Product Details:
Payment & Shipping Terms:
|
1746-OG16 is the TTL Output Module in the Allen-Bradley SLC 500 range: SLC 500 TTL signal output module, 16 outputs.
It sits in an SLC 500 chassis slot and exchanges data with the processor through the backplane image table; the points, voltage category and backplane current below are what decide whether it fits the slot and the power budget.
| 1746-OG16 | TTL Output Module | IN STOCK |
Application |
SLC 500 TTL signal output module, 16 outputs |
Cat Num |
1746-OG16 |
Brand Name |
Rockwell |
Product Type |
TTL Output Module |
Points |
16 outputs |
Points per common |
16 |
Voltage category |
5V DC TTL signal output |
Operating voltage |
4.5...5.5V DC |
Backplane current, 5V DC |
Not published |
Backplane current, 24V DC |
0.0 A |
Signal delay, max |
Not published |
Isolation |
1500V, electro-optical to control logic |
Lifecycle |
Discontinued |
Discontinued date |
December 31, 2014 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN027 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 500 TTL signal output module, 16 outputs.
TTL Output Module, with 16 outputs and 16 per common terminal.
Application: SLC 500 TTL signal output module, 16 outputs.
Cat Num: 1746-OG16.
Brand Name: Rockwell.
Product Type: TTL Output Module.
Points: 16 outputs.
Points per common: 16.
Voltage category: 5V DC TTL signal output.
Operating voltage: 4.5...5.5V DC.
Backplane current, 5V DC: Not published.
Backplane current, 24V DC: 0.0 A.
Signal delay, max: Not published.
Isolation: 1500V, electro-optical to control logic.
Lifecycle: Discontinued.
Discontinued date: December 31, 2014.
Replacement category: Engineering Replacement.
TTL outputs are 5V DC level signals for a driver board or another logic card, not for a contactor.
Because the levels are low, wiring length and shielding matter more than on a 24V DC card.
Rockwell lists 1746-OG16 as Discontinued, with the discontinued date December 31, 2014 and the replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution rather than a direct part-for-part swap.
Rockwell's own migration guidance for Bulletin 1746 I/O points to the Compact 5000 I/O platform with a Logix controller; a machine that stays on SLC 500 is served from the secondary market.
The enclosure, the terminal armature and the address assignment are unchanged when a card is replaced by the same catalog number, which is why the original number keeps a value after the end of sale.
A modular SLC 500 chassis reserves slot 0 for the processor or the adapter, so this card goes in any other I/O slot; a fixed controller chassis has a published power limit instead of a slot rule.
The backplane current above is added to the draw of every other card in the chassis and compared with the chassis supply before a card is added, which is the check that prevents an intermittent chassis fault after a retrofit.
Electro-optical isolation between the field terminals and the control logic is 1500V, and the operating range of the whole family is 0...60 °C with 5...95% noncondensing humidity and NEMA ICS 2-230 noise immunity.
The card in red in the table at the top is the one on this page.
What is 1746-OG16?
SLC 500 TTL signal output module, 16 outputs. TTL Output Module.
How many points does 1746-OG16 have?
16 outputs, 16 per common.
What voltage does 1746-OG16 work at?
5V DC TTL signal output, operating range 4.5...5.5V DC.
Is 1746-OG16 still available?
Rockwell lists it as Discontinued with the discontinued date December 31, 2014, replacement category Engineering Replacement.
What has to be checked before fitting 1746-OG16?
The backplane current against the chassis supply, the sinking or sourcing convention of the field devices, and the terminal block, which is removable and often missing on a used card.
1746-OG16 is a 16-point 5V DC sourcing output module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-OG16 |
| Module type | 16-point 5V DC sourcing output module |
| Outputs | 16 |
| Voltage category | 5V DC |
| Operating voltage range | 4.5...5.5V DC |
| Backplane current @ 5V | 180 mA |
| Backplane current @ 24V | 0 mA |
A 5V DC output module drives logic-level loads directly, and the 180 mA backplane draw is nearly three times that of a 24V DC 16-point output, so a chassis built from these modules reaches the 5V limit sooner than the I/O count suggests. The 4.5 to 5.5V window is also narrow: a 5V rail sagging under a long LED or relay-coil load is out of range before the supply itself is out of specification.
Module density tops out at 32 channels per module in the 1746 range, and the chassis sizes are 4, 7, 10 and 13 slots. Open slots are closed with 1746-N2 card slot fillers, which matters because an unfilled slot changes the airflow and the mechanical retention of the modules around it rather than only the appearance of the rack.
Power supply selection is a two-rail comparison, not a wattage comparison: 1746-P1 gives 2.0 A at 5V and 0.46 A at 24V, 1746-P2 gives 5.0 A and 0.96 A, 1746-P3 gives 3.6 A and 0.87 A from a 19.2 to 28.8V DC input, and 1746-P4 gives 10.0 A and 2.88 A with a 70 W total limit across all outputs. Choosing by input voltage alone and ignoring the 24V allowance is how a chassis ends up short on analog capacity.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
The Allen-Bradley SLC 500 1746 I/O modules category groups the other catalog numbers, options and spare parts in the same range.