communication modules 700 to 1500) and the module installation procedure. Attribute values above are reproduced from the manufacturer's product data; nothing in this block is estimated.
Related models, options and spare parts for this range are listed in the Allen-Bradley PanelView 2711 HMI terminals category.