1746-NT4 is the 4 Point Thermocouple Input Module in the Allen-Bradley SLC 500 range: SLC 4 Point Input Module, thermocouple/mV analog input.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NT4 | 4 Point Thermocouple Input Module | IN STOCK |
| 1746-NT8 | 8 Point Thermocouple Input Module | IN STOCK |
Application |
SLC 4 Point Input Module, thermocouple/mV analog input |
Cat Num |
1746-NT4 |
Brand Name |
Rockwell |
Product Type |
4 Point Thermocouple Input Module |
Channels |
4 thermocouple or millivolt inputs |
Input range |
Types J, K, T, E, R, S, B, N; ±50 mV and ±100 mV direct |
Resolution |
16-bit |
Backplane current, 5V DC |
60 mA |
Backplane current, 24V DC |
40 mA |
Update time / filtering |
Sigma-Delta, filter 10/50/60/250 Hz, step response 26 ms...1.2 s |
Isolation |
500V dc channel to channel and channel to backplane |
Lifecycle |
Discontinued |
Discontinued date |
December 30, 2015 |
Replacement category |
Functional Replacement |
Replacement product |
1746-NT8 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-UM007 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 4 Point Input Module, thermocouple/mV analog input.
4 Point Thermocouple Input Module with 4 thermocouple or millivolt inputs.
Application: SLC 4 Point Input Module, thermocouple/mV analog input.
Cat Num: 1746-NT4.
Brand Name: Rockwell.
Product Type: 4 Point Thermocouple Input Module.
Channels: 4 thermocouple or millivolt inputs.
Input range: Types J, K, T, E, R, S, B, N; ±50 mV and ±100 mV direct.
Resolution: 16-bit.
Backplane current, 5V DC: 60 mA.
Backplane current, 24V DC: 40 mA.
Update time / filtering: Sigma-Delta, filter 10/50/60/250 Hz, step response 26 ms...1.2 s.
Isolation: 500V dc channel to channel and channel to backplane.
Lifecycle: Discontinued.
Discontinued date: December 30, 2015.
Replacement category: Functional Replacement.
Replacement product: 1746-NT8.
Cold junction compensation is on the terminal block, one sensor for the group of channels, so a terminal block swapped between modules carries its own calibration and has to stay with the card.
The input is differential and the potential between any two channels is limited, which rules out tying several thermocouples to a common earthed shield without checking the channel-to-channel voltage.
Thermocouple type, filter frequency and data format are configured in software; the type has to match the actual sensor, because a J curve read as a K curve produces a plausible but wrong temperature.
Rockwell lists 1746-NT4 as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.
Rockwell names 1746-NT8 as the replacement product on the catalog page.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc channel to channel and channel to backplane between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NT4?
SLC 4 Point Input Module, thermocouple/mV analog input. 4 Point Thermocouple Input Module.
How many channels does 1746-NT4 have?
4 thermocouple or millivolt inputs.
What ranges does 1746-NT4 accept?
Inputs: Types J, K, T, E, R, S, B, N; ±50 mV and ±100 mV direct.
How much backplane current does 1746-NT4 draw?
60 mA at 5V dc and 40 mA at 24V dc.
Is 1746-NT4 still available?
Rockwell lists it as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.
1746-NT4 is a 4-channel thermocouple/mV input module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-NT4 |
| Module type | 4-channel thermocouple/mV input module |
| Inputs | 4 plus a CJC sensor |
| Thermocouple types | J, K, T, E, R, S, B, N |
| Millivolt ranges | +/-50 mV and +/-100 mV |
| Backplane current @ 5V | 60 mA |
| Backplane current @ 24V | 40 mA |
| Cold junction compensation | Integrated |
| Filter | Selectable input filter frequencies |
The module carries its own cold junction compensation, so the terminal block temperature is measured rather than assumed, and the millivolt ranges of +/-50 mV and +/-100 mV let it read signals that a standard analog module cannot resolve at all. In a remote chassis these readings require block transfers, which is a programming consequence of the topology rather than of the sensor.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
SLC 500 processors span 1 K to 64 K of memory and can address up to 4096 inputs and 4096 outputs, and every modular processor except the SLC 5/01 can control remotely located I/O through a scanner. That distinction is what makes a 5/01 unsuitable as the head of a distributed system regardless of its I/O count.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
The Allen-Bradley SLC 500 1746 I/O modules category groups the other catalog numbers, options and spare parts in the same range.