This page documents the 22C-D072A103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, D fixes the 380...480 V AC three phase input, 072 is the rating code that sets 72.0 A and 37.0 kW (50 HP) in frame E, A is the enclosure (panel mount, IP30, NEMA/UL Type 1), and 103, the standard build ending used at both voltages and every frame closes the number.
| Position | Value |
| 1-3 | 22C, PowerFlex 400 adjustable frequency drive for fan and pump applications |
| 4 | D, 380...480 V AC three phase |
| 5-7 | 072, 72.0 A output current and 37.0 kW (50 HP), frame E |
| 8 | A, panel mount, IP30, NEMA/UL Type 1 |
| 9-12 | 103, the standard build ending used at both voltages and every frame |
| Attribute | Value |
| Output current | 72.0 A |
| Motor rating | 37.0 kW (50 HP), variable torque fan and pump duty |
| Frame | E |
| Power terminal range, frame E | 33.6 mm2 (2 AWG) maximum for 480V 37...45 kW (50...60 HP); 107.2 mm2 (4/0 AWG) maximum and 53.5 mm2 (1/0 AWG) minimum for 240V 30...37 kW (40...50 HP) and 480V 55...75 kW (75...100 HP) |
| Input voltage | 380...480 V AC , 340...528 V AC window printed in the rating table |
| Ambient, panel mount | 45 C (113 F) surrounding air, IP20 open and IP30 Type 1 |
The published table places this rating between 060: 60.0 A, 30.0 kW (40 HP), frame D; 088: 88.0 A, 45.0 kW (60 HP), frame E. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.
Direct links to the neighbouring ratings in this voltage class: 22C-D060, 22C-D088.
The isolation transformer pairing is published. Each rating is paired in the publication with a 1321-3TW or 1321-3TH isolation transformer from 5 kVA to 390 kVA, with 208 V, 230 V, 460 V and 575 V primaries. On a corner grounded delta or an ungrounded system, that pairing is the published route to a drive input voltage the range was tested at, and it is cheaper than arguing about the supply afterwards.
Ambient is a cabinet number, not a drive number. The panel mount drives are published for a 45 C (113 F) surrounding air temperature, and that figure is measured inside the enclosure rather than in the plant. A fan or pump room at 35 C with an unventilated cabinet at 52 C is a drive running 7 C over its published ambient, and the remedy is airflow or the flange option, not a larger drive.
Frame e is two terminal blocks under one letter. Frame E covers 480 V 37...45 kW (50...60 HP) drives that take up to 8 AWG and 240 V 30...37 kW / 480 V 55...75 kW drives that take up to 4/0 AWG. Two drives with the same frame letter can therefore need different lugs and different cable, and the rating code rather than the frame is what tells them apart.
What the current figure does and does not cover. The output current in the table is the drive rating at the published ambient and switching conditions. Motor current on a fan varies with speed and air density, so a drive sized exactly to the motor nameplate can be short of current on a cold day at full speed; the margin is a design decision, and the table gives the ceiling it has to fit under.
Terminals follow ul, the installation code may not. Power terminals are sized according to UL, and the publication states that local or national codes may require a larger conductor than the terminal accepts, in which case multiple conductors, 90 C wire or lugs are used. The wire range in the frame table is a terminal limit; the run to the motor is a separate calculation done against the installation code in force.
Frame E in practice. Frame E is two terminal blocks under one letter: 480 V 37...45 kW (50...60 HP) drives take up to 8 AWG, while 240 V 30...37 kW and 480 V 55...75 kW drives take up to 4/0 AWG at a different minimum. The flange option ends partway through this frame, at 15 kW (20 HP) at 480 V and 7.5 kW (10 HP) at 240 V, so a large frame E is always a cabinet mounted drive.
How this page should be used. Use the position table to confirm what the number actually contains, and the rating table to check the current against the motor. Neither table replaces the wiring manual or the protection selection, and a page that pretends otherwise is the reason commissioning arguments start at the terminal strip rather than at the drawing.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The family is designed so that the module is the replaceable unit and the base stays on the machine. That is why the base is ordered with the module, why the keyswitch on the base has to match the module class, and why the ground lug is also a mounting hole: the conductive path runs through the base and the plate rather than through the module. Swapping a module onto a dirty base is the failure that looks like a module fault and measures as a missing earth.
ArmorPoint modules are installed by bridging two bases, which is why every mechanical figure in this family is stated with the base included rather than for the module alone.
Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied.
This page links twelve of the 47 22C records on this site; the closest rating codes come first. This page is 22C-D072A103.
For the surrounding range, open the AB Drives & Motors catalogue index — 22C-D072A103 is listed there beside the rest of the drive and motor group. Reach it directly if the suffix on this record still needs confirming against a sibling.