This page documents the 22C-B120A103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, B fixes the 200...240 V AC three phase input, 120 is the rating code that sets 120.0 A and 30.0 kW (40 HP) in frame E, A is the enclosure (panel mount, IP30, NEMA/UL Type 1), and 103, the standard build ending used at both voltages and every frame closes the number.
| Position | Value |
| 1-3 | 22C, PowerFlex 400 adjustable frequency drive for fan and pump applications |
| 4 | B, 200...240 V AC three phase |
| 5-7 | 120, 120.0 A output current and 30.0 kW (40 HP), frame E |
| 8 | A, panel mount, IP30, NEMA/UL Type 1 |
| 9-12 | 103, the standard build ending used at both voltages and every frame |
| Attribute | Value |
| Output current | 120.0 A |
| Motor rating | 30.0 kW (40 HP), variable torque fan and pump duty |
| Frame | E |
| Power terminal range, frame E | 33.6 mm2 (2 AWG) maximum for 480V 37...45 kW (50...60 HP); 107.2 mm2 (4/0 AWG) maximum and 53.5 mm2 (1/0 AWG) minimum for 240V 30...37 kW (40...50 HP) and 480V 55...75 kW (75...100 HP) |
| Input voltage | 200...240 V AC |
| Ambient, panel mount | 45 C (113 F) surrounding air, IP20 open and IP30 Type 1 |
The published table places this rating between 090: 90.0 A, 22.0 kW (30 HP), frame D; 145: 145.0 A, 37.0 kW (50 HP), frame E. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.
Direct links to the neighbouring ratings in this voltage class: 22C-B090, 22C-B145.
Flange mounting is an option with a rating ceiling. Flange mounting is restricted to frames through 15 kW (20 HP) at 380...480 V AC and through 7.5 kW (10 HP) at 200...240 V AC, and the heatsink then passes through the back of the enclosure with an IP66, NEMA/UL Type 4X/12 backside rated for indoor or outdoor use. Above those ratings the option disappears from the selection table entirely, which is why a re-rated fan can lose the flange route without anyone noticing at quotation stage.
The isolation transformer pairing is published. Each rating is paired in the publication with a 1321-3TW or 1321-3TH isolation transformer from 5 kVA to 390 kVA, with 208 V, 230 V, 460 V and 575 V primaries. On a corner grounded delta or an ungrounded system, that pairing is the published route to a drive input voltage the range was tested at, and it is cheaper than arguing about the supply afterwards.
Ambient is a cabinet number, not a drive number. The panel mount drives are published for a 45 C (113 F) surrounding air temperature, and that figure is measured inside the enclosure rather than in the plant. A fan or pump room at 35 C with an unventilated cabinet at 52 C is a drive running 7 C over its published ambient, and the remedy is airflow or the flange option, not a larger drive.
Frame e is two terminal blocks under one letter. Frame E covers 480 V 37...45 kW (50...60 HP) drives that take up to 8 AWG and 240 V 30...37 kW / 480 V 55...75 kW drives that take up to 4/0 AWG. Two drives with the same frame letter can therefore need different lugs and different cable, and the rating code rather than the frame is what tells them apart.
What the current figure does and does not cover. The output current in the table is the drive rating at the published ambient and switching conditions. Motor current on a fan varies with speed and air density, so a drive sized exactly to the motor nameplate can be short of current on a cold day at full speed; the margin is a design decision, and the table gives the ceiling it has to fit under.
Frame E in practice. Frame E is two terminal blocks under one letter: 480 V 37...45 kW (50...60 HP) drives take up to 8 AWG, while 240 V 30...37 kW and 480 V 55...75 kW drives take up to 4/0 AWG at a different minimum. The flange option ends partway through this frame, at 15 kW (20 HP) at 480 V and 7.5 kW (10 HP) at 240 V, so a large frame E is always a cabinet mounted drive.
The boundary of the published data. Everything printed here comes from the 22C technical data, including the frame terminal ranges and the ambient statement. Anything an application needs beyond that, such as the motor cable length limit or the earth fault behaviour, is in the user manual for this range and not in the sales tables.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
ArmorPoint modules are installed by bridging two bases, which is why every mechanical figure in this family is stated with the base included rather than for the module alone.
Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied.
Of the 47 22C records carried here, these twelve stand closest to this catalog number. This page is 22C-B120A103.
Site tree: the AB Drives & Motors index carries 22C-B120A103 together with the other entries of the drive and motor group, which is where a catalogue walk usually starts. Reach it directly if the suffix on this record still needs confirming against a sibling.
Sources. Rockwell publishes the PowerFlex 400 user manual as 22C-UM001 and the technical data for the family as 22C-TD001. The ratings, terminal designations and ordering characters quoted on this page for 22C-B120A103 follow those two publications.