This page documents the 22C-D010N103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, D fixes the 380...480 V AC three phase input, 010 is the rating code that sets 10.5 A and 4.0 kW (5 HP) in frame C, N is the enclosure (panel mount, IP20, NEMA/UL Type Open), and 103, the standard build ending used at both voltages and every frame closes the number.
| Position | Value |
| 1-3 | 22C, PowerFlex 400 adjustable frequency drive for fan and pump applications |
| 4 | D, 380...480 V AC three phase |
| 5-7 | 010, 10.5 A output current and 4.0 kW (5 HP), frame C |
| 8 | N, panel mount, IP20, NEMA/UL Type Open |
| 9-12 | 103, the standard build ending used at both voltages and every frame |
| Attribute | Value |
| Output current | 10.5 A |
| Motor rating | 4.0 kW (5 HP), variable torque fan and pump duty |
| Frame | C |
| Power terminal range, frame C | 8.4 mm2 (8 AWG) maximum, 1.3 mm2 (16 AWG) minimum, recommended torque 3.7 N.m (33 lb.in) |
| Input voltage | 380...480 V AC , 340...528 V AC window printed in the rating table |
| Ambient, panel mount | 45 C (113 F) surrounding air, IP20 open and IP30 Type 1 |
The published table places this rating between 6P0: 6.0 A, 2.2 kW (3 HP), frame C; 012: 12.0 A, 5.5 kW (8 HP), frame C. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.
Direct links to the neighbouring ratings in this voltage class: 22C-D6P0, 22C-D012.
Interface options and the enclosure rating. Two interface options are published with the drives: a NEMA/UL Type 1 bezel for panel mounting and a NEMA/UL Type 4X/12 remote panel mount unit. The remote part lets an engineer stand at the fan during commissioning, and the bezel is what keeps a Type 1 rating intact after the interface is moved to the door.
Flange mounting is an option with a rating ceiling. Flange mounting is restricted to frames through 15 kW (20 HP) at 380...480 V AC and through 7.5 kW (10 HP) at 200...240 V AC, and the heatsink then passes through the back of the enclosure with an IP66, NEMA/UL Type 4X/12 backside rated for indoor or outdoor use. Above those ratings the option disappears from the selection table entirely, which is why a re-rated fan can lose the flange route without anyone noticing at quotation stage.
The isolation transformer pairing is published. Each rating is paired in the publication with a 1321-3TW or 1321-3TH isolation transformer from 5 kVA to 390 kVA, with 208 V, 230 V, 460 V and 575 V primaries. On a corner grounded delta or an ungrounded system, that pairing is the published route to a drive input voltage the range was tested at, and it is cheaper than arguing about the supply afterwards.
Ambient is a cabinet number, not a drive number. The panel mount drives are published for a 45 C (113 F) surrounding air temperature, and that figure is measured inside the enclosure rather than in the plant. A fan or pump room at 35 C with an unventilated cabinet at 52 C is a drive running 7 C over its published ambient, and the remedy is airflow or the flange option, not a larger drive.
Frame e is two terminal blocks under one letter. Frame E covers 480 V 37...45 kW (50...60 HP) drives that take up to 8 AWG and 240 V 30...37 kW / 480 V 55...75 kW drives that take up to 4/0 AWG. Two drives with the same frame letter can therefore need different lugs and different cable, and the rating code rather than the frame is what tells them apart.
Frame C in practice. Frame C is the frame that changes character with the enclosure code. It ships as IP20 open and reaches IP30 Type 1 only through a field installed conversion kit with a top cover and conduit box, and it is the only frame where flange mounting is available at the lower ratings. The terminal block takes up to 8 AWG at 3.7 N.m, so a 5 HP fan on a long run is a wire size question rather than a lug question.
How this page should be used. Use the position table to confirm what the number actually contains, and the rating table to check the current against the motor. Neither table replaces the wiring manual or the protection selection, and a page that pretends otherwise is the reason commissioning arguments start at the terminal strip rather than at the drawing.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
Field power and PointBus power are two separate budgets. The bus current listed for each module is drawn at 5 V dc from the adapter, and the field power at 10 to 28.8 V dc is what the sensors and the loads take; a segment planned on one of them and commissioned on the other trips on the one that was not counted.
Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied.
Twelve of the 47 22C records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 22C-D010N103.
Group index: AB Drives & Motors. 22C-D010N103 is filed under that heading in the site's own product tree. The index sits one level above this page in the site tree.
Sources. Rockwell publishes the PowerFlex 400 user manual as 22C-UM001 and the technical data for the family as 22C-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22C-D010N103 follow those two publications.