1746-OAP12 is the High Current Triac Output Module in the Allen-Bradley SLC 500 range: 1746 SLC System, 12 ch-Triac Output Module, high current.
It sits in an SLC 500 chassis slot and exchanges data with the processor through the backplane image table; the points, voltage category and backplane current below are what decide whether it fits the slot and the power budget.
| 1746-OA8 | 8 Point Triac Output Module | IN STOCK |
| 1746-OA16 | 16 Point Triac Output Module | IN STOCK |
| 1746-OAP12 | High Current Triac Output Module | IN STOCK |
Application |
1746 SLC System, 12 ch-Triac Output Module, high current |
Cat Num |
1746-OAP12 |
Brand Name |
Rockwell |
Product Type |
High Current Triac Output Module |
Points |
12 outputs |
Points per common |
6 |
Voltage category |
120/240V AC signal output |
Operating voltage |
85...265V AC @ 47...63 Hz |
Backplane current, 5V DC |
0.370 A |
Backplane current, 24V DC |
0.0 A |
Signal delay, max |
On = 1 ms, Off = 11.0 ms |
Isolation |
1500V, electro-optical to control logic |
Lifecycle |
Discontinued |
Discontinued date |
December 31, 2015 |
Replacement category |
Engineering Replacement |
1746-OAP12 (SLC 500 12-channel 120/240 V AC protected triac output module): 12 protected triac outputs, 120/240 V AC category, fused commons with a blown-fuse LED on the front of the module, 370 mA from the 5 V backplane. Heat dissipation 1.850 W minimum, 10.85 W maximum (1.000 W per point).
The blown-fuse LED is the practical difference against 1746-OA16: a dead output is diagnosed from the door of the enclosure, and a replacement fuse holder is available as 1746-R17. Twelve points instead of sixteen means the card is chosen when the AC load count is already known. Sources: Rockwell publications 1747-SG001 (SLC 500 digital I/O specifications and module descriptions) and 1747-UM011 (power supply worksheet and heat dissipation).
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN027 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, 12 ch-Triac Output Module, high current.
High Current Triac Output Module, with 12 outputs and 6 per common terminal.
Application: 1746 SLC System, 12 ch-Triac Output Module, high current.
Cat Num: 1746-OAP12.
Brand Name: Rockwell.
Product Type: High Current Triac Output Module.
Points: 12 outputs.
Points per common: 6.
Voltage category: 120/240V AC signal output.
Operating voltage: 85...265V AC @ 47...63 Hz.
Backplane current, 5V DC: 0.370 A.
Backplane current, 24V DC: 0.0 A.
Signal delay, max: On = 1 ms, Off = 11.0 ms.
Isolation: 1500V, electro-optical to control logic.
Lifecycle: Discontinued.
Discontinued date: December 31, 2015.
Replacement category: Engineering Replacement.
A triac output switches at the AC zero cross, so the published OFF delay is a line-frequency figure and not a logic delay.
A minimum load current is needed to hold the triac on; below it the output can stay off or chatter, and a bleed resistor across the load is the usual fix.
Continuous current per point is 1.0 A at 30 °C and 0.50 A at 60 °C on the 8-point card, so a panel that runs warm has to be derated before the load is chosen.
Rockwell lists 1746-OAP12 as Discontinued, with the discontinued date December 31, 2015 and the replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution rather than a direct part-for-part swap.
Rockwell's own migration guidance for Bulletin 1746 I/O points to the Compact 5000 I/O platform with a Logix controller; a machine that stays on SLC 500 is served from the secondary market.
The enclosure, the terminal armature and the address assignment are unchanged when a card is replaced by the same catalog number, which is why the original number keeps a value after the end of sale.
A modular SLC 500 chassis reserves slot 0 for the processor or the adapter, so this card goes in any other I/O slot; a fixed controller chassis has a published power limit instead of a slot rule.
The backplane current above is added to the draw of every other card in the chassis and compared with the chassis supply before a card is added, which is the check that prevents an intermittent chassis fault after a retrofit.
Electro-optical isolation between the field terminals and the control logic is 1500V, and the operating range of the whole family is 0...60 °C with 5...95% noncondensing humidity and NEMA ICS 2-230 noise immunity.
The card in red in the table at the top is the one on this page.
What is 1746-OAP12?
1746 SLC System, 12 ch-Triac Output Module, high current. High Current Triac Output Module.
How many points does 1746-OAP12 have?
12 outputs, 6 per common.
What voltage does 1746-OAP12 work at?
120/240V AC signal output, operating range 85...265V AC @ 47...63 Hz.
Is 1746-OAP12 still available?
Rockwell lists it as Discontinued with the discontinued date December 31, 2015, replacement category Engineering Replacement.
What has to be checked before fitting 1746-OAP12?
The backplane current against the chassis supply, the sinking or sourcing convention of the field devices, and the terminal block, which is removable and often missing on a used card.
Every 1746 digital module is one slot wide, so slot count is never the constraint in an SLC rack - the 5 V and 24 V backplane currents are. This table is the printed current for each module in the same functional group, taken from the 1746-IN027 specification rows, so the budget can be added up before the rack is ordered instead of after it browns out.
| Catalog | Points | Signal | 5 V backplane | 24 V backplane | Signal delay |
| 1746-OA8 | 8 outputs | 120/240V AC signal output | 0.185 A | 0.0 A | On = 1 ms, Off = 11.0 ms |
| 1746-OA16 | 16 outputs | 120/240V AC signal output | 0.370 A | 0.0 A | On = 1 ms, Off = 11.0 ms |
| 1746-OAP12 | 12 outputs | 120/240V AC signal output | 0.370 A | 0.0 A | On = 1 ms, Off = 11.0 ms |
Where this module sits: Read the backplane column before the point count: 1746-OAP12 takes 0.370 A at 5 V and 0.0 A at 24 V. Added up, on the 5 A 1746-P2 even the tighter rail (the 5 V one) carries 13 of them, more than the thirteen slots of the longest 1746 chassis, so slot count and not current decides.
Two things this block does not answer. It gives the module current, not the surge a rack sees at power-up, which is printed separately as inrush for the supply and not per module. And it says nothing about the 24 V field supply drawn by the loads themselves - the 24 V backplane figure is what the module takes from the rack, not what the sensors and coils take from the field supply.
Source: Rockwell 1746-IN027 digital I/O specification rows, 1746-IN008 and 1746-UM007 analog rows, 1746-IN016/IN004 chassis and supply rows. Backplane currents are quoted as printed; only the "how many fit" divisions are arithmetic, and they are integer divisions of the printed capacity.
This part sits in the Allen-Bradley SLC 500 1746 I/O modules category, with the other models and spare parts listed alongside it.