Product Details:
Payment & Shipping Terms:
|
1746-HSCE2 is the Multi-channel high speed counter module for the Allen-Bradley SLC 500: 1746 SLC System, Multi-channel High Speed Counter Module.
It is a specialty module, so the values below are the ones Rockwell publishes for this catalog number, and anything the publication does not print is marked not published.
| 1746-HSCE | SLC 1 Channel High Speed Counter Module | IN STOCK |
| 1746-HSCE2 | SLC 4 Channel High Speed Counter Module | IN STOCK |
| 1746-HSTP1 | SLC 1 Axis Stepper Module | IN STOCK |
| 1746-BTM | SLC Barrel Temperature Control Module | IN STOCK |
| 1746-BAS-T | SLC High Speed BASIC Language Module | IN STOCK |
| 1746-INT4 | SLC 4 Channel Isolated Thermocouple Module | IN STOCK |
| 1746-HCA | IMC 110 to Terminal Panel Cable | IN STOCK |
| 1746-HT | IMC 110 Termination Panel | IN STOCK |
Application |
1746 SLC System, Multi-channel High Speed Counter Module |
Cat Num |
1746-HSCE2 |
Brand Name |
Rockwell |
Product Type |
Multi-channel high speed counter module |
Number of channels |
4 |
Input signal |
5V dc at 4.2...12V dc, and 24V dc |
Output |
2 analog voltage outputs |
Isolation |
1000V |
Lifecycle |
Discontinued |
Discontinued date |
September 30, 2024 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN011 (module specifications) and 1746-IN011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-HSCE2 is the multi-channel member of the family: four counter inputs in one slot instead of one, plus two analog voltage outputs that can be driven from the counter result.
Application: 1746 SLC System, Multi-channel High Speed Counter Module.
Cat Num: 1746-HSCE2.
Brand Name: Rockwell.
Product Type: Multi-channel high speed counter module.
Number of channels: 4.
Input signal: 5V dc at 4.2...12V dc, and 24V dc.
Output: 2 analog voltage outputs.
Isolation: 1000V.
Lifecycle: Discontinued.
Discontinued date: September 30, 2024.
Replacement category: Engineering Replacement.
Inputs accept 5V dc signals in the 4.2...12V dc window and 24V dc signals directly, with 1000V isolation. The two analog voltage outputs mean a counter value can be sent to a drive or a meter without a separate analog card in the rack.
Four channels in one slot is the reason this card is specified where several axes are counted on the same machine; the alternative is four single-channel modules and four slots of chassis current.
It suits a machine with several independent encoders, such as a converting line with an unwind, a feed and a cutoff, where each axis needs its own count but the analog demand is modest.
A slot-zero rule applies across the family: the module goes in any I/O slot except the processor slot, and its address follows the slot number.
Rockwell lists 1746-HSCE2 as discontinued, date September 30, 2024, replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page for this number, so the route is an engineering substitution with the function re-implemented on a Logix platform.
Rockwell documents the module in 1746-IN011; that publication, not a distributor page, is the source for the values above.
What is 1746-HSCE2?
1746 SLC System, Multi-channel High Speed Counter Module. Multi-channel high speed counter module.
How many channels does 1746-HSCE2 have?
4
Which slot does 1746-HSCE2 go in?
Any I/O slot except slot 0, which is reserved for the processor.
What isolation does 1746-HSCE2 provide?
1000V
Is 1746-HSCE2 still available?
Rockwell lists it as discontinued, date September 30, 2024, replacement category Engineering Replacement.
1746-HSCE2 is a high-speed counter module with 24-bit resolution for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-HSCE2 |
| Module type | high-speed counter module with 24-bit resolution |
| Function | High-speed counting with sourcing outputs |
| Counts | 24-bit, +/-8,388,607 in Class 4, 16-bit +/-32,768 in Class 1 |
| Throughput | 700 microseconds typical |
| Outputs | 4 sourcing outputs, 5...30V DC, electronically protected |
| Output current | 1 A |
The 24-bit count in Class 4 is what makes this module usable for a totalising application where a 16-bit counter would roll over mid-shift, and the 1 A sourcing outputs will drive a small solenoid or a relay directly rather than through an interface. Both are decisions about the application, not about the backplane: the counter still uses one slot.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
Heat is part of the same calculation as current: the selection guide carries a heat dissipation figure per module, and the chassis total is the sum of those figures. A rack that is electrically legal and thermally packed still derates in a closed cabinet, which is why the procedure in the guide sums watts slot by slot instead of estimating from the 5V current.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.