Product Details:
Payment & Shipping Terms:
|
1746-BAS-T is the BASIC language coprocessor module for the Allen-Bradley SLC 500: SLC High Speed BASIC Language Module.
It is a specialty module, so the values below are the ones Rockwell publishes for this catalog number, and anything the publication does not print is marked not published.
| 1746-HSCE | SLC 1 Channel High Speed Counter Module | IN STOCK |
| 1746-HSCE2 | SLC 4 Channel High Speed Counter Module | IN STOCK |
| 1746-HSTP1 | SLC 1 Axis Stepper Module | IN STOCK |
| 1746-BTM | SLC Barrel Temperature Control Module | IN STOCK |
| 1746-BAS-T | SLC High Speed BASIC Language Module | IN STOCK |
| 1746-INT4 | SLC 4 Channel Isolated Thermocouple Module | IN STOCK |
| 1746-HCA | IMC 110 to Terminal Panel Cable | IN STOCK |
| 1746-HT | IMC 110 Termination Panel | IN STOCK |
Application |
SLC High Speed BASIC Language Module |
Cat Num |
1746-BAS-T |
Brand Name |
Rockwell |
Product Type |
BASIC language coprocessor module |
Official title |
SLC High Speed BASIC Language Module |
Lifecycle |
Discontinued |
Discontinued date |
October 1, 2013 |
Replacement category |
No planned RA replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1747-UM011 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1746-BAS-T is the high-speed BASIC language module: a coprocessor that runs a BASIC program alongside the SLC ladder and exchanges data with it through the module's image words.
Application: SLC High Speed BASIC Language Module.
Cat Num: 1746-BAS-T.
Brand Name: Rockwell.
Product Type: BASIC language coprocessor module.
Official title: SLC High Speed BASIC Language Module.
Lifecycle: Discontinued.
Discontinued date: October 1, 2013.
Replacement category: No planned RA replacement.
The module exists for the work a PLC ladder is poor at: string handling, ASCII protocols on a serial port, and arithmetic that would take hundreds of ladder rungs. The ladder keeps the machine interlock and the BASIC side does the message building.
Port count, memory and the file structure are printed in the 1746-BAS and 1746-BAS-T installation instructions; this page does not restate numbers that belong to that document.
Typical applications are a weighbridge or a label printer link, where a third-party device speaks an ASCII protocol and the SLC has to be the master without a communication card.
A slot-zero rule applies across the family: the module goes in any I/O slot except the processor slot, and its address follows the slot number.
Rockwell lists 1746-BAS-T as discontinued, date October 1, 2013, replacement category No planned RA replacement.
No replacement catalog number is printed on the Rockwell page for this number, so the route is an engineering substitution with the function re-implemented on a Logix platform.
Rockwell documents the module in 1747-UM011; that publication, not a distributor page, is the source for the values above.
What is 1746-BAS-T?
SLC High Speed BASIC Language Module. BASIC language coprocessor module.
How many channels does 1746-BAS-T have?
See the technical data table above.
Which slot does 1746-BAS-T go in?
Any I/O slot except slot 0, which is reserved for the processor.
What isolation does 1746-BAS-T provide?
Not published for this catalog number.
Is 1746-BAS-T still available?
Rockwell lists it as discontinued, date October 1, 2013, replacement category No planned RA replacement.
1746-BAS-T is a BASIC language module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-BAS-T |
| Module type | BASIC language module |
| Memory | 24 Kbytes battery-backed RAM |
| Optional memory modules | 1771-DBMEM1, 1771-DBMEM2 |
| Port 1 | RS-232/423, RS-422, RS-485 |
| Port 2 | RS-232/423, RS-422, RS-485 |
| DH-485 port | DH-485 |
| Isolation, backplane to port | 710V DC for 1 minute |
| Power supply loading | 5V DC 0.150 A, 24V DC 0.040 A |
The BASIC module runs its own program in BASIC and exchanges data with the SLC through the backplane, which makes it a co-processor rather than an I/O card: serial devices that speak an ASCII protocol can be integrated without loading the ladder scan. The 710V DC one-minute isolation between the backplane and each port is what allows an RS-232 device referenced to a different ground to be connected without a common-mode path back into the rack.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
Power supply selection is a two-rail comparison, not a wattage comparison: 1746-P1 gives 2.0 A at 5V and 0.46 A at 24V, 1746-P2 gives 5.0 A and 0.96 A, 1746-P3 gives 3.6 A and 0.87 A from a 19.2 to 28.8V DC input, and 1746-P4 gives 10.0 A and 2.88 A with a 70 W total limit across all outputs. Choosing by input voltage alone and ignoring the 24V allowance is how a chassis ends up short on analog capacity.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
This part sits in the Allen-Bradley SLC 500 1746 I/O modules category, with the other models and spare parts listed alongside it.