logo
Home ProductsAB SLC-500 Systems 1746

Allen Bradley PLC 1746-NT8 / 1746NT8

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1746-NT8 / 1746NT8

China Allen Bradley PLC 1746-NT8 / 1746NT8 supplier
Allen Bradley PLC 1746-NT8 / 1746NT8 supplier Allen Bradley PLC 1746-NT8 / 1746NT8 supplier Allen Bradley PLC 1746-NT8 / 1746NT8 supplier Allen Bradley PLC 1746-NT8 / 1746NT8 supplier Allen Bradley PLC 1746-NT8 / 1746NT8 supplier

Large Image :  Allen Bradley PLC 1746-NT8 / 1746NT8

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1746-NT8 / 1746NT8

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $1160.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1746-NT8 technical data PDF download 1746-NT8 8 Point Thermocouple Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: SLC 500 thermocouple/mV input module

1746-NT8 is the 8 Point Thermocouple Input Module in the Allen-Bradley SLC 500 range: 1746 SLC System, Thermocouple/Mv Analog Input Module.

It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.

1746-NT4 4 Point Thermocouple Input Module IN STOCK
1746-NT8 8 Point Thermocouple Input Module IN STOCK

Product Specifications 1746-NT8 (PDF)
 Application
 1746 SLC System, Thermocouple/Mv Analog Input Module
 Cat Num
 1746-NT8
 Brand Name
 Rockwell
 Product Type
 8 Point Thermocouple Input Module
 Channels
 8 thermocouple or millivolt inputs
 Input range
 Types J, K, T, E, B, R, S, N; ±50 mV and ±100 mV direct
 Resolution
 16-bit, 0.1 °C or 0.1 °F
 Backplane current, 5V DC
 120 mA
 Backplane current, 24V DC
 70 mA
 Update time / filtering
 Sigma-Delta, filter 10...250 Hz, step response 356 ms...4.05 s
 Isolation
 500V dc transient, backplane and channel-to-channel
 Lifecycle
 Discontinued
 Discontinued date
 September 30, 2024
 Replacement category
 Engineering Replacement

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN015 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1746-NT8 original product photograph 1 1746-NT8 original product photograph 2 1746-NT8 original product photograph 3

What 1746-NT8 is

Official Rockwell description: 1746 SLC System, Thermocouple/Mv Analog Input Module.

8 Point Thermocouple Input Module with 8 thermocouple or millivolt inputs.

Technical data

Application: 1746 SLC System, Thermocouple/Mv Analog Input Module.

Cat Num: 1746-NT8.

Brand Name: Rockwell.

Product Type: 8 Point Thermocouple Input Module.

Channels: 8 thermocouple or millivolt inputs.

Input range: Types J, K, T, E, B, R, S, N; ±50 mV and ±100 mV direct.

Resolution: 16-bit, 0.1 °C or 0.1 °F.

Backplane current, 5V DC: 120 mA.

Backplane current, 24V DC: 70 mA.

Update time / filtering: Sigma-Delta, filter 10...250 Hz, step response 356 ms...4.05 s.

Isolation: 500V dc transient, backplane and channel-to-channel.

Lifecycle: Discontinued.

Discontinued date: September 30, 2024.

Replacement category: Engineering Replacement.

Wiring and channel configuration

Cold junction compensation is on the terminal block, one sensor for the group of channels, so a terminal block swapped between modules carries its own calibration and has to stay with the card.

The input is differential and the potential between any two channels is limited, which rules out tying several thermocouples to a common earthed shield without checking the channel-to-channel voltage.

Thermocouple type, filter frequency and data format are configured in software; the type has to match the actual sensor, because a J curve read as a K curve produces a plausible but wrong temperature.

Lifecycle and migration route

Rockwell lists 1746-NT8 as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.

No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.

Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.

The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.

Power budget, slot rules and accuracy

A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.

The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.

Isolation is 500V dc transient, backplane and channel-to-channel between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.

Related cards in this family

  • 1746-NT4 — 4 Point Thermocouple Input Module
  • 1746-NT8 — 8 Point Thermocouple Input Module

The card in red in the catalogue table at the top of this page is the one described here.

FAQ — 1746-NT8

What is 1746-NT8?

1746 SLC System, Thermocouple/Mv Analog Input Module. 8 Point Thermocouple Input Module.

How many channels does 1746-NT8 have?

8 thermocouple or millivolt inputs.

What ranges does 1746-NT8 accept?

Inputs: Types J, K, T, E, B, R, S, N; ±50 mV and ±100 mV direct.

How much backplane current does 1746-NT8 draw?

120 mA at 5V dc and 70 mA at 24V dc.

Is 1746-NT8 still available?

Rockwell lists it as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.


Data sources. Technical values on this page come from Rockwell publication 1746-IN015 and the Rockwell product page for this catalog number. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

1746 1746-NT8: 8-channel thermocouple/mV input module

1746-NT8 is a 8-channel thermocouple/mV input module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.

AttributeValue
Catalog number1746-NT8
Module type8-channel thermocouple/mV input module
Inputs8 plus a CJC sensor
Thermocouple typesJ, K, T, E, R, S, B, N
Backplane current @ 5V120 mA
Backplane current @ 24V70 mA
Cold junction compensationIntegrated
DiagnosticsFault diagnostics and status LEDs

Eight thermocouples in one slot means eight cold junctions inside one terminal block, and the integrated CJC is what keeps those eight readings from drifting together as the cabinet warms. The 120 mA 5V draw is the reason a full thermocouple chassis is planned on the 5V rail first and the 24V rail second.

A maximum of three chassis can be linked with chassis interconnect cables, and the cable is chosen by the physical gap between the enclosures rather than by preference: 1746-C7 covers up to 152.4 mm, 1746-C9 covers 152.4 mm up to 914.4 mm, and 1746-C16 covers 0.914 m up to 1.27 m. A gap of 1.3 m is outside the range of every cable in the family.

Heat is part of the same calculation as current: the selection guide carries a heat dissipation figure per module, and the chassis total is the sum of those figures. A rack that is electrically legal and thermally packed still derates in a closed cabinet, which is why the procedure in the guide sums watts slot by slot instead of estimating from the 5V current.

Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.

Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.

Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.

This part sits in the Allen-Bradley SLC 500 1746 I/O modules category, with the other models and spare parts listed alongside it.