Product Details:
Payment & Shipping Terms:
|
1746-NOC is the spare assembly in the Allen-Bradley SLC 500 range: 1746 SLC System spare assembly, catalog number 1746-NOC.
It is a hardware part of the modular system rather than an I/O card, so this page records what the part does, how it has to match the rack and what Rockwell still publishes about it.
| 1746-N2 | SLC Modular Card Slot Filler | IN STOCK |
| 1746-N3 | SLC Mating Connector | IN STOCK |
| 1746-NOC | SLC 500 Spare Assembly | IN STOCK |
| 1746-NGC | SLC Integrated Circuit Assembly | IN STOCK |
| 1746-NLB | SLC LED Module Assembly | IN STOCK |
Application |
1746 SLC System spare assembly, catalog number 1746-NOC |
Cat Num |
1746-NOC |
Brand Name |
Rockwell |
Product Type |
Spare assembly |
Official data |
Rockwell product page for this catalog number has been retired (link dead) |
Lifecycle |
Discontinued |
Discontinued date |
Not published (Rockwell product page retired) |
Replacement category |
Not published |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN016 (module specifications) and 1746-IN016 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-NOC is sold on its catalog number. Rockwell's own product page for the number has been retired, so this page does not describe an internal function that the manufacturer no longer publishes; it records the number, the family it belongs to and the checks to make before a spare is ordered.
Application: 1746 SLC System spare assembly, catalog number 1746-NOC.
Cat Num: 1746-NOC.
Brand Name: Rockwell.
Product Type: Spare assembly.
Official data: Rockwell product page for this catalog number has been retired (link dead).
Lifecycle: Discontinued.
Discontinued date: Not published (Rockwell product page retired).
Replacement category: Not published.
Every part on this page belongs to the Bulletin 1746 SLC 500 modular system. Before ordering, match the number printed on the label of the failed part with the number on this listing, because the N-series numbers in this family cover slot fillers, connectors and small assemblies that are not interchangeable.
For a part in this position in the catalogue, the practical check is the physical form: connector shell, pin count and latch style have to match the mating part on the rack. Photographs on this page are of the actual stock item for that comparison.
Spares in this family are matched on the catalog number and on the physical form of the part, not on a photograph alone, because several numbers in the N series look alike and are not interchangeable.
Rockwell lists 1746-NOC as discontinued, date Not published (Rockwell product page retired), replacement category Not published.
No replacement catalog number is planned for this number, so stock in the secondary market is the supply route and a machine that depends on it should carry its own spare.
Rockwell's migration guidance for Bulletin 1746 moves I/O to Compact 5000 modules on a Logix controller; a mechanical part such as this does not migrate with the electronics.
What is 1746-NOC?
1746 SLC System spare assembly, catalog number 1746-NOC, spare assembly in the SLC 500 range.
Which chassis does 1746-NOC fit?
The modular SLC 500 chassis, 1746-A4, A7, A10 and A13, and the fixed-style expansion rack where the number is listed for it.
Does 1746-NOC draw backplane current?
No. It is a mechanical or assembly part and takes no slot address.
Is 1746-NOC still available?
Rockwell lists it as discontinued, date Not published (Rockwell product page retired), replacement category Not published.
Is a Rockwell publication available for 1746-NOC?
Rockwell documents it under 1746-IN016.
1746-NOC belongs to the SLC 500 modular hardware range. A SLC 500 modular system is a 1746 chassis with a power supply, a processor or an I/O adapter in the left-most slot, and I/O modules in the remaining slots.
The chassis sizes published in the SLC 500 selection guide are 4, 7, 10 and 13 slots, and a maximum of three chassis can be linked in one system. Where a catalog number falls outside those published sizes, its slot count has to be confirmed against current literature before it is quoted into a bill of materials.
A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.
Power supply selection is a two-rail comparison, not a wattage comparison: 1746-P1 gives 2.0 A at 5V and 0.46 A at 24V, 1746-P2 gives 5.0 A and 0.96 A, 1746-P3 gives 3.6 A and 0.87 A from a 19.2 to 28.8V DC input, and 1746-P4 gives 10.0 A and 2.88 A with a 70 W total limit across all outputs. Choosing by input voltage alone and ignoring the 24V allowance is how a chassis ends up short on analog capacity.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
The Allen-Bradley SLC 500 1746 I/O modules category lists the related catalog numbers, options and accessories for this range.