Product Details:
Payment & Shipping Terms:
|
1746-OA8 is the 8 Point Triac Output Module in the Allen-Bradley SLC 500 range: 1746 SLC System, 8 ch-Triac Output Module For Programmable Controller.
It sits in an SLC 500 chassis slot and exchanges data with the processor through the backplane image table; the points, voltage category and backplane current below are what decide whether it fits the slot and the power budget.
| 1746-OA8 | 8 Point Triac Output Module | IN STOCK |
| 1746-OA16 | 16 Point Triac Output Module | IN STOCK |
| 1746-OAP12 | High Current Triac Output Module | IN STOCK |
Application |
1746 SLC System, 8 ch-Triac Output Module For Programmable Controller |
Cat Num |
1746-OA8 |
Brand Name |
Rockwell |
Product Type |
8 Point Triac Output Module |
Points |
8 outputs |
Points per common |
4 |
Voltage category |
120/240V AC signal output |
Operating voltage |
85...265V AC @ 47...63 Hz |
Backplane current, 5V DC |
0.185 A |
Backplane current, 24V DC |
0.0 A |
Signal delay, max |
On = 1 ms, Off = 11.0 ms |
Isolation |
1500V, electro-optical to control logic |
Lifecycle |
Discontinued |
Discontinued date |
December 31, 2022 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN027 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, 8 ch-Triac Output Module For Programmable Controller.
8 Point Triac Output Module, with 8 outputs and 4 per common terminal.
Application: 1746 SLC System, 8 ch-Triac Output Module For Programmable Controller.
Cat Num: 1746-OA8.
Brand Name: Rockwell.
Product Type: 8 Point Triac Output Module.
Points: 8 outputs.
Points per common: 4.
Voltage category: 120/240V AC signal output.
Operating voltage: 85...265V AC @ 47...63 Hz.
Backplane current, 5V DC: 0.185 A.
Backplane current, 24V DC: 0.0 A.
Signal delay, max: On = 1 ms, Off = 11.0 ms.
Isolation: 1500V, electro-optical to control logic.
Lifecycle: Discontinued.
Discontinued date: December 31, 2022.
Replacement category: Engineering Replacement.
A triac output switches at the AC zero cross, so the published OFF delay is a line-frequency figure and not a logic delay.
A minimum load current is needed to hold the triac on; below it the output can stay off or chatter, and a bleed resistor across the load is the usual fix.
Continuous current per point is 1.0 A at 30 °C and 0.50 A at 60 °C on the 8-point card, so a panel that runs warm has to be derated before the load is chosen.
Rockwell lists 1746-OA8 as Discontinued, with the discontinued date December 31, 2022 and the replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution rather than a direct part-for-part swap.
Rockwell's own migration guidance for Bulletin 1746 I/O points to the Compact 5000 I/O platform with a Logix controller; a machine that stays on SLC 500 is served from the secondary market.
The enclosure, the terminal armature and the address assignment are unchanged when a card is replaced by the same catalog number, which is why the original number keeps a value after the end of sale.
A modular SLC 500 chassis reserves slot 0 for the processor or the adapter, so this card goes in any other I/O slot; a fixed controller chassis has a published power limit instead of a slot rule.
The backplane current above is added to the draw of every other card in the chassis and compared with the chassis supply before a card is added, which is the check that prevents an intermittent chassis fault after a retrofit.
Electro-optical isolation between the field terminals and the control logic is 1500V, and the operating range of the whole family is 0...60 °C with 5...95% noncondensing humidity and NEMA ICS 2-230 noise immunity.
The card in red in the table at the top is the one on this page.
What is 1746-OA8?
1746 SLC System, 8 ch-Triac Output Module For Programmable Controller. 8 Point Triac Output Module.
How many points does 1746-OA8 have?
8 outputs, 4 per common.
What voltage does 1746-OA8 work at?
120/240V AC signal output, operating range 85...265V AC @ 47...63 Hz.
Is 1746-OA8 still available?
Rockwell lists it as Discontinued with the discontinued date December 31, 2022, replacement category Engineering Replacement.
What has to be checked before fitting 1746-OA8?
The backplane current against the chassis supply, the sinking or sourcing convention of the field devices, and the terminal block, which is removable and often missing on a used card.
1746-OA8 is a 8-point AC output module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-OA8 |
| Module type | 8-point AC output module |
| Outputs | 8 |
| Output type | AC, triac output |
| Chassis | 1746 modular chassis, any slot right of the processor |
AC output modules switch line voltage at the load, so the module is a switching element and not a power supply: the load current, the inrush of the load, and the leakage through an off triac are the three numbers that decide whether the circuit behaves. Off-state leakage is what makes a small relay or an indicator glow when the output is commanded off, and it is a property of the output circuit rather than a fault in the program.
Module density tops out at 32 channels per module in the 1746 range, and the chassis sizes are 4, 7, 10 and 13 slots. Open slots are closed with 1746-N2 card slot fillers, which matters because an unfilled slot changes the airflow and the mechanical retention of the modules around it rather than only the appearance of the rack.
SLC 500 processors span 1 K to 64 K of memory and can address up to 4096 inputs and 4096 outputs, and every modular processor except the SLC 5/01 can control remotely located I/O through a scanner. That distinction is what makes a 5/01 unsuitable as the head of a distributed system regardless of its I/O count.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Browse the Allen-Bradley SLC 500 1746 I/O modules category for the other models, options and spare parts that share this range.