Product Details:
Payment & Shipping Terms:
|
1746-HSCE is the High speed counter/encoder module for the Allen-Bradley SLC 500: 1746 SLC System, High Speed Counter Encoder For Programmable Ctrlr.
It is a specialty module, so the values below are the ones Rockwell publishes for this catalog number, and anything the publication does not print is marked not published.
| 1746-HSCE | SLC 1 Channel High Speed Counter Module | IN STOCK |
| 1746-HSCE2 | SLC 4 Channel High Speed Counter Module | IN STOCK |
| 1746-HSTP1 | SLC 1 Axis Stepper Module | IN STOCK |
| 1746-BTM | SLC Barrel Temperature Control Module | IN STOCK |
| 1746-BAS-T | SLC High Speed BASIC Language Module | IN STOCK |
| 1746-INT4 | SLC 4 Channel Isolated Thermocouple Module | IN STOCK |
| 1746-HCA | IMC 110 to Terminal Panel Cable | IN STOCK |
| 1746-HT | IMC 110 Termination Panel | IN STOCK |
Application |
1746 SLC System, High Speed Counter Encoder For Programmable Ctrlr |
Cat Num |
1746-HSCE |
Brand Name |
Rockwell |
Product Type |
High speed counter/encoder module |
Number of channels |
1 |
Input signal |
Differential, 0...5V dc |
Isolation |
1500V |
Module interface |
Analog, per the Rockwell product data |
Lifecycle |
Discontinued |
Discontinued date |
September 30, 2024 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN011 (module specifications) and 1746-IN011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-HSCE is a single-channel high-speed counter and encoder interface for the SLC 500. It counts pulses in hardware instead of in the ladder scan, so a shaft encoder that turns faster than the program can read a discrete input still produces a usable count.
Application: 1746 SLC System, High Speed Counter Encoder For Programmable Ctrlr.
Cat Num: 1746-HSCE.
Brand Name: Rockwell.
Product Type: High speed counter/encoder module.
Number of channels: 1.
Input signal: Differential, 0...5V dc.
Isolation: 1500V.
Module interface: Analog, per the Rockwell product data.
Lifecycle: Discontinued.
Discontinued date: September 30, 2024.
Replacement category: Engineering Replacement.
The input is differential, 0...5V dc, with 1500V isolation between the field side and the backplane. A differential input is what allows an encoder line driver to be run over a longer cable than a single-ended signal would tolerate in a panel full of contactors.
The module is configured from the processor's I/O configuration and its data appears in the input image, so the count, the preset and the output pattern are read and written as ordinary SLC addresses rather than through a separate bus.
Typical use is a machine axis where length or position is derived from an encoder count: a flying saw, a cut-to-length line, or a web tension loop. The module is not a motion controller and does not close a position loop on its own.
A slot-zero rule applies across the family: the module goes in any I/O slot except the processor slot, and its address follows the slot number.
Rockwell lists 1746-HSCE as discontinued, date September 30, 2024, replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page for this number, so the route is an engineering substitution with the function re-implemented on a Logix platform.
Rockwell documents the module in 1746-IN011; that publication, not a distributor page, is the source for the values above.
What is 1746-HSCE?
1746 SLC System, High Speed Counter Encoder For Programmable Ctrlr. High speed counter/encoder module.
How many channels does 1746-HSCE have?
1
Which slot does 1746-HSCE go in?
Any I/O slot except slot 0, which is reserved for the processor.
What isolation does 1746-HSCE provide?
1500V
Is 1746-HSCE still available?
Rockwell lists it as discontinued, date September 30, 2024, replacement category Engineering Replacement.
1746-HSCE is a high-speed counter module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-HSCE |
| Module type | high-speed counter module |
| Function | High-speed counting with outputs |
| Counts | 16-bit, +/-32,768 |
| Throughput | 1.8 ms in sequencer mode, 3.9 ms in range mode |
| Outputs | 4 open-collector outputs, 5V / 12V / 24V DC |
| Output current | 16 mA at 4.5V DC, 40 mA at 10V DC |
A counter module counts in hardware, so the count does not depend on the ladder scan time: 1.8 ms throughput in sequencer mode and 3.9 ms in range mode are the module reporting intervals, not the resolution of the count itself. The open-collector outputs are low-current devices, which is why they drive a solid-state relay or an input card rather than a contactor coil directly.
A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.
SLC 500 processors span 1 K to 64 K of memory and can address up to 4096 inputs and 4096 outputs, and every modular processor except the SLC 5/01 can control remotely located I/O through a scanner. That distinction is what makes a 5/01 unsuitable as the head of a distributed system regardless of its I/O count.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
This part sits in the Allen-Bradley SLC 500 1746 I/O modules category, with the other models and spare parts listed alongside it.