Product Details:
Payment & Shipping Terms:
|
1746-NR8 is the 8 Point Resistance Input Module in the Allen-Bradley SLC 500 range: 1746 SLC System, 8 channel Rtd Input Module.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NR4 | 4 Point Resistance Input Module | IN STOCK |
| 1746-NR8 | 8 Point Resistance Input Module | IN STOCK |
Application |
1746 SLC System, 8 channel Rtd Input Module |
Cat Num |
1746-NR8 |
Brand Name |
Rockwell |
Product Type |
8 Point Resistance Input Module |
Channels |
8 RTD or resistance inputs |
Input range |
100/200/500/1000 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance |
Resolution |
16-bit |
Backplane current, 5V DC |
100 mA |
Backplane current, 24V DC |
55 mA |
Update time / filtering |
Sigma-Delta, filter 7.80...1677 Hz, step response 1.47...120 ms |
Isolation |
500V ac for 1 min |
Lifecycle |
Discontinued |
Discontinued date |
September 30, 2024 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN007 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, 8 channel Rtd Input Module.
8 Point Resistance Input Module with 8 RTD or resistance inputs.
Application: 1746 SLC System, 8 channel Rtd Input Module.
Cat Num: 1746-NR8.
Brand Name: Rockwell.
Product Type: 8 Point Resistance Input Module.
Channels: 8 RTD or resistance inputs.
Input range: 100/200/500/1000 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
Resolution: 16-bit.
Backplane current, 5V DC: 100 mA.
Backplane current, 24V DC: 55 mA.
Update time / filtering: Sigma-Delta, filter 7.80...1677 Hz, step response 1.47...120 ms.
Isolation: 500V ac for 1 min.
Lifecycle: Discontinued.
Discontinued date: September 30, 2024.
Replacement category: Engineering Replacement.
The card measures resistance, not temperature: the RTD type, the excitation current and the temperature or resistance scaling are all set per channel, and a 2-wire element loses the lead resistance that a 3-wire or 4-wire connection cancels.
Broken sensor detection is per channel and reports open or short circuit, which is the reason an NR4 or NR8 is preferred over a temperature transmitter where the reading feeds a control loop.
The NR4 reads 4 channels at 50 mA from each backplane rail; the NR8 doubles the channel count at 100 mA at 5V dc, so a chassis at its limit gains channels but not power headroom.
Rockwell lists 1746-NR8 as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V ac for 1 min between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NR8?
1746 SLC System, 8 channel Rtd Input Module. 8 Point Resistance Input Module.
How many channels does 1746-NR8 have?
8 RTD or resistance inputs.
What ranges does 1746-NR8 accept?
Inputs: 100/200/500/1000 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
How much backplane current does 1746-NR8 draw?
100 mA at 5V dc and 55 mA at 24V dc.
Is 1746-NR8 still available?
Rockwell lists it as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.
1746-NR8 is a 8-channel RTD input module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-NR8 |
| Module type | 8-channel RTD input module |
| Inputs | 8 |
| Input type | RTD |
| Backplane current @ 5V | 100 mA |
| Backplane current @ 24V | 55 mA |
Doubling the channel count doubles the 5V draw and barely moves the 24V draw, which is typical of the analog family: the signal path runs on 5V and only the excitation and isolation side touches 24V. Eight RTDs in one slot also means eight sets of lead compensation, and the wiring discipline decides the accuracy of the module as much as its specification does.
The processor or the I/O adapter occupies the left-most slot of a 1746 chassis, and the power supply is a separate unit mounted on the left end of the chassis rather than a module inside it. That is why a spare chassis is not a spare system: chassis, power supply and processor are three catalog numbers, and the interconnect cable is a fourth.
Heat is part of the same calculation as current: the selection guide carries a heat dissipation figure per module, and the chassis total is the sum of those figures. A rack that is electrically legal and thermally packed still derates in a closed cabinet, which is why the procedure in the guide sums watts slot by slot instead of estimating from the 5V current.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Module density tops out at 32 channels per module in the 1746 range, and the chassis sizes are 4, 7, 10 and 13 slots. Open slots are closed with 1746-N2 card slot fillers, which matters because an unfilled slot changes the airflow and the mechanical retention of the modules around it rather than only the appearance of the rack.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Related models, options and spare parts for this range are listed in the Allen-Bradley SLC 500 1746 I/O modules category.