Product Details:
Payment & Shipping Terms:
|
1746-NLB is the led module assembly in the Allen-Bradley SLC 500 range: ASSY, LED MODULE FOR PROG CONTROLLER.
It is a hardware part of the modular system rather than an I/O card, so this page records what the part does, how it has to match the rack and what Rockwell still publishes about it.
| 1746-N2 | SLC Modular Card Slot Filler | IN STOCK |
| 1746-N3 | SLC Mating Connector | IN STOCK |
| 1746-NOC | SLC 500 Spare Assembly | IN STOCK |
| 1746-NGC | SLC Integrated Circuit Assembly | IN STOCK |
| 1746-NLB | SLC LED Module Assembly | IN STOCK |
Application |
ASSY, LED MODULE FOR PROG CONTROLLER |
Cat Num |
1746-NLB |
Brand Name |
Rockwell |
Product Type |
LED module assembly |
Official title |
ASSY, LED MODULE FOR PROG CONTROLLER |
Lifecycle |
Discontinued |
Discontinued date |
Not published (Rockwell product page retired) |
Replacement category |
Not published |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN016 (module specifications) and 1746-IN016 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-NLB is the LED module assembly for the SLC programmable controller, catalogued by Rockwell as an assembly rather than as an I/O card. It is the indicator hardware behind the status display on the unit it belongs to.
Application: ASSY, LED MODULE FOR PROG CONTROLLER.
Cat Num: 1746-NLB.
Brand Name: Rockwell.
Product Type: LED module assembly.
Official title: ASSY, LED MODULE FOR PROG CONTROLLER.
Lifecycle: Discontinued.
Discontinued date: Not published (Rockwell product page retired).
Replacement category: Not published.
An LED assembly is not a diagnostic: it reports what the board behind it has already decided. If a replacement assembly lights the same pattern as the old one, the fault is upstream of the LEDs and the board has to be checked before another assembly is ordered.
Rockwell's product page for this number has been retired, so the page states the catalog title, the family and the handling rules rather than quoting a lamp current or a viewing angle that no longer has a published source.
Spares in this family are matched on the catalog number and on the physical form of the part, not on a photograph alone, because several numbers in the N series look alike and are not interchangeable.
Rockwell lists 1746-NLB as discontinued, date Not published (Rockwell product page retired), replacement category Not published.
No replacement catalog number is planned for this number, so stock in the secondary market is the supply route and a machine that depends on it should carry its own spare.
Rockwell's migration guidance for Bulletin 1746 moves I/O to Compact 5000 modules on a Logix controller; a mechanical part such as this does not migrate with the electronics.
What is 1746-NLB?
ASSY, LED MODULE FOR PROG CONTROLLER, led module assembly in the SLC 500 range.
Which chassis does 1746-NLB fit?
The modular SLC 500 chassis, 1746-A4, A7, A10 and A13, and the fixed-style expansion rack where the number is listed for it.
Does 1746-NLB draw backplane current?
No. It is a mechanical or assembly part and takes no slot address.
Is 1746-NLB still available?
Rockwell lists it as discontinued, date Not published (Rockwell product page retired), replacement category Not published.
Is a Rockwell publication available for 1746-NLB?
Rockwell documents it under 1746-IN016.
1746-NLB belongs to the SLC 500 modular hardware range. A SLC 500 modular system is a 1746 chassis with a power supply, a processor or an I/O adapter in the left-most slot, and I/O modules in the remaining slots.
The chassis sizes published in the SLC 500 selection guide are 4, 7, 10 and 13 slots, and a maximum of three chassis can be linked in one system. Where a catalog number falls outside those published sizes, its slot count has to be confirmed against current literature before it is quoted into a bill of materials.
The processor or the I/O adapter occupies the left-most slot of a 1746 chassis, and the power supply is a separate unit mounted on the left end of the chassis rather than a module inside it. That is why a spare chassis is not a spare system: chassis, power supply and processor are three catalog numbers, and the interconnect cable is a fourth.
SLC 500 processors span 1 K to 64 K of memory and can address up to 4096 inputs and 4096 outputs, and every modular processor except the SLC 5/01 can control remotely located I/O through a scanner. That distinction is what makes a 5/01 unsuitable as the head of a distributed system regardless of its I/O count.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Module density tops out at 32 channels per module in the 1746 range, and the chassis sizes are 4, 7, 10 and 13 slots. Open slots are closed with 1746-N2 card slot fillers, which matters because an unfilled slot changes the airflow and the mechanical retention of the modules around it rather than only the appearance of the rack.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.