logo
Home ProductsAB Drives & Motors

Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103

China Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier
Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103 supplier

Large Image :  Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103

Product Details:

Place of Origin: Made in CHINA
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PowerFlex 22C-D022N103 / 22CD022N103

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $657.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Western Union and Paypal.
Supply Ability: 5 PCS
Detailed Product Description

22C-D022N103

This page documents the 22C-D022N103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, D fixes the 380...480 V AC three phase input, 022 is the rating code that sets 22.0 A and 11.0 kW (15 HP) in frame C, N is the enclosure (panel mount, IP20, NEMA/UL Type Open), and 103, the standard build ending used at both voltages and every frame closes the number.

Catalog number, position by position

PositionValue
1-322C, PowerFlex 400 adjustable frequency drive for fan and pump applications
4D, 380...480 V AC three phase
5-7022, 22.0 A output current and 11.0 kW (15 HP), frame C
8N, panel mount, IP20, NEMA/UL Type Open
9-12103, the standard build ending used at both voltages and every frame

Rating data for this number

AttributeValue
Output current22.0 A
Motor rating11.0 kW (15 HP), variable torque fan and pump duty
FrameC
Power terminal range, frame C8.4 mm2 (8 AWG) maximum, 1.3 mm2 (16 AWG) minimum, recommended torque 3.7 N.m (33 lb.in)
Input voltage380...480 V AC , 340...528 V AC window printed in the rating table
Ambient, panel mount45 C (113 F) surrounding air, IP20 open and IP30 Type 1

Ratings either side of this one

The published table places this rating between 017: 17.0 A, 7.5 kW (10 HP), frame C; 030: 30.0 A, 15.0 kW (20 HP), frame C. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.

Direct links to the neighbouring ratings in this voltage class: 22C-D017, 22C-D030.

The 103 ending is the standard build. Every standard drive in the published selection tables ends in 103, at both voltages and across every frame, so the ending is not an option code. Options change it by adding characters, and those options are listed separately as user installed equipment. A number that does not end in 103 is therefore worth reading against that option list rather than against the rating table.

480 v input window in the tables. The 380...480 V AC drives carry a 340...528 V AC input window in the rating tables, wider than the voltage on the nameplate. A loaded transformer sagging to 350 V during a large fan start stays inside that window, and a site running near 500 V stays inside it too; a site above 528 V does not, and that is a transformer tap question rather than a drive question.

The duty this range was written for. The published range covers 3.0...350 HP at 480 V AC and 3.0...50 HP at 240 V AC, all three phase and all variable torque fan and pump duty. That is not a marketing description: the overload profile, the current tables and the built-in pump functions are all written for a quadratic load, and a constant torque load such as a positive displacement pump has to be sized outside those tables.

Interface options and the enclosure rating. Two interface options are published with the drives: a NEMA/UL Type 1 bezel for panel mounting and a NEMA/UL Type 4X/12 remote panel mount unit. The remote part lets an engineer stand at the fan during commissioning, and the bezel is what keeps a Type 1 rating intact after the interface is moved to the door.

Flange mounting is an option with a rating ceiling. Flange mounting is restricted to frames through 15 kW (20 HP) at 380...480 V AC and through 7.5 kW (10 HP) at 200...240 V AC, and the heatsink then passes through the back of the enclosure with an IP66, NEMA/UL Type 4X/12 backside rated for indoor or outdoor use. Above those ratings the option disappears from the selection table entirely, which is why a re-rated fan can lose the flange route without anyone noticing at quotation stage.

Frame C in practice. Frame C is the frame that changes character with the enclosure code. It ships as IP20 open and reaches IP30 Type 1 only through a field installed conversion kit with a top cover and conduit box, and it is the only frame where flange mounting is available at the lower ratings. The terminal block takes up to 8 AWG at 3.7 N.m, so a 5 HP fan on a long run is a wire size question rather than a lug question.

The boundary of the published data. Everything printed here comes from the 22C technical data, including the frame terminal ranges and the ambient statement. Anything an application needs beyond that, such as the motor cable length limit or the earth fault behaviour, is in the user manual for this range and not in the sales tables.

Environmental and installation context

ParameterValue
Dimensions with base120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters
Enclosure ratingMeets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one
Operating temperature-20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock
Storage temperature-40 to 85 degrees C (-40 to 185 degrees F)
Relative humidity5 to 95 percent non-condensing, IEC 60068-2-30 damp heat
Shock and vibrationOperating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating
Isolation50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s
ESD and RF immunity6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz
Transient immunityPlus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge
EmissionsCISPR 11 Group 1 Class A
MountingMounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole
Weight0.29 kg (0.64 lb) with base
Field power bus24 V dc nominal, 10 to 28.8 V dc range
PointBus current75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23

A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.

Field power and PointBus power are two separate budgets. The bus current listed for each module is drawn at 5 V dc from the adapter, and the field power at 10 to 28.8 V dc is what the sensors and the loads take; a segment planned on one of them and commissioned on the other trips on the one that was not counted.

Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied.

Related catalog numbers in the 22C range

Twelve of the 47 22C records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 22C-D022N103.

Group index: AB Drives & Motors. 22C-D022N103 is filed under that heading in the site's own product tree.

Sources. Rockwell publishes the PowerFlex 400 user manual as 22C-UM001 and the technical data for the family as 22C-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22C-D022N103 follow those two publications.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)