1746-INT4 is the Isolated thermocouple/mV input module for the Allen-Bradley SLC 500: 1746 SLC System, 4 channel isolated thermocouple/mV input module.
It is a specialty module, so the values below are the ones Rockwell publishes for this catalog number, and anything the publication does not print is marked not published.
| 1746-HSCE | SLC 1 Channel High Speed Counter Module | IN STOCK |
| 1746-HSCE2 | SLC 4 Channel High Speed Counter Module | IN STOCK |
| 1746-HSTP1 | SLC 1 Axis Stepper Module | IN STOCK |
| 1746-BTM | SLC Barrel Temperature Control Module | IN STOCK |
| 1746-BAS-T | SLC High Speed BASIC Language Module | IN STOCK |
| 1746-INT4 | SLC 4 Channel Isolated Thermocouple Module | IN STOCK |
| 1746-HCA | IMC 110 to Terminal Panel Cable | IN STOCK |
| 1746-HT | IMC 110 Termination Panel | IN STOCK |
Application |
1746 SLC System, 4 channel isolated thermocouple/mV input module |
Cat Num |
1746-INT4 |
Brand Name |
Rockwell |
Product Type |
Isolated thermocouple/mV input module |
Number of channels |
4, backplane and channel-to-channel isolated |
Backplane current |
110 mA at 5V dc, 85 mA at 24V dc |
Backplane power |
0.6 W max |
A/D conversion |
Sigma-delta modulation |
Channel bandwidth |
8 Hz (-3 dB) |
Normal mode rejection |
greater than 50 dB at 50 Hz, greater than 60 dB at 60 Hz |
Common mode rejection |
greater than 120 dB at 50/60 Hz with 1 kOhm imbalance |
Isolation |
1000V transient or 150V ac continuous, channel to channel and channel to backplane |
Chassis position |
any I/O slot except slot 0 |
Lifecycle |
Discontinued |
Discontinued date |
Not published (Rockwell product page retired; see 1746-UM614) |
Replacement category |
Not published |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-UM614 (module specifications) and 1746-UM614 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-INT4 is the isolated thermocouple module: four channels, each isolated from the others and from the backplane, so four sensors at different earth potentials can sit on one card.
Application: 1746 SLC System, 4 channel isolated thermocouple/mV input module.
Cat Num: 1746-INT4.
Brand Name: Rockwell.
Product Type: Isolated thermocouple/mV input module.
Number of channels: 4, backplane and channel-to-channel isolated.
Backplane current: 110 mA at 5V dc, 85 mA at 24V dc.
Backplane power: 0.6 W max.
A/D conversion: Sigma-delta modulation.
Channel bandwidth: 8 Hz (-3 dB).
Normal mode rejection: greater than 50 dB at 50 Hz, greater than 60 dB at 60 Hz.
Common mode rejection: greater than 120 dB at 50/60 Hz with 1 kOhm imbalance.
Isolation: 1000V transient or 150V ac continuous, channel to channel and channel to backplane.
Chassis position: any I/O slot except slot 0.
Lifecycle: Discontinued.
Discontinued date: Not published (Rockwell product page retired; see 1746-UM614).
Replacement category: Not published.
Each channel takes a thermocouple or a dc millivolt source and has its own configuration and status word. Eight input words are reserved in the image table, four for data and four for status.
Channel-to-channel isolation is the difference between this card and a common-reference thermocouple card: a grounded thermocouple on a earthed barrel no longer pulls the other three channels with it.
The 8 Hz bandwidth and the 50/60 Hz rejection figures put the card in slow process temperature service, not on a fast thermal cycle; a heat-treat furnace with four zones is the natural fit.
A slot-zero rule applies across the family: the module goes in any I/O slot except the processor slot, and its address follows the slot number.
Rockwell lists 1746-INT4 as discontinued, date Not published (Rockwell product page retired; see 1746-UM614), replacement category Not published.
No replacement catalog number is printed on the Rockwell page for this number, so the route is an engineering substitution with the function re-implemented on a Logix platform.
Rockwell documents the module in 1746-UM614; that publication, not a distributor page, is the source for the values above.
What is 1746-INT4?
1746 SLC System, 4 channel isolated thermocouple/mV input module. Isolated thermocouple/mV input module.
How many channels does 1746-INT4 have?
4, backplane and channel-to-channel isolated
Which slot does 1746-INT4 go in?
Any I/O slot except slot 0, which is reserved for the processor.
What isolation does 1746-INT4 provide?
1000V transient or 150V ac continuous, channel to channel and channel to backplane
Is 1746-INT4 still available?
Rockwell lists it as discontinued, date Not published (Rockwell product page retired; see 1746-UM614), replacement category Not published.
1746-INT4 is a 4-channel thermocouple/mV input module with C and D types for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-INT4 |
| Module type | 4-channel thermocouple/mV input module with C and D types |
| Inputs | 4 plus a CJC sensor |
| Thermocouple types | J, K, T, E, R, S, B, N, C, D |
| Backplane current @ 5V | 110 mA |
| Backplane current @ 24V | 85 mA |
| Cold junction compensation | Integrated |
This is the variant that adds type C and type D thermocouples to the standard set, which is the difference between a general-purpose temperature card and one that can read the high-temperature couple in a kiln or a heat-treat furnace. Its 85 mA on the 24V rail is the highest of the thermocouple family, so it is also the one that most often decides whether a chassis needs a larger supply.
Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.
Heat is part of the same calculation as current: the selection guide carries a heat dissipation figure per module, and the chassis total is the sum of those figures. A rack that is electrically legal and thermally packed still derates in a closed cabinet, which is why the procedure in the guide sums watts slot by slot instead of estimating from the 5V current.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
The processor or the I/O adapter occupies the left-most slot of a 1746 chassis, and the power supply is a separate unit mounted on the left end of the chassis rather than a module inside it. That is why a spare chassis is not a spare system: chassis, power supply and processor are three catalog numbers, and the interconnect cable is a fourth.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.