This page documents the 22C-B033N103, a PowerFlex 400 fan and pump drive. The number decodes position by position: 22C is the series, B fixes the 200...240 V AC three phase input, 033 is the rating code that sets 33.0 A and 7.5 kW (10 HP) in frame C, N is the enclosure (panel mount, IP20, NEMA/UL Type Open), and 103, the standard build ending used at both voltages and every frame closes the number.
| Position | Value |
| 1-3 | 22C, PowerFlex 400 adjustable frequency drive for fan and pump applications |
| 4 | B, 200...240 V AC three phase |
| 5-7 | 033, 33.0 A output current and 7.5 kW (10 HP), frame C |
| 8 | N, panel mount, IP20, NEMA/UL Type Open |
| 9-12 | 103, the standard build ending used at both voltages and every frame |
| Attribute | Value |
| Output current | 33.0 A |
| Motor rating | 7.5 kW (10 HP), variable torque fan and pump duty |
| Frame | C |
| Power terminal range, frame C | 8.4 mm2 (8 AWG) maximum, 1.3 mm2 (16 AWG) minimum, recommended torque 3.7 N.m (33 lb.in) |
| Input voltage | 200...240 V AC |
| Ambient, panel mount | 45 C (113 F) surrounding air, IP20 open and IP30 Type 1 |
The published table places this rating between 024: 24.0 A, 5.5 kW (8 HP), frame C; 049: 49.0 A, 11.0 kW (15 HP), frame D. When a fan or pump is re-rated, these are the two numbers the drive is compared with, and the frame letter in each case tells you whether the terminal block changes along with the current.
Direct links to the neighbouring ratings in this voltage class: 22C-B024, 22C-B049.
The same ratings exist as packaged numbers. The same ratings appear as packaged 23C catalog numbers with disconnect, circuit breaker and bypass configurations. The drive selection does not change; the short circuit protection, the enclosure and the factory wiring do. A panel builder comparing a bare 22C drive with a packaged number is comparing scope, not two different drives.
The 103 ending is the standard build. Every standard drive in the published selection tables ends in 103, at both voltages and across every frame, so the ending is not an option code. Options change it by adding characters, and those options are listed separately as user installed equipment. A number that does not end in 103 is therefore worth reading against that option list rather than against the rating table.
480 v input window in the tables. The 380...480 V AC drives carry a 340...528 V AC input window in the rating tables, wider than the voltage on the nameplate. A loaded transformer sagging to 350 V during a large fan start stays inside that window, and a site running near 500 V stays inside it too; a site above 528 V does not, and that is a transformer tap question rather than a drive question.
The duty this range was written for. The published range covers 3.0...350 HP at 480 V AC and 3.0...50 HP at 240 V AC, all three phase and all variable torque fan and pump duty. That is not a marketing description: the overload profile, the current tables and the built-in pump functions are all written for a quadratic load, and a constant torque load such as a positive displacement pump has to be sized outside those tables.
Interface options and the enclosure rating. Two interface options are published with the drives: a NEMA/UL Type 1 bezel for panel mounting and a NEMA/UL Type 4X/12 remote panel mount unit. The remote part lets an engineer stand at the fan during commissioning, and the bezel is what keeps a Type 1 rating intact after the interface is moved to the door.
Frame C in practice. Frame C is the frame that changes character with the enclosure code. It ships as IP20 open and reaches IP30 Type 1 only through a field installed conversion kit with a top cover and conduit box, and it is the only frame where flange mounting is available at the lower ratings. The terminal block takes up to 8 AWG at 3.7 N.m, so a 5 HP fan on a long run is a wire size question rather than a lug question.
The three decisions this number does not make. A catalog number fixes the drive, the frame and the enclosure rating. It does not fix the motor cable, the branch protection or the cabinet cooling. The publication sends those to separate documents: 22C-UM001 for terminal wire ranges and wiring practice, the protection tables for the 140M or 100-C device that pairs with the rating, and the ambient statement for the enclosure.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
A backplane in this family is commissioned in the order of the bases rather than by the wiring, and that is the difference between a field-wired rack and a sealed I/O system: there is no terminal strip to inspect, so the channel number a technician sees on the module face is derived from the position on the backplane and the mapping in the adapter. A module inserted one position off is not a wiring error that can be traced with a meter; it is a mapping error that appears as shifted channels.
ArmorPoint modules are installed by bridging two bases, which is why every mechanical figure in this family is stated with the base included rather than for the module alone. This page documents 22C-B033N103.
Figures on this page are the published 22C technical data for this catalog number. Where a value is not printed in that publication it is not printed here either, and no price, lead time or lifecycle statement is implied. This page documents 22C-B033N103.
Twelve of the 47 22C records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 22C-B033N103.
Group index: AB Drives & Motors. 22C-B033N103 is filed under that heading in the site's own product tree. Sibling codes of the same group are one click away from that page.