|
Product Details:
Payment & Shipping Terms:
|
1746-P6 is the rack mounting power supply for the SLC 500 modular system: 1746 SLC System, Power Supply - Rack Mount, 30...60V dc.
It converts the panel supply into the two backplane rails the cards draw from, 5V dc and 24V dc, and on most versions into a small isolated 24V dc source for sensors.
| 1746-P1 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P2 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P3 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P4 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P5 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P6 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P7 | SLC Rack Mounting Power Supply | IN STOCK |
Application |
1746 SLC System, Power Supply - Rack Mount, 30...60V dc |
Cat Num |
1746-P6 |
Brand Name |
Rockwell |
Product Type |
SLC 500 rack mounting power supply |
Line voltage |
30...60V dc |
Typical line power requirement |
100 VA typical |
Inrush current, max |
20 A max, required for turn-on |
Internal capacity, 5V dc |
2.0 A at 5V dc and 0.46 A at 24V dc on 12V dc input; 3.6 A at 5V dc and 0.87 A at 24V dc on 24V dc input |
Internal capacity, 24V dc |
see 5V dc figure, the two rails are linked to the input voltage |
24V dc user-power output |
200 mA at 18...30V dc |
Isolation |
600V ac RMS for 1 s |
Fuse protection |
soldered in place, not field replaceable |
Dimensions, W x D x H |
85 x 140 x 140 mm |
Temperature, ambient operating |
0...60 °C (32...140 °F) |
Lifecycle |
Discontinued |
Discontinued date |
January 31, 2017 |
Replacement category |
Functional Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN004 (module specifications) and 1746-IN004 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Rockwell description: 1746 SLC System, Power Supply - Rack Mount, 30...60V dc.
The supply bolts to the left end of the chassis and feeds the backplane; it is not a slot card and it does not consume a slot address.
Application: 1746 SLC System, Power Supply - Rack Mount, 30...60V dc.
Cat Num: 1746-P6.
Brand Name: Rockwell.
Product Type: SLC 500 rack mounting power supply.
Line voltage: 30...60V dc.
Typical line power requirement: 100 VA typical.
Inrush current, max: 20 A max, required for turn-on.
Internal capacity, 5V dc: 2.0 A at 5V dc and 0.46 A at 24V dc on 12V dc input; 3.6 A at 5V dc and 0.87 A at 24V dc on 24V dc input.
Internal capacity, 24V dc: see 5V dc figure, the two rails are linked to the input voltage.
24V dc user-power output: 200 mA at 18...30V dc.
Isolation: 600V ac RMS for 1 s.
Fuse protection: soldered in place, not field replaceable.
Dimensions, W x D x H: 85 x 140 x 140 mm.
Temperature, ambient operating: 0...60 °C (32...140 °F).
Lifecycle: Discontinued.
Discontinued date: January 31, 2017.
Replacement category: Functional Replacement.
The 5V dc and 24V dc figures above are the supply's internal capacity. Every card in the rack draws from them, and the sum has to stay inside both rails at the same time, not just inside the larger one.
The 24V dc user output is a separate, isolated source for field devices. On the 1746-P4 the total of backplane and user power cannot exceed 70 W, so a fully loaded 10 A rack leaves little for sensors.
Capacity is derated 5 percent above 55 °C on the P1, P2, P4, P5 and P6, which matters in a sealed panel where the internal temperature runs above the ambient figure.
The P1, P2 and P4 have an input voltage jumper that has to be set before power is applied; the P3, P5, P6 and P7 have no jumper. Setting the jumper with the supply energised exposes line voltage on the pins.
The ground screw goes to the nearest ground bus with 1.68 mm² (#14 AWG) 75 °C copper, and the incoming terminals take the same wire, tightened to 0.8 N·m (7 lb-in).
Hold-up time is what the controller keeps scanning after the line drops. The P5 holds the CPU for 20 ms at full load, the P6 for 5 ms, and the P7 for 40 ms at 24V dc input and full load; the P7 also latches off if the input sits between 4V and 9V until it is raised to 11V dc.
Rockwell lists 1746-P6 as discontinued, date January 31, 2017, replacement category Functional Replacement.
Rockwell prints no replacement catalog number on the product page, so a failed supply is replaced from stock or the rack is migrated.
A power supply is the part that decides how much I/O a rack can hold, so a spare is normally kept at the same current rating rather than at the same physical size.
What is 1746-P6?
1746 SLC System, Power Supply - Rack Mount, 30...60V dc. Rack mounting power supply for the SLC 500 modular system.
What input voltage does 1746-P6 accept?
30...60V dc.
How much current does 1746-P6 give the backplane?
2.0 A at 5V dc and 0.46 A at 24V dc on 12V dc input; 3.6 A at 5V dc and 0.87 A at 24V dc on 24V dc input at 5V dc and see 5V dc figure, the two rails are linked to the input voltage at 24V dc.
Can 1746-P6 power field sensors?
200 mA at 18...30V dc.
Is 1746-P6 still available?
Rockwell lists it as discontinued, date January 31, 2017, replacement category Functional Replacement.
Seven rack supplies fit the same chassis footprint and differ mainly in what they can give the 5 V rail, which is what the I/O modules actually run on. Two of them are 5 V equivalents of each other on AC and DC input, the P4 doubles the 5 V capacity, and the fuse line separates a supply that can be serviced in place from one that cannot.
| Supply | Input | 5 V dc capacity | 24 V dc capacity | User 24 V | Fuse | Inrush | |
| 1746-P1 | 85...132 / 170...265 V ac | 2 A | 0.46 A | 200 mA | 1746-F1, replaceable | 65 x 140 x 140 mm | 20 A max |
| 1746-P2 | 85...132 / 170...265 V ac | 5 A | 0.96 A | 200 mA | 1746-F2, replaceable | 85 x 140 x 140 mm | 45 A max |
| 1746-P3 | 19.2...28.8 V dc | 3.6 A | 0.87 A | none | 1746-F3, replaceable | P1/P2 rack depth | not published |
| 1746-P4 | 85...132 / 170...250 V ac | 10.0 A | 2.88 A | 1 A | soldered, not replaceable | 110 x 145 x 140 mm | 20 A max |
| 1746-P5 | 90...146 V dc | 5 A | 0.96 A | 200 mA | soldered, not replaceable | 85 x 140 x 140 mm | 20 A max |
| 1746-P6 | 30...60 V dc | 2.0 A on 12 V dc input, 3.6 A on 24 V dc input | 0.46 / 0.87 A as the input rises | 200 mA | soldered, not replaceable | 85 x 140 x 140 mm | 20 A max, required for turn-on |
| 1746-P7 | 10...30 V dc | from the P7 capacity chart | from the same chart | none | soldered, not replaceable | P1/P2 rack depth | not published |
Where this supply sits: Read the supply against the rail it feeds: 1746-P6 gives 2.0 A on 12 V dc input, 3.6 A on 24 V dc input at 5 V and 0.46 / 0.87 A as the input rises at 24 V from 30...60 V dc, with a soldered, not replaceable fuse and an inrush of 20 A max, required for turn-on.
A supply table alone does not size a rack: the 5 V capacity has to be compared with the sum of the module draws, and this block prints the capacity without pretending the modules are free. The 24 V capacity is the in-rack rail for modules that need it, not a field supply for sensors and coils, and the user 24 V figure is a separate output with its own limit.
Source: Rockwell 1746-IN027 digital I/O specification rows, 1746-IN008 and 1746-UM007 analog rows, 1746-IN016/IN004 chassis and supply rows. Backplane currents are quoted as printed; only the "how many fit" divisions are arithmetic, and they are integer divisions of the printed capacity.
The Allen-Bradley SLC 500 1746 I/O modules category lists the related catalog numbers, options and accessories for this range.